Tripping Characteristic Manual Motor Starter MS 495 57... 75A
Tripping Characteristic Manual Motor Starter MS 495 57... 75A
M50 001
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Overload release
Tripping characteristic with three pole load and two pole load based at cold state at any setting. With three pole load and two pole load and currents higher than 3 times of current setting the tolerance of the tripping time is +-20%. DIN VDE 0165, IEC 60079-14, EN 50019+A1...A5. The tripping time of the short-circuit release and the damage curve of the overload release are based on the max. rated operational current. Maximum permissable fuse if the rated short-circuit breaking capacity is exceeded
Die Weitergabe und Vervielfltigung dieser Unterlage, sowie die Verwertung und Mitteilung ihres Inhaltes ist nicht gestattet, soweit nicht ausdrcklich zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle Rechte vorbehalten, besonders fr den Fall der Patenterteilung oder OEM-Eintragung.
Tripping time Multiples of current setting 3x 4x 5x 6x 7,2x 8x three pole load 41,7 sec. 23,9 sec. 15,0 sec. 11,0 sec. 8,0 sec. 6,8 sec. two pole load 35,0 sec. 19,0 sec. 13,0 sec. 9,4 sec. 6,8 sec. 5,8 sec. Short-circuit release
Tripping time
Seconds