BFP With VFD: G. Rozario
BFP With VFD: G. Rozario
G. ROZARIO
6.6 KV Break er VFD FAULT ALARM VFD READY TO START VFD TRIP FEEDBACK SEVERE FAULT
BFP - VFD
6.6 KV Break er
QS1
0 100%
QS4 QS6
QS3 QS2
BFP-1 VFD MODE DOL BFP-1 MODE BFP-1 AMPS BFP DISCH 125 KSC
VFD
SPEE D AMPS LOAD QS5
BFP-2 VFD MODE DOL BFP-2 MODE BFP-2 AMPS
BFP -1
BFP FEEDWATER
BFP -2
172 TPH
&
BFP-1 VFD START PERMISSIVE TO START FROM DCS VFD Ready to Start Available VFD Fault / Trip is not present QS1 & 2 Close Feedback present BFP-1 Ready to start Permissive O N
&
C o m m a n d
&
BFP -1 START PERMISSIVE AVAILABLE BFP -1 DOL MODE (QS-1 & 2 OPEN ) & QS3 (CLOSED)
&
RESENT BFP-1
PROCESS PROTECTIO
1. BALANCE LEAK OF PRESSURE HIGH =7 KSC. 2. SUCTION PRESSURE LOW =1.5KSC. 3. DEAERATOR LEVEL LOLO ( 40%) 4. LUBE OIL PRESSURE LOLO = 0.4 KSC. 5. TEMP OR VIBRATION HIGH.
O R
&
VFD OFF
AUTO STANDBY
BFP 2 START REQ BFP-1 PROTECTION ACTED BFP-2 DOL MODE(QS4 OPEN & QS6 CLOSED) BFP2 AUTO SELEC BFP2 REMOTE
OR
&
&
&
OR
BFP1 RUNNING FB BFP-1 DOL MODE (QS1 OPEN) DISCH HDR PR LOW <120 BAR BFP2 STANDBY SELECTED
&
OR
QUESTION : 1.AT PRESETN IN CASE OF BFP PROTECTION ACTED BREAKER IS OPENED BY DCS, BUT AFTER VFD INSTALLATION EITHER DCS WILL OPEN THE BREAKER OR IT GIVES OFF COMMAND TO VFD ? 2.WHAT ABOUT RUN OUT PROTECTION? 3.AS VFD IS NOT AN INTELLIGENT DEVICE LIKE DCS AND IT GIVES ON (6.6KV BREAKER) / OFF COMMAND BASED ON ISOLATOR FEEDBACKS, BUT HOW WE CAN ENSURE PROTECTION ? 4.IF OPERATOR GIVES LOW FREQUENCY SETPOINT THAN OPERATING FREQUENCY ,WHAT IS THE BEHAVIOUR OF VFD / WHICH ONE IT WILL TAKE?
THANK YOU