Airport Lighting Cable

600 Volt and 5kV. Copper Conductor. XLP Insulation.

APPLICATIONS
Southwire Airport Lighting Cable is primarily used for series lighting circuits for runways, control systems, and other multi-purpose installations. It can be used for direct burial, conduit, or raceway. These cables are capable of operating continuously at a conductor temperature not in excess of 90C for normal operation, 130C for emergency overload conditions, and 250C for short circuit conditions. Voltage rating for conductors is 600 volts and 5,000 volts.

SPECIFICATIONS
Southwire Airport Lighting Cable meets or exceeds FAA Specification L-824, AC150/5345-7D, and ICEA S-66-524.

CONSTRUCTION
Southwire Airport Lighting Cable conductors are annealed (soft) copper, compressed 7 strand. 600V cable insulation is an abrasion, moisture, and heat resistant black cross-linked polyethylene. 5kV cable has an extruded semi-conducting cross-linked conductor shield with an abrasion, moisture, heat, and 20-mil track resistant cross-linked polyethylene insulation.

Thu May 12 16:43:44 EDT 2011

Page 1 of 2

Airport Lighting Cable


600 VOLTS Size (AWG)
12 10 8 6 4

Number of Strands
7 7 7 7 7

Insulation Thickness (mils)


60 60 60 60 60

Nominal O.D. (mils)


209 233 262 298 345

Approximate Net Weight Lbs./1000'


34 48 70 103 156

5,000 VOLTS Size (AWG) Number of Strands Insulation Thickness (mils)


110 110

Nominal O.D. (mils)


402 485

Approximate Net Weight Lbs./1000'


97 198

8 4

7 7

RECOMMENDED SAMPLE SPECIFICATIONS: Cable shall be FAA L-824, Type C, suitable for operation at 600 volts or 5kV in wet or dry locations. Conductors shall be annealed (soft) copper, compressed 7 strand. 600V cable insulation shall be abrasion, moisture, and heat resistant black cross-linked polyethylene. 5kV cable shall have a 20 mil extruded cross-linked polyethylene conductor shield. 5kV cable shall have an abrasion, moisture, heat, and track resistant cross-linked polyethylene. Cable shall be printed with conductor size, manufacturer, voltage, and FAA-L-824, Type C.