Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

20.3/ 35 kV XLPE Yaltkanl, Bakr letkenli Orta Gerilim Enerji Kablolar 20.

3/ 35 kV XLPE Insulated, Copper Conductor Medium Voltage Power Cables

1 2 3 4 5 6 7 8

Yaps Bakr iletken yar iletken tabaka XLPE izole D yar iletken tabaka Yar iletken bant Bakr siper Koruma band PVC d klf YE3SV TEDA

Construction Copper conductor Inner semi conductive layer XLPE insulation Outer semi conductive layer Semi conductive tape Copper wire screen Protecting tape PVC outer sheath

Tip Standartlar

Code Standards Application

N2XSY IEC 60502-2

Kullanld yerler
Bu kablolardaki dielektrik kayplar kktr. Endstri blgelerinin ve yerleim merkezlerinin elektrik enerjisi ile beslenmesinde, yk art beklenen ebekelerde, dahilde, harite toprak altnda ve kablo kanallarnda kullanlr.

In this cables dielectric losses are low. Used in feeding urban and industrial region network, underground, indoor, outdoor, and cable channel applications.

Gerilim Deerleri
Anma gerilimi : Uo/ U= 20.3/ 35 kV

Voltages
Rated voltage : Uo/ U= 20.3/ 35 kV

Teknik Bilgiler
Maximum iletme scakl 90C Maximum ksa devre scakl 250C
Nominal kesit D ap yaklak Overall diameter approx. Net arlk yaklak 20C de iletken DC direnci ( Max. ) Conductor DC resistance at 20C ( Max. )

Technical Data
Maximum operating temperature 90C Short- circuit temperature 250C
alma indktans yaklak Operating inductance approx. Flat mH/km 0,77 0,75 0,71 0,68 0,66 0,64 0,62 0,60 0,58 0,55
Trefoil mH/ km

alma kapasitesi yaklak Operating capacity approx.

Akm tama kapasitesi* Toprakta Havada Boruda

Current carrying capacity in* Earth Air Duct

Nominal Cross- Section

Net weight approx.

mm2 1 x 35 / 16 rm 1 x 50 / 16 rm 1 x 70 / 16 rm 1 x 95 / 16 rm 1 x 120 / 16 rm 1 x 150 / 25 rm 1 x 185 / 25 rm 1 x 240 / 25 rm


1 x 300 / 25 rm 1 x 400 / 35 rm

mm 35 36 38 40 42 43 45 48 50 53

kg/ km 1370 1535 1800 2100 2400 2810 3220 3830 4450 5550

/ km 0,524 0,387 0,268 0,193 0,153 0,124 0,0991 0,0754 0,0601 0,0470

F/km 0,11 0,12 0,14 0,15 0,16 0,17 0,18 0,20 0,23 0,25

A 172 203 246 293 332 366 410 470 524 572

A 166 196 239 285 323 361 406 469 526 590

A 203 243 303 369 426 481 550 647 739 837

A 198 238 296 361 417 473 543 641 735 845

A 156 188 229 274 311 347 391 453 510 571

A 157 186 227 271 308 343 387 447 504 564

0,51 0,48 0,46 0,44 0,42 0,40 0,39 0,37 0,36 0,35

* Akm tama kapasiteleri toprak scakl 20C hava scakl 30C, 1.5 K.m/ W toprak sl direnci, 1.2 K.m/ W toprakta boru sl direnci ve 0.80 ykleme derecesi artlarnda geerlidir. * Current carrying capacity values given are rated at 20C earth temperature, at 30C free air temperature, 1.5 K.m/ W thermal resistivity of soil 1.2 thermal resistivity of earthenware ducts and 0.8 charging conditions.