Capacitive Voltage Transformer
Capacitive Voltage Transformer
SW ITC H G EAR C O M P L E X
SWITC H G EAR C O M P L E X
More than 3400 Crompton Greaves Capacitive Voltage Transformers upto 420 kV have been put into service in various environments in many countries all over the world since 1984 where they are operating satisfactorily. Our CVTs adhere to the requirements of the quality standards and scope of supply of ISO 9001.
FIG. 1
2 11 3
12
13
14 15 16 17 18 6 19 7 20 8 9 10 22 21
1 2 3 4 5 6 7 8 9 10 11
HV Terminal ( 30) Porcelain Flange Porcelain Insulator NHF Terminal Oil Sight Glass (EMU) Intermediate Voltage Terminal Tank Compensating Choke Damping Device Oil Sampling Valve (EMU) Bellow
12 13 14 15 16 17 18 19 20 21 22
Capacitor Unit Oil Oil Filling Plug (EMU) Multi Terminal Monoblock Secondary Terminal Box L.V. Terminal Block Rating/Schematic Plate Varistor Gland Plate EMU Unit Intermediate Vol Transformer
Electromagnetic Unit
A
The Electromagnetic Unit (EMU) consists of a medium voltage transformer, compensating reactor, damping element and surge protection device. The unit is housed inside an aluminium tank which is filled with insulating oil leaving a gas cushion at the top in order to take care of changes in the oil volume due to fluctuations in the ambient temperature. An oil sight glass is mounted on the side wall of the tank. The CC unit is mounted on the EMU tank and the insulated earth terminal of the CC (marked as NHF in Fig. 1) is also accessible for connecting to power line carrier communication equipment. A spark gap across this terminal and earth serves as the surge protection device. The NHF terminal must always be connected to earth if the CVT is not connected to carrier equipment. The secondary terminal box is provided on the EMU tank. Secondary leadouts, NHF lead and earth leads are all terminated inside the secondary terminal box. The EMU is caliberated and adjusted at factory for all burden and accuracy requirements. No site adjustments or measurements are neccessary. The EMU is given adequate surface FIG. 3 treatment for corrosion protection for life long service.
temperature variations are compensated by a FIG. 2 stainless steel bellow installed at the upper end C1 of the CC. The unit is completely filled with C2 L degassed insulated oil under vacuum. The bellow is Tr pressurised by inert gas (from the top surface) to Zd V maintain a positive oil pressure even in the case of F large oil contraction. The CVT thus has very low PD Lk levels even at low ambient temperatures. f-g
HV Capacitance Intermediate Voltage Capacitor Compensating Reactor Intermediate Transformer Damping Device Varistor HRC Fuse / MCB Cable Link For Earthing Auxiliary Secondary Winding
D2
ARCING DISTANCE
C1
C2 NHF OPTIONAL L Tr
F F D S ES 1a 1n 2a 2n f
Zd
g Lk
W BOTTOM VIEW
MAINTENANCE
The product is self contained, maintenance free and requires no spares over its entire life span. We recommend regular and periodic checks as per pre-specified schedules (specified in the Instruction Manuals supplied with the CVTs).
OPTIONALS / ACCESSORIES
Terminal Connector (Aluminium/Bimetallic, NEMA or as per customer specs) Three element Carrier Protection Device(comprising Drain Coil, Lightning Arrester & Earth Switch) Oil Level Indicator (EMU) and Bellow Position Indicator (CC) Cable Glands Aluminium EMU tank
1. TYPE DESIGNATION 2. APPLICABLE STANDARDS 3. HIGHEST SYSTEM VOLTAGE 4. ONE MIN POWER FREQUENCY WITHSTAND VOLTAGE (DRY & WET) 5. 1.2/50 s LIGHTNING IMPULSE WITHSTAND VOLTAGE 6. 250/2500 s SWITCHING IMPULSE WITHSTAND 7. RATED FREQUENCY 8. AMBIENT TEMPERATURE 9. SEISMIC ACCELERATION 10. RATED VOLTAGE FACTOR
CVE
CVE
CVE
CVE
CVE
CVE
IEC 44-2, 1997 (IEC 186, 1987) / IEC 358 (1990) IS 3156, 1992 / IS 9348, 1979 72.5 140 325 NA 123 230 550 NA 145 275 650 50/60 -25 TO 50 0.3/0.5 1.2 (CONT) / 1.5 (30 SEC) 3 100, 100/ 3, 110, 110/ 3 , 120 , 120/ 3. 1810 8800 3075 6000 500VA 125 820 1790 755 315 75 360 85 2385 200 1415 2525 800 450 X 450 435 100 STAINLESS STEEL BELLOW CLIP ON STUD TYPE 510 110 820 200 2630 3815 825 3625 4400 4250 6000 6125 4400 750VA 250 2830 4100 10500 4400 170 325 750 245 460 1050 420 630 1425 1050
11. ONE MIN. POWER FREQUENCY WITHSTAND : VOLTAGE ON SECONDARY WINDINGS 12. SECONDARY VOLTAGE 13. TOTAL CREEPAGE DISTANCE 14. EQUIVALENT CAPACITANCE 16. TOTAL THERMAL BURDEN 17. CANTILEVER LOAD 18. ARCING DISTANCE 19. TOTAL HEIGHT (WITHOUT SUPPORT STRUCTURE) (H) 20. MAXIMUM DEPTH (A) 21. MOUNTING DIMENSIONS (W) 22. TOTAL WEIGHT 23. QTY OF INSULATING OIL 24. OIL VOLUME COMPENSATION (CC UNIT) 25. TYPE OF SECONDARY TERMINAL BLOCKS : : : : : : : : : : : : :
200VA / CL 0.5
OPTIONALS
TYPE DESIGNATION 1. HIGHEST SYSTEM VOLTAGE 2. VOLTAGE FACTOR 3. CREEPAGE DISTANCE : UNITS : : kV CVE 72.5 CVE 123 CVE 145 CVE 170 CVE 245 CVE 420 25 100 VA /CL 0.2
: mm/kV -
Power Systems
A Business Unit of Crompton Greaves Ltd.
Inst. Trans. & Bushing Divn. Switchgear Complex A-3, MIDC, Ambad, Nashik : 422 010, India, Tel: +91-253-382271 to 75, Fax: +91-253-381247 E-mail: cglambad@cgswgear.com (General) exports@cgswgear.com (Exports) Web: www.cgswgear.com Regd. Office : 6th Floor, CG House, Dr. Annie Besant Road, Prabhadevi, Mumbai -400 025, India.
Quality through care. Care through quality.