12 MGDP I 1150 0 (Instr Utility Air Calculation)
12 MGDP I 1150 0 (Instr Utility Air Calculation)
12 MGDP I 1150 0 (Instr Utility Air Calculation)
Instrument Type Emergency Shutdown Valves (ESDV-0105) Shutdown Valves (SDV-0106) Emergency Shutdown Valves (ESDV-0205) Shutdown Valves (SDV-0206) Emergency Shutdown Valves ( ESDV-0401A3) Shutdown Valves (SDV-0306) Shutdown Valves (SDV-0112,0212) Emergency Shutdown Valve ( ESDV-2002A) E/P TRANSDUCER Emergency Shutdown Valve ( 0401A1) Emergency Shutdown Valves ( ESDV-0403A2,0404A2) Emergency Shutdown Valves ( ESDV-2002B) E/P TRANSDUCER Emergency Shutdown Valves ( ESDV-0404)
Qty 1 1 1 1 1 1 2 1 3 1 2 1 3 1 20
Phase - 1 Air Total Air Required/Unit Required 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 0.25 1 0.25 0.25 0.25 1 0.25 scfm scfm scfm scfm scfm scfm scfm scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.25 scfm 0.50 0.25 3.00 0.25 0.50 0.25 3.00 0.25 9.50 scfm scfm scfm scfm scfm scfm scfm scfm scfm
Remarks
Note 1 Note 1 Note 1 Note 1 Note 1 Note 1 Note 1 Note 1 Note 2 Note 1 Note 1 Note 3 Note 3 Note 3 Note 3
4 NORTH GATHERING MANIFOLD - MEV1 5 TEST SEPARATOR V-2010 - MEV1 6 PIG LAUNCHER L-0401 - MEV1 7 PIG RECEIVER & MANIFOLD - MEV2 8 TEST SEPARATOR V-2011 - MEV2 9 PIG RECEIVER R-0401 - MEV2
Total Instrument Air Consumption Leakages @ 10% Contingency @ 20% Total Utility Air Required at GPF
Phase 1
Phase 1
12.35 scfm
Note 4
Overall Air Requirement for Phase 1 WELL HEAD -01 WELL HEAD -02 WELL HEAD -03 NORTH GATHERING MANIFOLD - MEV1 Nitrogen Bottles Required Nitrogen Bottles Required Nitrogen Bottles Required Nitrogen Bottles Required Total No. of Bottles Required 2 2 2 2 8
NOTES: