Vortex Enclosure Cooler - Sizing & Selection Worksheet

Height (in.) Width (in.) Depth (in.) Internal Temp. Now Ambient Temp. Now Square Feet of Enclosure 0

Delta T *F

0 Vortex Cooler & Vortex A/C - BTUH Capacity

Desired Worst Delta T *F Internal Case Temp. Ambient If internal and ambient temperatures are unknown, use dissipated heat in watts. Dissipated Heat in Watts Additional BTU's 0 Total Delta T *F

0 Enclosure Cooler Model Number 0 750 / 760 730 / 740 780 / 790 785 / 795 7870 / 7970 737 / 747 770 787 / 797 770-35H 787-35H / 797-35H 7875 / 7975 737SS / 747SS / 7715 7725 787SS / 797SS 7735 787SS-35H / 797SS-35H 7875SS / 7975SS NEMA 12 NEMA 12 NEMA 12 NEMA 12 NEMA 12 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4 NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X NEMA 4X BTUH 250 600 750 1200 2400 600 750 850 1200 1200 2400 600 750 850 1200 1200 2400

AVAILABLE COMPRESSED AIR PRESSURE 60 PSIG 80 PSIG 100 PSIG

Temp. Rise Due To Solar Radiation if enclosure is exposed to direct sunlight Number Cabinet Color Approx. Temp Rise 1 White 4 2 Cream 7 3 Yellow 9 4 Light Gray 14 5 Medium Gray 22 6 Dark Gray 25 7 Black 27 8 National Aluminum or 14 Stainless Steel The cabinet is: * Sealed and unvented. Vented-fan cooled. ( Vented-no fan.

Color Number

>70 Deg. F 200 375 625 900 1800 375 625 700 900 900 1800 375 625 700 900 900 1800

BTUH 375 775 1050 1600 3200 775 1050 1120 1600 1600 3200 775 1050 1120 1600 1600 3200

>70 Deg. F 275 525 800 1250 2500 525 800 900 1250 1250 2500 525 800 900 1250 1250 2500

BTUH 400 900 1500 2500 5000 900 1500 1700 2500 2500 5000 900 1500 1700 2500 2500 5000

>70 Deg. F 375 700 1100 1600 3200 700 1100 1300 1600 1600 3200 700 1100 1300 1600 1600 3200

Total BTUH

CAPACITIES

SCFM)

Additional BTU's provided by fan(s). 0

*Temperature of air entering enclosure (F). If fan cooled: *Temperature of air exiting enclosure (F).

Note: If the compressed air supply is not dried to a -40 degree F pressure dew point, devalue capacities by 15%. Compressed air temperatures must not exceed 110 degrees F. If compressed air temperatures exceed 110 degrees F, call the factory. Note: "BTUH" capacity when compressed air temperature does not exceed 70 degrees F. ">70 degrees F" capacity when compressed air temperature exceeds 70 degrees F. Note: The Panel Guard models have a 770 prefix and the Vortex A/C models (listed in blue) both feature a mechanical thermostat to maintain cabinet temperatures within a range of 80 to 90 degrees F