NOTES
LINES
A
PIPING SYMBOLS
NOTES:-
GENERAL
LINES IDENTIFICATION PROCESS/UTILITY LINE BASKET STRAINER ELECTRICAL LINE INSTRUMENT GAS/ PNEUMATIC LINE ELECTRICAL TRACED LINE CHECK VALVE UNION VENDOR LIMIT LINE CENTER LINE INSULATION JOINT
L L L L
GATE VALVE
B
GLOBE VALVE
BURIED
FLAME ARRESTOR
1. HIGH POINT VENT AND LOW POINT DRAIN NOT SHOWN ON P&ID SHALL BE SHOWN ON PIPING ISOMETRIC / GENERAL ARRANGEMENT DRAWINGS .
ST
STEAM TRAP
ANGLE VALVE
2. ALL SAFETY VALVES DISCHARGE & EQUIPMENT DEPRESSURIZING LINES SHALL BE FREE DRAINING
CAPILLARY LINE
BUTTERFLY VALVE
3. ALL ISOLATION VALVES IN TAPPINGS OF INSTRUMENTS (SUCH AS PRESSURE, LEVEL AND FLOW SWITCHES) CAUSING SHUTDOWN SHALL BE LOCKED OPEN.
PLUG VALVE
4. LINE NUMBERS SHALL BE INDICATED AS PER LINE LEGEND. 5. ALL INSTRUMENTS SHALL BE PROVIDED WITH ISOLATION VALVES FOR MAINTENANCE PURPOSE. IT SHOULD BE ENSURED THAT THESE VALVES SHALL BE EASILY ACCESSIBLE.
B
o o o
BALL VALVE SS TUBING (PROCESS) NEEDLE VALVE SCOPE OF WORK/LINE RATING CHANGE (WITH PIPING SPEC. DESIGNATION)
THREE WAY CONTROL VALVE FLOW ELEMENT ORIFICE/ RESTRICTION ORIFICE SPRING LOADED VALVE TURBINE METER DIAPHRAGM VALVE CONTINUOUS DRAIN
6. DRAINS OF LEVEL INSTRUMENTS (NON-SOUR SERVICES) SHALL BE PIPED TO NEAREST DECK DRAIN FUNNEL WITH 1/2" TUBE PIPE.
7. FOR PUMPS HANDLING SWEET LIQUID, CASING VENTS, DRAINS AND BASE PLATE DRAINS SHALL
BE PIPED WITH VALVE TO NEAREST DECK DRAIN FUNNEL. CASING DRAINS AND VENT FOR PUMPS IN SOUR SERVICE SHALL BE PIPED TO CLOSED DRAIN HEADER RESPECTIVELY.
LOCALLY MOUNTED CONTROL VALVE LOCAL PURGED CONTROL VALVE WITH HAND WHEEL PANEL MOUNTED / CENTRAL CONTROL PANEL SELF ACTUATED PCV (DOWN STREAM)
C
S
SILENCER
10. ALL LIQUID SAMPLE POINTS EXCEPT FOR WELL FLUID SAMPLES SHALL BE TAKEN FROM CENTER OF
SONIC METER
JOHANUSMIRECFT
ELECTRIC MOTOR
SAMPLE POINT
11. INSTRUMENT ISOLATION VALVES SHALL BE AS PER DETAILS GIVEN BELOW. ALL VALVES SHALL
DIAPHRAGM SEAL BACK PANEL MOUNTED HAND OPERATED VALVE BACK LOCAL PANEL PISTON OPERATED VALVE COMPUTER FUNCTION
M
BE AS PER APPROPRIATE PIPING/INST. SPECS. DIAPHRAGM SEAL ALSO AS PER SPECS. ALL TAKE OFF CONNECTIONS SHALL BE SW (SOCKET WELD) UNLESS OTHERWISE SPEIFIED.
PSV 101
(TYPICAL FOR PI,PT,PIC,PSH,PSL,PSHL) COMPUTER LOCAL PANEL SHUT DOWN VALVE DCS/DIDC BALL CONTROL VALVE FUNCTION BLOCK
D
TAKE OFF CONNECTIONS- PIPING : 3/4", VESSELS : 1.5" FLANGED ALL DIAPHRAGM SEAL TYPE INSTR. TO HAVE 1.5" FLANGED TAPPING.
INSTR.
1/2"
PIPING
INSTR.
INTERLOCK
SPECIALITY ITEM
3/4"
FLEXIBLE HOSE
LO
PI
3/4"
3/4"
PI
PI
PI
RUNNING LIGHT,LOCAL
3/4" LO
PIPING
BLIND FLANGE RUNNING LIGHT,LOCAL PANEL SPECTACLE BLIND CAP (WELDED) SOLENOID VALVE(2 WAY) FLANGE
SHUT DOWN
INSTR.
1/2"
PDI
PDI
N2
E
LC/LO
NORMALY LOCK CLOSE INTERCHANGABLE TO LO (TYPICAL FOR PDI,PDT,PDSH,PDSL,PDSHL) TAKE OF CONNECTION-PIPING : 3/4", VESSELS : 1.5" FLANGED ESD/FSD VALVES
POSITIVE CHOKE
ADJUSTABLE CHOKE NC Y-TYPE STRAINER CONTROL VALVE W/POSITIONER FUSIBLE PLUG FOUR WAY VALVE NO NORMALLY OPEN NORMALY CLOSED
TS
QUICK EXHAUST VALVE
TEMPORARY STRAINER
1/2"
1/2"
28.02.06 DATE
RVG BY
SG CHD APPR.
NO.
ISSUE
PIPING & INSTRUMENTATION DIAGRAM (P&ID) FLOW SHEET & INSTRUMENT LEGEND
7045-OD-1002
REV.