MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A.

AND WATER
6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

6M.7 FIRE FIGHTING AND DETECTION SYSTEM Item No. Description 1. Fire protection water distribution (ring main) system 1.1 1.2 Design Code Total water flow to feed largest risk area 1.3 1.4 1.5 1.6 Design Pressure Design Temperature Operating Pressure Range Normal pressure in ring main 1.7 Pressure at which pressure maintaining device starts 1.8 Pressure at which first pump starts 1.9 Pressure at which second pump starts 1.10 1.11 Time delay between pumps Size of ring main pipe work for largest risk 1.12 Length of ring main pipe work 1.13 Number of fire hydrants supplied 1.14 1.15 Max Spacing of fire hydrants Number of outdoor hose storage cabinets supplied and locations 1.16 Max spacing of outdoor hose storage cabinets 1.17 1.17.1 Ring main pipe material: Fresh water above ground m m m Sec mm Bar Bar Bar Bar 12.5 C Bar Bar NFPA l/min 5000

Particulars

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No. 2. 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8

Description Fire Hydrant System Outdoor hydrants: Type/Model Number Manufacturer Design Codes/Class Quantity Max spacing of fire hydrants Size Discharge per hydrant outlet valve (2 Nos. 65 mm each) m 60 mm 150 l/min NFPA 24

Particulars

2.9 2.10 2.11 2.12 2.13 2.14

Design Pressure Design Temperature Operating pressure (in/out) Minimum operating pressure End style Operating nut size and threads

bar C bar bar

2.15 2.16 2.17

Body material Internal valve materials Fire engine connections (100 mm) No.

2.18

Fire hydrant auxiliary gate valve:

2.18.1 2.18.2 2.18.3 2.18.4 2.18.5 2.18.6 2.18.7 2.18.8 2.18.9 2.18.10

Type/Model Number Manufacture Design Code Quantity Size Body material Internal material Curb box size Curb box material Depth of cover 130 Cast Iron Shall be adjust to proper depth of pipe mm

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No. 2.19

Description Fire hydrant post indicator valves:

Particulars

2.19.1 2.19.2 2.19.3 2.19.4 2.19.5 2.19.6 2.19.7 2.19.8 2.19.9 3.

Type/Model Number Manufacturer Design Code Quantity Size Body material Internal materials Building/plant areas: Breeching inlet (No., size and threads) Standpipes and hose cabinet No/mm

Butterfly

3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 3.11 3.12 3.13 3.13.1 3.13.2 3.13.3 3.13.4 3.13.5 3.13.6

Type/Model Number Manufacturer Design Codes/Class Quantity Dimensions (LxWxH) Cabinet material/thickness Hose valves: Type/Model Number Manufacturer Design Pressure Quantity Material Fire hose: Reel Type Type/Model Number Manufacturer Design Codes/Class Quantity Length Material bar mm

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No. 3.14 3.14.1 3.14.2 3.14.3 3.14.4 3.14.5 3.14.6 3.15 3.15.1 3.15.2 3.15.3 3.15.4

Description Fire hose: Rack Type Type/Model Number Manufacturer Design Codes/Class Quantity Length Material Hose couplings: Type/Model Number Manufacturer Pressure rating Material

Particulars

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No.

Description

GOPH/ Gas Conditioning Building

Gas Turbine area

Diesel generator units

Others

4.

Automatic foam/water spray systems

4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6

General Foam concentrate type Manufacturer Design Code Mixture rate Specific gravity Maximum useable temperature
o

4.1.7 4.1.8

Quantity provided Guaranteed life

litres years

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No. 4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.2.5 4.2.6 4.2.7 4.2.7.1 4.2.7.2 4.2.7.3 4.2.7.4 4.2.8 4.2.8.1 4.2.8.2 4.2.8.3 4.2.8.4 4.2.8.5

Description
Diaphragm Pressure Proportioner Ratio controller Quantity Type/model No. Manufacturer Size Flow rate Diaphragm tank: Quantity Type/model No. Manufacturer Capacity Valves: Valve type Materials: Body Internals Seal litres

Gas Turbine area

Diesel generator units

Others

mm
l/sec

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No. 4.2.9 4.2.9.1 4.2.9.2 4.2.9.3 4.2.9.4 4.2.9.5

Description
Hydraulic/electric ball valves: Valve type Materials: Body Internals Seal Tenderer to indicate other areas provided with Diaphragm Pressure Proportioner System

Gas Turbine area

Diesel generator units

Others

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No 4.3
Balanced

Description

Particulars

proportioning equipment

4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.3.6 4.3.7 4.3.7.1 4.3.7.2 4.3.7.3 4.3.7.4 4.3.7.5 4.3.7.6 4.3.7.7 4.3.8

Ratio controller: Quantity Type/model No. Manufacturer Size Flow rate Proportioning control valve: Quantity Type/model No. Manufacturer Size Flow rate Pressure set points Material AFFF Foam Concentrate Storage tanks:

mm
l/sec

mm
l/sec

bar

4.3.8.1 4.3.8.2 4.3.8.3 4.3.8.4 4.3.8.5 4.3.8.6


4.3.8.7

Manufacturer Material Specification Dimensions Capacity Tank weight full Tank weight empty Tank material AFFF Foam concentrate pumps: kg kg

4.3.9 4.3.9.1 4.3.9.2

Number provided and rating (eg 2 x 100%) Type/Model number

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No 4.3.9.3 4.3.9.4 4.3.9.5 4.3.9.6 4.3.9.7 4.3.9.8 4.3.9.9 4.3.9.10 4.3.9.11 4.3.9.12 4.3.9.13

