Calculation of chart:

433V

690V

3.3KV

6.6KV

11KV

1 KVA

1.33A

1 KW

1.66A

1 KVA

0.84A

1 KW

1.1A

1 MVA

175A

1 MW

218A

1MVA

87A

1MW

109A

1MVA

52.5A

1 MW

65A

(I = KWX1000/1.732XLine voltagex PF) = 1000/1.732X11000X0.8


KW
MW

= 0.06561X1000
=65A

(I= KVAX1000/1.732XLine voltage) = 1000/1.732X11000


KVA

= 0.0525X1000

MVA

22KV

33KV

66KV

110KV

132KV

=52.5

1MVA

26.2A

1 MW

32.8A

1 MVA

17.4A

1 MW

21.8A

1 MVA

8.8A

1 MW

10.9A

1 MVA

5.25A

1 MW

6.5A

1 MVA

4.37A

1 MW

5.46A

220KV

400KV

1 MVA

2.62A

1 MW

3.28A

1 MVA

1.44A

1 MW

1.8A

Maximum demand calculation:


Capacity of the plant: 8250 Tons of per day
Specific energy consumption: 85 KWH/Ton of cement PF of
Efficiency: 0.9
KW Demand= (8250X85)/24

( Capacity of Tons/Day

= 29219 KW
KVA Demand= 29219/(0.8X0.9)
= 40582 KVA
Connected load calculation:

( KW Demand/ PFXEfficiency)
( 40582 KVA/1000=40MVA)

Demand KW/ LFXDFXPF)

LF: Load factor- 0.85


DF:Diversity factor- 0.75
PF: Power factor- 0.8
Connected load= 29219/0.85X0.75X0.8
= 57292 KW