METHOD

Factor of load light: m = 1,05


Nominal tension between phase of the transformer: A = 400v
Factor of tension: c=1,05

Icc = (mcUn) / 3 Rt + Xt (KA)


Rt=R1+R2+R3 +..
Xt=X1+X2+X3 +..

Installation
Value to R consdrer in m.
Network Uphill

R1=

0,1*Zq

Reactance in m.
X1=
Zq=

Transformer

R2

(Wc*U / S) * 10EXP (-3)

X2=

Wc:losses coppers

Z=

S:Power of the transformer


in KVA
* L/S
= 18,51 (cu) 29,41 (Aluminum)
L in m and S in mm

X3=

Link cables

R3=

In Busbar

R3=

* L/S
X3=
= 18,51 (Loss) 29,41 (Aluminum)
L in m and S in mm

Breakers DP
fast
selective

R
R

negligible
negligible

CALCUL/1000 KVA
Skq = 500000 KVA
R1=

0.035 X1=

S=1000 KVA
Ukr=4%
U = 400v

R2=

1.248 X2=

Pcu = 7800 w

R3=

0.108 X3=

L=5m Transf---->BusBar

R4=

0.000 X4=

L=2m BusBar ---->Breakes DP

R5=

0.093 X5=

Rm
Xm

Icc in M1

Icc=

1.391
11.830

21.384 KA

CALCUL/1600 KVA
Skq = 500000 KVA

S=1600 KVA
Ukr=4%
U = 400v

R1=

0.035 X1=

R2=

0.840 X2=

R3=

0.108 X3=

R4=

0.000 X4=

R5=

0.093 X5=

Rm1=
Rm1=

1.076 Xm1=
1.158 Xm1=

Pcu = 8400 w
L=5m Transf---->BusBar
L=2m BusBar ---->Breakes DP

Icc in M1

Icc=

53.764 KA

Transformer
Reactance in m.
0,995*Zq
M1
(M*Un) / Skq
Breaker
Z2-R2
(Ucc/100) / (U / S)
Ucc: tension of
short circuit
0,15*L
L in m

,15*L
L in m

negligible
negligible

busbar

M2

0.35
11.13

0.05
0.00
0.30

Rm1=1,
Xm1=139,

0.351
3.911
0.050
0.000
0.300

4.612
21.269