P500P3/P550E3: Output Ratings Ratings and Performance Data
P500P3/P550E3: Output Ratings Ratings and Performance Data
P500P3/P550E3: Output Ratings Ratings and Performance Data
com
P500P3/P550E3
Image for illustration purposes only. Output Ratings Generating Set Model 380-415V,50Hz Prime* Standby* 550.0 kVA / 440.0 kW - / Ratings and Performance Data Engine Make & Model: Alternator manufactured for FG Wilson by: Alternator Model: Ratings at 0.8 power factor. Control Panel: Base Frame: Circuit Breaker Type: Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25C (77F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Frequency: Engine Speed: RPM Fuel Tank Capacity:
litres (US gal)
Perkins 2506A-E15TAG2 Leroy Somer LL6114F PowerWizard 1 Heavy Duty Fabricated Steel 3 Pole MCCB 50 Hz 1500 928 (245.2) 60 Hz -
- Prime
97.2 (25.7)
Available Options FG Wilson offer a range of optional features to tailor our generating sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generating set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com
Width (W)
mm (in)
Height (H)
mm (in)
Dry
kg (lb)
Wet
kg (lb)
2143 (84.4)
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22. Generating set pictured may include optional accessories.
FG Wilson has manufacturing facilities in the following locations: Northern Ireland Brazil China India USA
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network. To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com
Engine Technical Data No. of Cylinders / Alignment: Cycle: Bore / Stroke: mm (in) Induction: Cooling Method: Governing Type: Governing Class: Compression Ratio: Displacement: l (cu. in) Moment of Inertia: kg m (lb/in) Engine Electrical System: - Voltage / Ground - Battery Charger Amps Weight: kg (lb) - Dry - Wet 24/Negative 70 1633 (3600) 1714 (3779) 6 / In Line 4 Stroke 135.0 (5.3)/167.0 (6.6) Turbocharged Air To Air Charge Cooled Water Electronic ISO 8528 G2 16.0:1 15.2 (927.6) 4.29 (14660)
Air Systems Air Filter Type: Combustion Air Flow: m/min (cfm) - Prime - Standby Max. Combustion Air Intate Restriction: kPa (in H2O)
50 Hz
60 Hz
Cooling System Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil:
kW (Btu/min)
50 Hz 38.3 (10.1)
60 Hz -
Centrifugal
- Prime - Standby
47.0 (2673) 49.0 (2787) 16.0 (21.5) 660.0 (23308) 125 (0.5)
Radiator Fan Load: kW (hp) Performance Engine Speed: rpm Gross Engine Power: kW (hp) - Prime - Standby BMEP: kPa (psi) - Prime - Standby 2471.0 (358.4) 2717.0 (394.0) Lubrication System Oil Filter Type: Total Oil Capacity: l (US gal) Oil Pan: l (US gal) Oil Type: Fuel System Fuel Filter Type: Recommended Fuel: Fuel Consumption: l/hr (US gal/hr) 110% Prime 50 Hz 60 Hz Load 106.8 (28.2) 100% Load 97.2 (25.7) 75% Load 73.6 (19.4) 50% Load 50.4 (13.3) Replaceable Element Class A2 Diesel Exhaust System Silencer Type: Silencer Model & Quantity: Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction Level: dB 110% Standby 50 Hz 60 Hz Load 100% Load 106.8 (28.2) 75% Load 80.7 (21.3) 50% Load 55.0 (14.5) Maximum Allowable Back Pressure:
kPa (in Hg)
50 Hz 1500
60 Hz -
Radiator Cooling Airflow: m/min (cfm) External Restriction to Cooling Airflow: Pa (in H2O)
Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local FG Wilson Dealer for power ratings at specific site conditions.
Eco, Full Flow 62.0 (16.4) 53.0 (14.0) API CI4 15W-40 Water
50 Hz Industrial
60 Hz
Exhaust Gas Flow: m/min (cfm) - Prime - Standby Exhaust Gas Temperature: C (F) - Prime - Standby 514 (957) 528 (982) 81.0 (2860) 87.0 (3072) -
(Based on diesel fuel with a specific gravity of 0.84 and conforming to BS2869, Class A2)
Alternator Physical Data Manufactured for FG Wilson by: Model: No. of Bearings: Insulation Class: Winding Pitch Code: Wires: Ingress Protection Rating: Excitation System: AVR Model: Leroy Somer LL6114F 1 H 2/3 - 6 12 IP23 SHUNT R450M
Alternator Operating Data Overspeed: rpm Voltage Reguation: (Steady state) Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW (Btu/min) - 50 Hz - 60 Hz 26.7 (1518) 2250 +/- 0.5 50 2.0% 2.0%
Suppression is in line with European Standard EN61000-6
50 Hz
415/240V 400/230V 230/115V 200/115V 380/220V 220/110V 220/127V
60 Hz
Data Item
Motor Starting Capability* kVA Short Circuit Capacity** % Reactances: Per Unit Xd X'd X"d 2.850 0.150 0.103 3.070 0.160 0.111 3.400 0.180 0.123 2.330 0.120 0.084 300 300 300 300 1296 1213 1106 1438
Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor. **With optional permanent magnet generator or AREP excitation.
Prime: kVA
550.0 550.0 550.0 550.0 506.0 550.0 550.0
Voltage kW
440.0 440.0 440.0 440.0 404.8 440.0 440.0
Standby: kW
General Information
Documentation A full set of operation and maintenance manuals and circuit wiring diagrams.
Generating Set Standards The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company.
Warranty All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.
FG Wilson has manufacturing facilities in the following locations: Northern Ireland Brazil China India USA
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network. To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com
In line with our policy of continuous product development, we reserve the right to change specification without notice P500P3 / P550E3/4PP/0910/GB