BFP WITH VFD

G. ROZARIO

6.6 KV Break er VFD FAULT ALARM VFD READY TO START VFD TRIP FEEDBACK SEVERE FAULT

BFP - VFD

6.6 KV Break er

QS1

0 100%

QS4 QS6

QS3 QS2
BFP-1 VFD MODE DOL BFP-1 MODE BFP-1 AMPS BFP DISCH 125 KSC

VFD
SPEE D AMPS LOAD QS5
BFP-2 VFD MODE DOL BFP-2 MODE BFP-2 AMPS

BFP -1
BFP FEEDWATER

BFP -2

172 TPH

BFP-1 READY TO START PERMISSIVE INTERLOCK TO VFD


Lube oil pressure healthy >1KSC. De-aerator level normal (Individual Transmitter) + 200 mmwc (60%). Suction pressure is healthy > 1.85 (LOW 1.5KSC) Vibration / temperature normal. Discharge MOV closed or if it is auto
BFP1 Rea dy to Start Per miss ive inter lock to VFD

&

BFP-1 VFD START PERMISSIVE TO START FROM DCS VFD Ready to Start Available VFD Fault / Trip is not present QS1 & 2 Close Feedback present BFP-1 Ready to start Permissive O N

&

C o m m a n d

BFP-1 READY TO START PERMISSIVE DCS


Lube oil pressure healthy >1KSC. De-aerator level normal (Individual Transmitter) + 200 mmwc (60%). Suction pressure is healthy > 1.85 (LOW 1.5KSC) Remote selection. Vibration / temperature normal.
BFP1 Rea dy to Start Per miss ive

&

DOL START FROM DCS

BFP -1 START PERMISSIVE AVAILABLE BFP -1 DOL MODE (QS-1 & 2 OPEN ) & QS3 (CLOSED)

&

START PERMISSIVE ENABLE

BFP PROTECTION WITH VFD

RESENT BFP-1

PROCESS PROTECTIO

1. BALANCE LEAK OF PRESSURE HIGH =7 KSC. 2. SUCTION PRESSURE LOW =1.5KSC. 3. DEAERATOR LEVEL LOLO ( 40%) 4. LUBE OIL PRESSURE LOLO = 0.4 KSC. 5. TEMP OR VIBRATION HIGH.

O R

BFP PROT ECTIO N ACTE D

BFP PROTECTION = ADDING VFD


BFP1 VFD MODE (QS1 CLOSED) BFP -1 PROTECTION ACTED

&

VFD OFF

AUTO STANDBY

BFP 2 START REQ BFP-1 PROTECTION ACTED BFP-2 DOL MODE(QS4 OPEN & QS6 CLOSED) BFP2 AUTO SELEC BFP2 REMOTE

OR

&

BFP2 STAR T CMD

&

PRESENT AUTO STANDBY BFP 1 RUNNING / BFP2 STANDBY


BFP1 ELEC TRIP FB BFP2 STANDBY SELECTED

&

OR
BFP1 RUNNING FB BFP-1 DOL MODE (QS1 OPEN) DISCH HDR PR LOW <120 BAR BFP2 STANDBY SELECTED

BFP2 STAR T REQ

&

BFP 1 STOP FB BFP2 STOP FB BFP2 RUN SELECTION &

OR

BFP2 START REQ

QUESTION : 1.AT PRESETN IN CASE OF BFP PROTECTION ACTED BREAKER IS OPENED BY DCS, BUT AFTER VFD INSTALLATION EITHER DCS WILL OPEN THE BREAKER OR IT GIVES OFF COMMAND TO VFD ? 2.WHAT ABOUT RUN OUT PROTECTION? 3.AS VFD IS NOT AN INTELLIGENT DEVICE LIKE DCS AND IT GIVES ON (6.6KV BREAKER) / OFF COMMAND BASED ON ISOLATOR FEEDBACKS, BUT HOW WE CAN ENSURE PROTECTION ? 4.IF OPERATOR GIVES LOW FREQUENCY SETPOINT THAN OPERATING FREQUENCY ,WHAT IS THE BEHAVIOUR OF VFD / WHICH ONE IT WILL TAKE?