Capacitor Bank
Capacitor Bank
EASUN REYROLLE
INTRODUCTION
ES E R SIN Power transfer = X
The phase angle between the voltages at the sending end and receiving end cannot exceed a certain critical value.
Excessive voltage drops between the ends of the feeders. Unequal sharing of the load between parallel feeders.
EASUN REYROLLE
SYNCHRONOUS MACHINES
EASUN REYROLLE
TYPE OF CAPACITORS
TANK TYPE UNIT TYPE
TYPE OF CONNECTIONS
SERIES CONNECTED SHUNT CONNECTED
EASUN REYROLLE
EASUN REYROLLE
EASUN REYROLLE
EASUN REYROLLE
ES RL I
ES I ER I ER ES
XL
ER
ES
RL
XL
XC
ER
Equivalent circuit of a transmission line with a SERIES CAPACITOR at the receiving end
EASUN REYROLLE
Distance
Load point
Without capacitor
EASUN REYROLLE
ES ER
ES
XL
ES I
XL
XC
ER
I ER
ES ER
POWER TRANSFERED
POWER TRANSFERED
ER
ER
EASUN REYROLLE
INCREASE ABILITY OF THE TIE FEEDER TO TRANSFER MORE POWER AND THERE BY INCREASE THE STABILITY OF THE SYSTEM
EASUN REYROLLE
EG Z=R+jX IL EM IM M FEEDERS GEN IC SHUNT CAPACITOR
IL
EM
IC IM
EASUN REYROLLE
ES Z=R+jX I ER
LOAD
GEN FEEDERS IC SHUNT CAPACITOR
ES C IC
X IC B
R IC
ER
R IX X IR OA - VOLTAGE AT LOAD - ER OB - SENDING END VOLTAGE WITHOUT CAPACITOR OC - SENDING END VOLTAGE WITH CAPACITOR - ES
IR I IX
A R IR
X IX
EASUN REYROLLE
ES C X IC IC R IC B R IX
X IR
IR A R IR IX I X IX
ER
EASUN REYROLLE
Capacitor voltage rise
Voltage
EASUN REYROLLE
EFFECTS OF COMPENSATION WITH SHUNT CAPACITORS
EASUN REYROLLE
EFFECTS OF COMPENSATION WITH SHUNT CAPACITORS
BY REDUCING KVA LOAD ON THE SOURCE GENERATOR, ADDITIONAL KW LOADING MAY BE PLACED ON THE GENERATOR IF TURBINE CAPACITY IS AVAILABLE. TO REDUCE DEMAND KVA WHERE POWER IS PURCHASED CORRECTING TO 100% POWER FACTOR MAY BE ECONOMICAL IN SOME CASES (TWO-PART TARIFF) REDUCES INVESTMENT IN SYSTEM FACILITIES PER KW OF LOAD SUPPLIED.
EASUN REYROLLE
EASUN REYROLLE
EASUN REYROLLE
EASUN REYROLLE
PROTECTION REQUIREMENTS
FOR SERIES CAPACITORS
UNBALANCE PROTECTION SPARK GAP PROTECTION MOV (NON-LINEAR RESISTOR PROTECTION) SHORT CIRCUIT PROTECTION
EASUN REYROLLE
PROTECTION REQUIREMENTS
FOR SHUNT CAPACITORS
UNBALANCE PROTECTION
OVERCURRENT PROTECTION
OVER VOLTAGE PROTECTION UNDER VOLTAGE PROTECTION TIMER FOR SUCCESSIVE SWITCHING
EASUN REYROLLE
R Relay Y Relay B Relay Current Unbalance Protection for Star connected bank (Two limbs per phase)
EASUN REYROLLE
R Relay Y Relay B Relay Current Unbalance Protection for Star connected bank (Two limbs per phase)
EASUN REYROLLE
R Y B
Relay
EASUN REYROLLE
R Y B
Relay
EASUN REYROLLE
R
Y Relay B
EASUN REYROLLE
Y Relay B
EASUN REYROLLE
CAPACITORS CAN WITHSTAND
POWER FREQUENCY OVERVOLTAGE AS PER ANSI 18-1980 & IEC 871-1
MULTIPLES OF RMS VOLTAGE 1.1 1.15 1.2 1.3 1.4 1.7 2.0 2.2 2.7 3.0 DURATION (SECS) CONTINUOUS 1800 300 60 15 1 0.3 0.12 0.02 0.01
CONTINUOUS CURRENT OF 1.3 TIMES IRMS AT RATED SINUSOIDAL VOLTAGE AND RATED FREQUENCY EXCLUDING TRANSIENTS
CAPACITOR UNITS RATED ABOVE 600V SHALL HAVE AN INTERNAL DISCHARGE DEVICE TO REDUCE THE RESIDUAL VOLTAGE TO 50V OR LESS IN FIVE MINUTES
EASUN REYROLLE
TYPICAL UNBALANCE CURRENT FORMULA
IL
NUMBER OF GROUPS IN SERIES PER PARALLEL PATH NUMBER OF UNITS PER GROUP
= 2S = N
GROUP A1
TO
GROUP C1
TO
= n
GROUP AS
IU
GROUP CS
V IL XC
GROUP B1 TO GROUP BS
RELAY
GROUP D1 TO GROUP DS
n4 S 3 4 S N n 3n
UNBALANCE CURRENT
n IU IL 4S N n 3n
EASUN REYROLLE
MIT 114
MVT 181
MIT 161
CAPACITOR BANK
EASUN REYROLLE
MIT 114
MVT 171 MVT 181
CAPACITOR BANK