AMBIENT TEMP:

41C

DATE:

06-06-2012

TIME: 14 45

PARAMETER

TG 701

TG 702

LOAD ( MW)

13.3

13

P.F

0.88

0.88

MODE

DROOP

ISO

Turbine Side

WINDING TEMPERATURE

Generator Side

RTD 1 RTD 2 RTD 3 RTD 4

104

96

97

124

T / IN G / IN

EX

Turbine Side

Generator Side T / IN G / IN

RTD 5 RTD 13 RTD 14 RTD 15 RTD 1 RTD 2 RTD 3 RTD 4

114

57

83

77

82

61

83

80

EX

RTD 5 RTD 13 RTD 14 RTD 15

80

46

65

102

RTD-6

RTD-3
RTD-1

RTD-15

RTD-5
RTD-4
RTD-2
RTD-13

RTD-14
Turbine End

Collector End

Date

Ambient

TG-701

(At 1500
Hrs)

(C)

RTD 1

RTD 2

RTD 3

1-Jun-01

44

94

86

80

84

87

50

86

70

11.7

1-Jun-02

40

98

89

83

87

89

51

87

72

11.8

1-Jun-03

43

100

91

84

88

90

52

88

73

11.2

1-Jun-04

41

114

82

77

128

83

45

78

12

1-Jun-05

40

103

12.6

1-Jun-06

1-Jun-07

1-Jun-08

40

95

13

1-Jun-09

40

103

93

87

103

93

41

91

68

15

1-Jun-10

43

108

96

98

108

99

46

95

74

13

1-Jun-11

34

97

88

90

103

93

40

80

70

12.6

1-Jun-12

44

110

102

104

128

122

65

89

84

13.5

RTD 4 RTD 5 RTD 13 RTD 14 RTD 15

Load(M
W)

Date

Ambient

TG-702

(At 1500
Hrs)

(C)

RTD 1

RTD 2

RTD 3

1-Jun-01

44

1-Jun-02

40

92

87

90

88

90

55

11.9

1-Jun-03

43

93

87

91

89

91

56

11.9

1-Jun-04

41

92

86

91

89

90

57

72

12

1-Jun-05

40

91

86

90

88

89

56

71

88

12.3

1-Jun-06

1-Jun-07

1-Jun-08

40

83

74

83

81

82

47

57

94

13

1-Jun-09

40

84

74

85

83

83

46

60

97

14.3

1-Jun-10

43

86

75

87

85

85

51

67

100

13.7

1-Jun-11

34

75

63

76

73

74

41

58

93

11.7

1-Jun-12

44

87

66

88

86

86

51

70

107

13.1

RTD 4 RTD 5 RTD 13 RTD 14 RTD 15

Load(M
W)

Fatima

FFBL

Date

05.06.12

05.06.12

Time

1500 HRS

1500 HRS

Make

BRUSH

GE

MW (Rating)

26 MW / 26 MW

26 MW / 26 MW

MW(Running)

10 MW / 10 MW

10 MW / 10 MW

WINDING Temp.

80 C

70 C

Alarm / Tripping

130 C / 150 C

130 C / 150 C

Inlet / Outlet

48 C / 65 C

37 C / 52 C

Description

Due to improper heat transfer/ Dissipation Stator


Winding Temperatures of TG 701 are on higher side
Air Passage should be looked into for proper flow
Inspection and Cleaning of stator/ rotor should be
carried out
Major overhauling of Generator TG 701 is required