FSSS
FSSS
Learning Agenda
Objective of FSSS Inter facing of field equipments and instrumentation Operational features of FSSS Role of FSSS in starting/shutdown Role of FSSS in maintaining the design prescribed values of the parameters
2 of 27
confidentia
It must be recognized that no amount of written instruction can replace intelligent thinking and reasoning on the part of boiler operators, especially when coping with unforeseen operating conditions. It is operators responsibility to become thoroughly familiar, not only with immediate steam generating equipment but also with all pertinent control equipment. Satisfactory performance and safety depend to a great extent on proper functioning of controls and auxiliary equipment.
3 of 27
confidentia
Purpose
The FSSS is designed to ensure the execution of safe, orderly operating sequence in the start up and shutdown of fuel firing equipment and to prevent errors of omission and commission in following such a safe operating procedure.
4 of 27
confidentia
Purpose
Furnace purge supervision. Secondary air damper modulation, on/off control and supervision. Light oil on-off control and supervision. Heavy oil on-off control and supervision. Pulveriser and feeder on-off control and supervision. Flame scanner intelligence and checking. Overall boiler flame failure protection. Boiler trip protection.
5 of 27
confidentia
Purpose
Prevent any fuel firing unless a satisfactory furnace purge sequence has first been completed. Prevent start-up of individual fuel firing equipment unless certain permissive, interlocks have been satisfied. Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment. Subject continued operation of fuel firing equipment to ascertain safety interlocks remaining satisfied.
6 of 27
confidentia
Purpose
Provide component status feedback to the operator and, in some cases, to the unit control system and / or to the data logger. Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination. Effect a Master Fuel Trip upon certain adverse Unit operating conditions.
7 of 27
confidentia
Subsystem of FSSS
Purge Permissive (s) HOTV Open/Close Interlocks HORV Open/Close Interlocks Oil Guns Start/Stop Cycle Boiler Protection Logics
8 of 27
confidentia
PA Fan Interlocks Coal Mill Start/Stop Interlocks Coal Feeder Start/Stop Interlocks Scanner Air Fans Seal Air Fans Secondary Air Damper Interlocks
9 of 27
confidentia
Purge Permissives
All HFO Nozzle Valves Closed HFO Trip Valve closed No Boiler Trip From MFR A & B All Pulverizers Off. All Feeders Off All Flame Scanners Sense No Flame Both PA fans Off
10 of 27
confidentia
All Auxiliary Air Dampers Modulating and furnace to wind box P OK All Hot Air Gates Closed Air Flow > 30 % Mode Permit Proven (Air Flow < 40% Burner Tilt Horizontal) Drum Level Satisfactory FSSS AC / DC Power Available.
11 of 27
confidentia
HOTV Interlocks
To Open HOTV : Permissives SET I
No. Boiler Trip persisting HFO Header temperature satisfactory >950 C HFO supply pressure > 15 Kg / cm2 All HONVs closed No close / Trip command Open PB depressed
12 of 27
confidentia
HOTV Interlocks
To Open HOTV : Permissives SET II
13 of 27
confidentia
HOTV Interlocks
1. HOTV closes automatically under the following conditions: Any HONV not closed AND a) HFO pressure low < 3 Kg/cm2 OR b) Atomizing steam pressure low < 3.5 Kg/cm2 OR c) HFO Header Temperature Lo-Lo for > 2 secs. < 95 0C 2. Any HONV not closed and MFT acted 3. Loss of critical power > 2 Seconds 4. HOTV can be closed manually
14 of 27
confidentia
HORV Interlocks
HORV can be opened by pressing the OPEN Push button (PB) from Console if All the HONV s are closed.
HORV closes automatically when any HONV is not closed OR by pressing close PB.
15 of 27
confidentia
HFO HTR-1
HFO PUMP-2
HFO HTR-2
TO BOILER FRONT
confidentia
CD ELEVATION M
SHORT RECIRCULATION
FT
EF ELEVATION
17 of 27
confidentia
AB ELEVATION
CD ELEVATION
EF ELEVATION
SCAVENGE VALVE
OIL GUN
confidentia
Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4) When pair 1-3 start push button is pressed; A 30 second counting period is started A 70 second counting period is started Oil Gun No-1 advances from retracted position if, it is engaged, corresponding scavenge valve is closed, atomizing steam and HFO isolation valves are open.