Description

Particulars

Manufacturer Rated Capacity Net positive suction head at rated capacity Maximum power absorbed by pump Discharge pressure at rated capacity Discharge pressure against closed valve Speed Pump inlet connection diameter Pump discharge connection diameter Weight Materials : rpm bar bar l/s

m
kW

mm mm kg

4.3.9.13.1 Casing material 4.3.9.13.2 Impeller material 4.3.9.13.3 Shaft material 4.3.9.13.4 Shaft sleeves material
4.3.9.14 4.3.9.15 4.3.9.16 4.3.9.17 4.3.9.18 4.4 Type of bearings Type of seals Type of coupling Motor type/manufacturer Motor Rated power Guaranteed life Portable fire extinguishers (Tenderer to schedule per building) Number of dry powder type provided

years

5.

5.1 5.2

Capacity of dry powder extinguishers

kg

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No 5.3 5.4 5.5 5.6 5.7 5.8

Description

Particulars

Number of carbon dioxide type provided Capacity of carbon dioxide extinguishers Number of water extinguishers Capacity of water extinguishers Number of foam type provided Capacity of foam extinguishers

kg

6. 6.1 6.2 6.3 6.4

Gas extinguishing system Gas turbine noise enclosure Type of gas used Volume of gas per discharge Number of cylinders (2 100%)

6.5 6.6

Duration of discharge Volume required to maintain concentration for required period Switchgear/electronic rooms

7. 7.1 7.2 7.3

Type of gas used Volume of gas per discharge Number of cylinders (2 100%)

7.4

Duration of discharge

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No 7.5

Description

Particulars

Volume required to maintain concentration for required period

8. 8.1 8.2 8.3

Panel injection Type of gas used Volume of gas per discharge Number of cylinders (2 100%)

8.4 8.5

Duration of discharge Volume required to maintain concentration for required period

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No.

Description

No. of Units and location

Approx. oil content of each unit (litres)

Oil conditions (press./ temp. & flash point o (bar/ C)

Envelope dimensions & area taken 2 (m & m )

Type of detector system

Number of Detectors per unit

Number and type of nozzles per unit

Minimum pressure at each nozzle (bar)

Nozzle discharge rate at min. pressure (l/s)

Theoretical Water quantity per unit (l/s)

Installed water quantity per unit (l/s)

9.

9.1 9.2 9.3 9.4

9.5

Automatic water spray deluge protection Generator transformers Unit transformers Other transformers 11 kV/415V auxiliary transformers Cable floors (list all areas)

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item Description No.

No. of Units and location

Envelope Type of dimensions detector & area taken system (m & m2)

Number of Detectors per unit

Number and type of nozzles per unit

Minimum pressure at each nozzle (bar)

Nozzle discharge rate at min. pressure (l/s)

Theoretical Water quantity per unit (l/s)

Installed water quantity per unit (l/s)

10.

Automatic wet pipe sprinkler systems

10.1

Store buildings

10.2

Others, if any:

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No.

Description

No. of Units/ Zones

Approx. oil content of each unit (litres)

Oil conditions (press./ temp. & flash point o (bar/ C)

Envelope dimensions & area taken 2 (m & m )

Type of detector system

Number of Detectors per unit

Number and type of nozzles per unit

Minimum pressure at each nozzle (bar)

Discharge rate of projector at min. pressure (l/s)

Theoretical Water quantity per unit (l/s)

Installed water quantity per unit (l/s)

11.

Automatic foam/water spray protection systems Balanced pressure proportioning systems: Gas oil pump house Others (list):

11.1

11.1.1 11.1.2

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No.

Description

No. of zones/ units and location

Approx. oil content of each unit (litres)

Oil conditions (press./ temp. & flash point o (bar/ C)

Envelope dimensions & area taken 2 (m & m )

Type of detector system

Number of Detectors per unit

Number and type of nozzles per unit

Minimum pressure at each nozzle (bar)

Discharge rate of projector at min. pressure (l/s)

Theoretical Water quantity per unit (l/s)

Installed water quantity per unit (l/s)

20.

Automatic foam/water spray protection systems (cont) Diaphragm pressure proportionin g systems: Emergency diesel generators and day tanks GT area lub.oil tanks & pipes GT Lub. oil system

11.2

11.2.1

11.2.2

11.2.3

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item No.

Description

No. of zones/ units and location

Approx. oil content of each unit (litres)

Oil conditions (press./ temp. & flash point o (bar/ C)

Envelope dimensions & area taken 2 (m & m )

Type of detector system

Number of Detectors per unit

Number and type of nozzles per unit

Minimum pressure at each nozzle (bar)

Discharge rate of projector at min. pressure (l/s)

Theoretical Water quantity per unit (l/s)

Installed water quantity per unit (l/s)

11.2.4

11.2.5

Generator Hydrogen seal oil system Gas Conditioning Building Others (List):

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.7 FIRE FIGHTING AND DETECTION SYSTEM

Item no.

Description

Room/area dimensions LxWxH metres

Storage rack dimensions metres

Enveloped volume 3 m

Size & No. of Gas Gas design Quantity type Nozzle Cylinders storage Concentration and discharge rate litres/No. capacity and % manufacturer at min. discharge of pressure duration nozzles ltr/sec litres/secs

Type and number of detector systems

12.

Gas extinguishing systems Areas protected to be listed by Contractor : Areas with total room flooding (unmanned areas) Areas with panel injection (manned areas)

12.1

12.2