SF Error - Air Net

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

FTA -------

March 1, 2005 Service Planning Department

Countermeasure plans

SF alarm generated

Wiring
(5%)

Multi-core wire used Short-circuiting or disconnection Descendant branching More than one type of wire used Work beyond specifications

Beyond the specified range of D3NET wiring work.

Corrections

* SF D3NET communication over the Airnet monitors communications commands once per minute. If there is no command for 20 minutes continuously, the Airnet in its own discretion will take the situation as an SF error.

Power interruption
(90%)

Equipment turned off Turned off owing to an insulation failure in the air conditioner.

Turned off manually. Turned off owing to a failure in the air conditioner.

The monitoring system is normal. Repairs or corrections

Noise
(5%)

Atmospherics noise

Power line Inverters High-frequency equipment, railroads, roads, and other external noise sources

Keep an isolation distance. Terminal resistance and expansion adapter

Power supply noise

From the LC side From the air-conditioner side

Countermeasures on power supply side

Telephone line noise

Influence of telephone line on LC side

Single-unit failure
(0.1%)

LC Outdoor unit PCB Indoor unit PCB Other devices on D3NET Devices other than the above are connected to the D3NET.

Repairs and replacement of defective parts

Improper design
(0%)

LC Outdoor unit PCB Indoor unit PCB Devices other than the above are connected to the D3NET. Corrections to improper part

Other devices on D3NET

Values in parentheses indicate estimated failure rates occurring in the market.