19 of 27
confidentia
HEA igniter advances. Atomizing steam valve opens. Igniter starts sparking. HFO Nozzle valve for corner 1 opens HFO catches fire and flame indication comes. After 25 seconds igniter retracts. When the 30 second counting period expires command will go to corner 3 and same events will take place. Corner 2-4 can also be placed exactly in the same manner.
20 of 27
confidentia
Elevation firing mode is selected when any feeder is proven. Oil elevation is placed in service when Pair 1-3 or Pair 2-4 start Push Button is pressed. In elevation firing mode also the oil guns are proven on pair basis. First command goes for placing Pair 1-3 into service and Pair 1-3 is placed into service exactly in the same way as in the pair mode.
21 of 27
confidentia
First start command goes to corner-1 then after 30 second start command goes to corner-3. After the start command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then start command goes for corner 2-4 and corner 2-4 are placed into service exactly in the same manner as in the pair mode.
22 of 27
confidentia
Pair firing mode is selected when no feeder is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4) When pair 1-3 stop push button is pressed the following events take place A 30 second counting period is started A 340 second counting period is started Oil Gun No-1 HFO nozzle valve closes. Scavenge and atomizing steam valve opens. HEA igniter advances and spark remains for 15 seconds.
23 of 27
confidentia
When atomizing steam valve is proven fully open, a 5 minutes counting period starts. When 5 minutes counting period expires scavenge valve and atomizing steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed. Oil Gun corner no-1 retracts to its home position. When the 30 second counting period expires stop command will go to corner 3 and same events will take place. Corner 2-4 can be shut-down exactly in the same manner.
24 of 27
confidentia
Elevation firing mode is selected when any feeder is proven. By pressing stop push-button of Pair 1-3 or Pair 2-4 the following events will take place. Corner 1-3 will be shut-down in the similar way as in the pair mode. When stop command has gone to corner 3, a 30 second counting period is started. When 30 seconds counting period expires then stop command goes for corner 2-4 and corner 2-4 are shut-down exactly in the same manner as in the pair mod
25 of 27
confidentia
Both FD Fans Off All ID Fans Off Inadequate Water Wall Circulation Loss Of Reheater Protection Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic) All Boiler Feed Pumps Off Drum Level High-High (> + 250 mm, delay of 10 seconds) Drum Level Lo-Lo (< - 375 mm, delay 10 seconds) Elevation Power Failure For > 2 seconds. Furnace Pressure High-High (> + 325 mmWCl, 2 / 3 logic)
26 of 27
confidentia
Furnace Pressure Lo-Lo (< -250 mmWC, 2 / 3 logic) Loss Of All Fuel Unit Flame Failure Loss Of Critical Power For > 2 seconds Loss Of 220 V DC For > 2 seconds Loss Of ACS Power > 2 seconds Simulated Trip Air Flow < 30 % Both Emergency Push Buttons Pressed.
27 of 27
confidentia
Boiler Trip
When the boiler trips the following events takes place
Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A fans are tripped.
28 of 27
confidentia
Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and can not be opened unless furnace purge is completed. Turbine Trips
29 of 27
confidentia
30 of 27
confidentia
Reheat Protection
1. Turbine trip or generator circuit breaker open and hp/lp bypass opening < 2 %. 2. Turbine working (hp & ip cvs opening > 2 % and load shedding relay operated and hp/lp bypass opening < 2 %. 3. Turbine not working and boiler working and hp/lp bypass opening < 2 %.
confidentia
31 of 27
MFT
5 SEC
Any elevation Nozzle valve proven All HFO Elevation Trip All feeders off
2 SEC
confidentia
2 Sec
Elevation FG No Flame Vote Elevation DE No Flame Vote Elevation BC No Flame Vote Elevation AB No Flame Vote
confidentia
2 Sec
2 Sec
Feeder A Off
2 Sec
confidentia
34 of 27
ELEVATION GH ANY HFO NOZZLE VALVE NOT CLOSED ELEVATION GH 2/4 NOZZLE VALVE NOT PROVEN
35 of 27
confidentia
Mill Interlocks
Start Permissive (s): Mill starts after the ON push button is pressed if following conditions are fulfilled. Pulveriser Ready available signal will be available if following conditions are fulfilled M.D.V. is open (all four) Mill outlet temp < 93 0 C Feeder local switch in Remote
36 of 27
confidentia
Mill Interlocks
Pulverizer start permit (if Nozzle tilt Horizontal & air flow < 40 %) OR Any feeder proven & NO MFT Tramp iron valve open Cold air gate open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing
37 of 27
confidentia
Mill Interlocks
P.A. permit available. (i) Hot P.A. duct Pressure. not low (< 625 mmWCl) (ii) P.A. duct pr. not lo-lo ( > 500 mmWCl AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON) No Auto pulverizer unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" WCl Mill not ON Pulverizer Ignition permit available.
confidentia
38 of 27
Mill Interlocks
FOR Mill A AB elevation 3/4 HONVs open OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.) For Mill B AB elevation proven 3/4 HONVs open OR Boiler load > 30 % and Feeder A or Feeder C proven.
