Product data sheet

Characteristics

16434

PRD-DC 40r 600PV modular surge arrester - 2 poles - 600V - with remote transfer

Main
Range of product Product or component type Device short name Poles description Remote signalling Signal contacts composition Surge arrester type PRD-DC Surge arrester with removable cartridge PRD-DC 40r 600PV 2P With 1 SD (1 C/O) Electrical distribution network

Complementary
Surge arrester class type Surge arrester technology [Ue] rated operational voltage Nominal discharge current Maximum discharge current [Uc] maximum continuous operating voltage [Up] voltage protection level Type 2 MOV + GDT 600 V DC 15 kA 40 kA Common mode: 600 V L/PE Differential mode: 840 V L+/L1.6 kV type 2 common mode L+/PE 1.6 kV type 2 common mode L-/PE 2.8 kV type 2 differential mode L+/LFlag color: white/red AC: 250 V 50/60 Hz 0.25 A Fixed 35 mm symmetrical DIN rail 6 81 mm 54 mm 69 mm 0.4 kg Grey ( RAL 7035 ) <= 25 ns Tunnel type terminal downside 2.5...35 mm Tunnel type terminal upside 2.5...35 mm 2.5 N.m

Local signalling Signalling circuit voltage Signalling output current Mounting mode Mounting support 9 mm pitches Height Width Depth Product weight Colour Response time Connections - terminals Tightening torque

Environment
Standards EN 61643-11 IEC 61643-1 UTE C 61740-51 PrEN 50539-11 CE On front face: IP40 On terminal: IP20 IK03 5...90 % 2000 m

Quality labels IP degree of protection IK degree of protection Relative humidity Operating altitude
Jan 17, 2013

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Ambient air temperature for operation Ambient air temperature for storage RoHS EUR status RoHS EUR conformity date

-25...60 C -40...85 C Compliant 1001