TRANSFORMER TEST REPORT

Transformer Manufactured by: Rating 63 KVA HV(KV) L.V(K.V) M/S Maa Ugratara Transformer Pvt.Ltd. Nizigarh Kuhuri,Tangi, Phases 3 3 No Load Voltage 11000 433 Order for - Subhashree Construction Co. ltd, Jharapada, BBSR Full Load in Amp 3.33 84 Date for Testing 07.07.2012 Full Load in Amp/Ph 1.90 84 Specification IS 2026 Connection: DELTA STAR Sl No Bee/MUT/63/62 Vector Group: DYn11 Year of Manufaturing 2012 Wound: Aluminium NO LOAD VOLTAGE RATIO ( % VARIATION FROM -DETERMINED THORITICAL RATIO 8.80X5) TAP POSITION 1 2 3 4 5 8 (+5%) (+2.5%) N (-2.5%) (-5%) (-7.5%) (-12.5%) (-15%) U-V 0.30 V-W 0.40 W-U 0.20 POLARITY OK 3) Vector GroupOK Oil Temp.OIL TEMP 30 C D.C RESISTANCE (NORMAL TAP) H.V (OHM) L.V(m-ohm) U.V. 28.08 U.V. 29.64 V.W 28.12 V.W. 29.61 W.U. 28.11 W.U. 29.63 Avg. / phase 42.15 Avg./Phase 14.82

NO-LOAD TEST(NORMALTAP)
Applied Voltage NO. load current 433V 0.95 A LOAD TEST (AT NORMAL TAP) Applied Current IMP.VOL 3.33 A 491 V 1.66 A 248 V CTR 1 WMF 1

WATTMETER READING IN WATTS


TMF 1 W-1 85 W-2 27 W-3 18 TOTAL LOSS 130 Watt

(WATTMETER READING IN WATTS) OIL TEMP 30 C W-1 W-2 W-3 CTRWMF TMFLOSS 284 285 282 1 1 1 851watt 71 73 71 1 1 1 215watt IR loss at Test . For full load 782 Watts %Imp at Test Temp. 4.46 Load loss at test Temp for full load 851 Watts % Resistance at Test Temp. 1.35 Stary Loss at Temp Temp. 69 Watts % Reactance 4.25 iR loss at Test 75c 920 Watts % Resistance at 75c 1.55 Stray loss at 75c 58 Watts % Impedance at 75c 4.52 Load loss at 100% @75C 978 Watts Load Loss at 50%load @75C 247 watt Over Voltage Power Frequency Separate Source Voltage Test f 60 Seconds Leakage Current current H.V. 28 (K.V) (WITHSTOOD).. mA 18 mA L.V 3(KV) .V ( 3(KV) L WITHSTOOD).2mA. (WITHSTOOD)2mA Induced Over Voltage Test -0.866KV applied on L.T for60Seconds of 100Hz & WITHSTOOD Measurement of INSULATION Resistance:- Insulation Test volts , Make - WACO, Sl No H.V to L.V 3000 M-ohms H.V to E 1500 M-ohms L.V to E 1000 M-ohms DI- ELECTRIC STRENGTH OF TRANSFORMER OIL The oil of the above Transformer WTHSTOOD ..60 K.V RMS Pressure Test - OK E.M.R SEAL NO- A194273 Testing Engineer A194274 INSPECTING OFFICER OF CESU M/S Maa Ugratara Trans Pvt Ltd

You might also like