39 of 27
confidentia
Mill Interlocks
For Mill C
CD elevation proven AB oil elevation and feeder B proven OR OR
For Mill D
CD elevation proven OR Boiler load > 30 % and either feeder C or feeder E proven. For Mill E,F,G & H identical logic
40 of 27
confidentia
confidentia
confidentia
confidentia
confidentia
confidentia
confidentia
SADC
The secondary air dampers located in wind box apportions the total secondary air between various elevations. How this air is proportioned, depends on which fuel is being burnt, the number of elevations in service and the firing rate at each elevation. The function of Secondary Air Damper Control System (SADC) is to proportion the total secondary air around the firing elevation as per the criteria spelt above. In fact the SADC system is a combination of both analog and digital system, as the amount of fuel fired and confidentia the no. of firing elevations decide the damper
47 of 27
The auxiliary air dampers are positioned to maintain the required wind box to furnace differential pressure according to the boiler load. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various wind box to furnace differential pressures and the values are to be optimized at site (the values are adjustable). Based on this, the final curve showing the relationship between the wind box to furnace differential pressure versus the boiler load is to be decided for the type of coal used.
48 of 27
confidentia
The auxiliary elevation dampers act as fuel (oil) air dampers when oil firing is taking place and is open to a preset position. The fuel (oil) elevation dampers are selected to be closed if there is a back up trip in that elevation and adjacent pulverizers are off and No Boiler Trip signal is present. When a HFO Elevation is started (i.e. when the associated elevation back-up trip is removed) the associated auxiliary air dampers in that elevation are set to preset position for HFO firing.
confidentia
49 of 27
Above 30% MCR boiler load, the auxiliary air elevation associated with the main fuel elevation in service modulate to maintain the varying DP. Those not associated with any elevation in service are closed from top to bottom. The closing signal comes from FSSS. When the unit load is increased above 30% MCR, the Aux. air dampers of elev. AA,AB, BC, CD, DE, EF & FF are closed in a timed sequence (10 sec. interval) provided the associated coal elevations are not in service and the associated oil elevations are not in service. The auxiliary air dampers are closed, starting from the top elevation, progressing towards the lowest elevation.
50 of 27
confidentia
All elevations of the aux. air dampers will be automatically switched to Manual control and then commanded to open 100%, if any one of the following conditions exist. Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit critical power . (+24V DC) Also the auxiliary air control loop is tripped to manual if any of the following conditions exist. DP transmitter deviation high. Failure of selected DP transmitter Furnace to Windbox DP very high (> 240mm WCL).
51 of 27
confidentia
The fuel air damper control system positions the fuel air damper in proportion to the fuel firing rate. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various fuel air damper positions and the values are to be optimized at site. Based on this the final curve showing the relationship between the fuel air damper positions versus the fuel feed rate is to be decided for the type of coal used.
52 of 27
confidentia
All elevations of fuel air dampers are commanded to open 100% when any one of the following conditions exist. Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit Critical Power.(+24 VDC)
53 of 27
confidentia
On coal fired boilers the characteristics of fuel like, Fixed Carbon, Volatile Matter and Ash composition will determine the optimum wind box to furnace differential pressures and the fuel air damper positions. Accordingly the optimized settings are to be decided as above for the coal used.
54 of 27
confidentia
Later, if the coal quality changes or the coal source itself is changed, it shall be necessary to once again carryout optimization studies for the new coal and revised settings are to be finalized.
55 of 27
confidentia
56 of 27
confidentia
57 of 27
confidentia
58 of 27
confidentia
59 of 27
confidentia
The two elevations of the over fire air dampers will be automatically switched to Manual control and then commanded to open 100%, if any one of the following conditions exist
Master fuel trip occurs. Loss of unit critical power .(+24 VDC) Both FD fans are OFF. Both ID fans are OFF. WB To Furnace DP exceeds 240mm WCL.
confidentia
60 of 27
61 of 27
confidentia
62 of 27
confidentia
Thank you