CT Interpose For SEPAM
CT Interpose For SEPAM
CSH30 InterposingringCT
Function
E E0
The CSH30 interposing ring CT is used as an interface when the residual current is measured using 1 A or 5 A current transformers.
Characteristics
Weight Vertical assembly of CSH30 interposing ring CT. Horizontal assembly of CSH30 interposing ring CT. Assembly 0.12 kg (0.265 lb) On symmetrical DIN rail In vertical or horizontal position
Dimensions
DE80023
mm in
0.18
0.16
1.18
3.23
0.2
1.97
0.63 0.18
4
2.36
0.315 1.14
Connection
The CSH30 is adapted for the type of current transformer, 1 A or 5 A, by the number of turns of the secondary wiring through the CSH30 interposing ring CT: b 5 A rating - 4 turns b 1 A rating - 2 turns Connectionto5Asecondarycircuit
DE80118 PE00 PE00
Connectionto1Asecondarycircuit
turns turns
1. Plug into the connector. 2. Insert the transformer secondary wire through the CSH30 interposing ring CT 4 times.
1. Plug into the connector. 2. Insert the transformer secondary wire through the CSH30 interposing ring CT twice.
DE80119
ConnectiontoSepamseries20andSepamseries40 To residual current I0 input, on connector A , terminals 19 and 18 (shielding). ConnectiontoSepamseries80 b To residual current I0 input, on connector E , terminals 15 and 14 (shielding) b To residual current I0 input, on connector E , terminals 18 and 17 (shielding). Recommendedcable b Sheathed cable, shielded by tinned copper braid b Minimum cable cross-section 0.93 mm (AWG 18) (max. 2.5 mm, AWG 12) b Resistance per unit length < 100 mW/m (30.5 mW/ft) b Minimum dielectric strength: 1000 V (700 Vrms) b Maximum length: 2 m (6.6 ft). It is essential for the CSH30 interposing ring CT to be installed near Sepam (Sepam - CSH30 link less than 2 m (6.6 ft) long). Flatten the connection cable against the metal frames of the cubicle. The connection cable shielding is grounded in Sepam. Do not ground the cable by any other means.
turns turns