Modbus Using CompactLogix 1769 SM2
Modbus Using CompactLogix 1769 SM2
Anish Shrivastava
Modbus Slaves
Modbus RTU Network
Modbus Cable
Conzerv EM6400
Before installing the module, make sure its Configuration Mode Switch is correctly set.
SW1 Setting
CONT (Controller) back position PARAM (Parameter) front position
Description
Default settingThe 1769-SM2 module uses the configuration data downloaded from the controller on power-up and when the controller is placed in run mode. The 1769-SM2 module uses its internal parameter settings to configure the module.
SW2 Setting
Single Position (For Single drive per channel) Multi-Drive Position (For Max 5 drives per channel or up 31 RTU slave devices per channel)
Notes
Slave Device ID, Function Code, Register Address and Length may vary according to the slave devices parameters. Please select the proper data for slave devices otherwise communication fails.
References
1769 SM 2 Module User Manual
(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1769-um013_-enp.pdf)