Current Ratings For Installation
Current Ratings For Installation
Installation in thermally insulated walls Installation method Cross-section, mm 1,5 2,5 4 6 10 10 16 25 35 50 70 95 120 150 185 240 300
2 2)
Installation in insulating tubes B1 B2 3 15,5 21 28 36 50 68 89 110 134 171 207 239 2 16,5 23 30 38 52 69 90 111 133 168 201 232 3 15,0 20 27 34 46 47,174) 62 80 99 118 149 179 206 2 17,5 24 32 41 57 76 101 125 151 192 232 269
A2 3 13,5 18,0 24 31 42 56 73 89 108 136 164 188 216 245 286 328 2 15,5 18,5 25 32 43 57 75 92 110 139 167 192 219 248 291 334
3)
Conversion factors for deviating ambient temperature, grouping, installation under the ceiling, multicore cables and insulated wires see DIN VDE 0298 part 4.
1) 2) 3)
The current ratings are valid for cables with concentric conductor, only for multicore versions for further installation methods see DIN VDE 0298 part 4 see DIN VDE 0298 part 4 4) not permitted for the installation on a wooden wall and not for application of the conversion factors, see DIN VDE 0298 part 4
T 20