Low Forward Power Protection The Generator will run still since there some steam trapped in Turbine.

This suitation is called Low Forward Power since there is not enough Steam to run the Generator in desired speed.This occurs because of some trapped steam in turbine for some seconds.Now Days special vents doors are designed in turbine to release these steam on account of tripping of turbines. But Normally in protection Trip Logic of Generators there will be Class:A,Class:B,Class:C For Class A Gen Breaker will trip for below faults U/V Stage-2 , O/V , Low Forward Power,Reverse Reactive power,Neg Ph Seq ,Over Voltage. For Class B Turbine Breaker will Trip which also trip Gen breaker instantly for below faults. Differential protection , Restricted Earth Fault ..... For Class C Grid Breaker will trip for below faults Over Frequency and Under Frequency Under Voltage stage-1 and Over voltage. Because when you trip Gen Breaker for Undervoltage it will result in whole plant black out so for stage-1 tripping of grid breaker will do.similarly for All turbine faults the Gen Breaker is tripped so that it is isolated from the system.