Electrical Safety

You might also like

Download as ppt, pdf, or txt
Download as ppt, pdf, or txt
You are on page 1of 18

Potential Hazards with Neutral Conductors

Click to Advance

Neutrals Are Current Carrying Conductors


Neutrals are grounded but carry current under load. The source of neutral current cannot always be identified.

Click to Advance

Potential Hazards with Neutral Conductors


Breaking a neutral under load could create a shock hazard. Individuals contacting a lifted neutral potentially provide an alternate path to ground. A broken neutral or lifted neutral could result in a shock or an arc.

Click to Advance

Energized Neutral Examples


A neutral was misidentified and inadvertently opened creating an arc (ORPS EM-SR-WSRC-FTANK-20050009) A circuit was moved to a different distribution panel, but the neutral was spliced in the original panel (ORPS EMRL-PHMC-PFP-2005-0011) An electrician received a shock after lifting a neutral from its bus bar. The neutral received its power through an emergency light that received power from another distribution panel. (ORPS SC-PNSOPNNL=PNNLBOPER-2005-0018)

Click to Advance

Configuration That Requires Additional Precautions:

Click to Advance

Component labels
For the purpose of this presentation, please review the following labels: Circuit Breaker Circuit A Ungrounded Conductor Circuit B Ungrounded Conductor Grounded Conductor (Neutral Conductor) Ground Ballast / Fluorescent Light
Notes: 3 current carrying conductors in a raceway. Copper ground wire omitted for simplicity. Highlighted in yellow indicates energized.

Ballast / Fluorescent Light enclosure

Click to Advance

The Multi-Wire Branch Circuit is an acceptable configuration according to the National Electrical Code (NEC) Section 210.4.

Click to Advance

This circuit has also been referred to as:


The Edison Circuit Common Neutral Circuit

Shared Neutral Circuit

Click to Advance

These circuits are typically found on 120 / 240 volt single phase systems, but can be found on 208Y /120 and 277Y / 480 volt systems as well. The Grounded Neutral wire carries the unbalanced load current. (Grounded Conductor)

Click to Advance

Ckt A

Ckt B

Click to Lock Out Circuit Energize Circuits Click to B

The desired technique used to remove a device Is to cut the neutral The Neutral Will lead or disconnect Remain at leaving the device Ground a Potential neutral pigtail. (Click)
Ckt B

Ckt A

Ckt B

Ckt A

Click to Advance

Ckt A

Ckt B

If You Break The Neutral Bundle, It Will Become Energized From You May See an Arc Circuit A (Click) when disconnecting

Avoid Breaking The Neutral Bundle in a Multi-Wire Branch Circuit!

If You Contact The Neutral Conductor You May Feel A Shock.


Click to Advance

Use the following guidance when the neutral conductor must be interrupted: Treat the neutral as energized even though the circuit is locked out at the source. (Use PPE that is appropriate for the hazard, i.e. gloves and eye protection) Measure absence of voltage to ground immediately after lifting leads when more than one neutral is lifted from a device or when a splice is broken.

Click to Advance

Use the following guidance when the neutral conductor must be interrupted:
If known, Lock out both / all load breakers. If both circuit breakers in a multi-wire branch circuit are not known? o Test the neutral circuit with a clamp-on type current detector to identify if the neutral is carrying current before lifting neutral leads or breaking a neutral connection.

NOTE: Current will exist only if one or more circuits sharing the neutral have a load energized at the time of measurement.

Click to Advance

When a common neutral hazard is discovered at a device: Stop work and remove the hazardous condition or plan a new work package considering known energized conductors. It should be corrected by installation of pigtails or other means, to maintain continuity of the neutral wiring in accordance with NFPA 70 National Electrical Code.

Click to Advance

Other general precautions include:

Label the doors of lighting and power panels where common neutrals are known to exist. This will alert LOTO planners and workers of potential problems.

Click to Advance

Other general precautions include:

Provide instructions in work packages where common neutrals are known to exist to remind workers to be alert to wiring that may indicate a common neutral and to maintain neutral circuit continuity.

Click to Advance

Other general precautions include:

Suspect a multi-wire branch circuit when three or more neutral conductors are spliced together in a junction box, outlet box, or lighting fixture.

1 2

Click to Advance

Potential Hazards with Neutral Conductors

Questions or Comments?
Contact Bobby Gray or Jerald Kinz

Click to End Show

You might also like