How to find Amps Rating?

TRANSFORMER
Capacity: VOLTAGE Ratio: Current Rating: PRIMARY SIDE: KVA=1.732x11KVxI SECONDARY SIDE: KW=KVAxP.F KW=1.732xVxIxCOS HV Amps 16.79613689 amps LV Amps 256 kw 426.6916992 amps 320 KVA 11 KV/ 433 v

APFCR
Capacity: VOLTAGE Ratio: kvar=VISin Cos Angle Sin 2500 KVAR 433 Volt

0.8 36.86989765 0.6

Current Rating

103.92 Amps

dg
Capacity: VOLTAGE: Current Rating: 500 KVA 415 Volts

KW=KVAxP.F KVA=1.732xVxI

450 Kw 695.6231 Amps

UPS BACKUP CALCULATION GIVEN: INPUT: NEED: Eff: Backup for Full Load 24V 220VAC 90% 6 to 12 hr 3kw

3000

How to cal calculate AH? Ans: dont know how did they calculate 3333w from 3000w 3333w 24v kw=VI 138.875 AMPS Hrs to backup 6 12 Ah . Reqrd 833.25 1666.5 Calculate to below percentage of discharge for 6 hr 80% discharge of battery -Give Normal life 50% discharge of battery -Give Long Life 0.8 0.5 for 12 hr

1041.563 2083.125 AH 1666.5 3333 AH

UPS BACKUP CALCULATION GIVEN: INPUT: NEED: Eff: Backup for Full Load 24V 220VAC 90% 6 to 12 hr 310 Load Details Load Watts Qty Fan 75 Tube light 40 3000 Total 2 4 150 160 310

Total watts

How to cal calculate AH? Ans: dont know how did they calculate 350w from 310w 350w 24v kw=VI 14.58333 AMPS Hrs to backup 6 Ah . Reqrd 87.5 Calculate to below percentage of discharge 80% discharge of battery -Give Normal life 50% discharge of battery -Give Long Life

0.8

109.375 Ah Reqrd for 6 hr

0.5

175 Ah Reqrd for 6 hr

UPS BACKUP CALCULATION GIVEN: INPUT: NEED: Eff: Backup for Full Load in VA Ahr given Calculate Backup time? Ans: 24V 220VAC 90% ? 875 185 AH

700 watts

Hrs to backup Ah . Reqrd

700w kw=VI 29.16667 5.074286 148

24v AMPS Hr AH Amps per hr can taken Ah=Ampsxhr

Calculate to below percentage of discharge 80% discharge of battery -Give Normal life 50% discharge of battery -Give Long Life

0.8

185 Ah Reqrd for 6 hr

final AH=Ah/80%discg

0.5

296 Ah Reqrd for 6 hr

Load Details Load Watts Qty Fan 75 Tube light 40 w Total 4 10 300 400 700

Total watts

LOAD CURRENT CALCULATION LOAD IN KVA LOAD IN KW VOLTAGE 3 LOAD CURRENT 1 LOAD CURRENT 60% of full Load Current CABLE CURRENT RATING 90% OF CURRENT RATING 108 86.4 415 150.2546 469.5652 KVA KW V Amps Amps 86.4 KW

KW=1.732*V*I*COS KW=V*I*COS

51.84 kw 90.15276 Amps RUNS 270 486 Total Current 2 540 Feeder

Load 4.3

Nos 18

Total 77.4

30

90

1.333333

Total load Per Feeder 3DB

1000 watts 750 333.3333