Professional Documents
Culture Documents
How To Measure The Expansion Tanks For Heating Systems
How To Measure The Expansion Tanks For Heating Systems
How To Measure The Expansion Tanks For Heating Systems
THE FOLLOWING DATA HAVE TO BE KNOWN: 1. THE WHOLE VOLUME OF WATER OF THE PLANT INTO WHICH THE EXPANSION VESSEL HAS TO BE INSTALLED 2. MINIMAL AND MAXIMAL WORKING TEMPERATURES 3. THE VESSEL'S PRE-CHARGE PRESSURE 4. THE CALIBRATION PRESSURE OF THE SAFETY VALVE 5. THE POSSIBLE DIFFERENCE IN LEVEL (IN METERS) BETWEEN THE POSITION OF THE SAFETY VALVE AND THE POSITION OF THE VESSEL. TYPE A POSITIVE LEVEL IF THE VALVE IS HIGHER THAN THE VESSEL, TYPE A NEGATIVE LEVEL IF THE VALVE IS LOWER.
1 4 0 40
50
60
70
80
90
99
Coefficient of expansion of water with respect to a 10 C 0.0076 0.0118 0.0168 0.0224 0.0287 0.0357 0.0432 Minimal volume fo the vessel (liters) with respect to the maximal working temperature
500
6.3
9.8
14
18.7
24
29.7
36
THIS MEASURING IS VALID ONLY IF THE PRESSURE ON THE EXPANSION VESSEL IS NOT SUPERIOR TO THE PRECHARGE PRESSURE. PLAESE CONSIDER THAT A 10 METER WATER COLUMN MAKES A PRESSURE OF ONE BAR, AT SEA LEVEL. THE PRESSURE OF THE SAFETY VALVE, ADDED TO THE PRESSURE OF THE POSSIBLE DIFFERENCE IN LEVEL, MUST BE INFERIOR TO THE MAXIMAL WORKING PRESSURE OF THE VESSEL.
rev. 31/05/2002