Mohammed Sanaobar, LBE TC Dubai, 25.06.08
AGENDA THE EIFS / ETICS SYSTEM WHY EIFS / ETICS? MOST IMPORTANT COMPONENTS NORMS AND REGULATIONS CRITICAL FACTORS EOTA WALL CASE STUDY CHINA COST MODEL
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 1
adhesive
substrate
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 2
WHY EIFS / ETICS? POSSIBILITIES FOR ENERGY SAVING: EIFS MAIN LEVER
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 3
WHY EIFS?
EIFS has proved to have a superior energy efficiency by reducing heat transmission by approx 50% Improved energy efficiency helps to reduce harmful emissions typically associated with energy production such as CO2 emissions and other by-products Design Flexibility and Decorative Finishing Superior EIFS energy efficiency reduces required air conditioning equipment capacity and limits the physical effects of temperature fluctuations hence reducing structural stress EIFS can be applied to new and existing structures. EIFS is the ONLY solution for insulating existing buildings
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 4
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 5
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 6
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 7
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 8
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 9
base coat
EPS
x 3000 times
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 10
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 11
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 12
t igh we
Min. req..
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 13
MOST IMPORTANT COMPONENT BASECOAT MORTAR IMPACT TEST WITH 500 GRAM STEAL BALL
e. g.
RD
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 14
e. g. 1%
4%
R D P
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 15
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 16
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 17
MINERALWOOL ( MW )
0,033
0,028 - 0,031
0,040
20 - 250
8 - 250
B1 or B2 14
B1 or B2 20
Flame proof
8 - 500
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 18
MOST IMPORTANT COMPONENTS FLAMMABILITY STANDARDS CLASSIFICATION AS PER EN 13501-1: May 2007
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 19
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 20
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 21
source ETAG 004 Edition 2004 PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 22
source WDVS in anderen Klimazonen by Dr. Knzel PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 23
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 24
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 25
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 26
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 27
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 28
TESTING THE EFFECTS OF EIFS UNDER PRACTICAL CONDITIONS IN DIFFERENT CLIMATIC ZONES IN CHINA
50
Hot Humid Summer Shanghai & Cold Winter Area Tropic Climate Guangzhou Area
North
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 29
ONE YEAR MODEL HOUSE PROJECT WITH CHINESE UNIVERSITIES PROVES EFFECTIVENESS OF EXTERIOR INSULATION FINISHING SYSTEMS
Beijing North
Aim Aim
Prove effectiveness of EIFS to the Chinese building Prove effectiveness of EIFS to the Chinese building industy under the existing climatic conditions industy under the existing climatic conditions
Approach Approach
Two identical model houses one with, one without Two identical model houses one with, one without EIFS in Beijing, Shanghai, Guangzhou EIFS in Beijing, Shanghai, Guangzhou Cooperation with Customers to build houses Cooperation with Customers to build houses Cooperation with the Universities Tsing Hua, Tongji Cooperation with the Universities Tsing Hua, Tongji and South China Science & Technology for data and South China Science & Technology for data collection and interpretation collection and interpretation Spreading message in seminars, media, to Spreading message in seminars, media, to associations, government etc. associations, government etc.
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 30
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 31
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 32
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 33
TEMPERATURE VARIATIONS INSIDE THE MODEL HOUSES WITH AND WITHOUT EIFS DURING THE COLD AND HOT SEASON IN CHINA
Temperature [degr. C]
20 18 16 14 12 10 8 6 4 2 0 -2 -4 -6 -8 -10 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
32 30 28 26
24 22 20 18 1 3 5
time/d
time/d
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 34
EIFS ACHIEVE CONSIDERABLE REDUCTION OF ENERGY USED TO HEAT AND COOL IN THREE DIFFERENT CLIMATIC ZONES
Average reduction of electricity consumption in %, Oct. 2002- Oct. 2003
50 40 30 20 10 0 Winter Summer
Beijing
Shanghai
Guangzhou
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 35
The Total Thermal Resistance = 0.104+0.03 = 0.17 m.K/W Total U value = 1/ 0.17= 5.8823 W/mk Heat loss = U * Area * dT( standard temp difference) = 5.8823* 200 * 17 = 20000
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 36
Thickness (m) U value (W/mk) 0.24 0.015 0.15 2.29 0.50 0.33
Thermal Resistance = 0.24/ 2.29 = 0.104 = 0.015/0.50 =0.03 = 0.15/ 0.33 = 0.45
The Total Thermal Resistance = 0.104+0.03 + 0.45 = 0.548 m.K/W Total U value = 1/ 0.548 = 1.71 W/mk Heat loss = U * Area * dT( standard temp difference)= 1.71* 200 * 17 = 5821
PERFORMANCE REQUIREMENTS AND STANDARDS FOR EIFS Mohammed Sanaobar, L-B-E-T/TC Dubai, 25-06-2008, Slide 37
COST MODEL ENERGY SAVING CALCULATION Conclusion: The Energy Saving between the two cases = 20000- 5821 = 14718 W In average you can save between 60-70 % of the heating oil required.