ATI - Instruction Manual-Transfer - Panel
ATI - Instruction Manual-Transfer - Panel
Instruction Manual
INTRODUCTION________________________________________________ 4 GENERAL INTRODUCTION ____________________________________ ATI TRANSFER PANEL RANGE _________________________________ NEW MOTORIZED CHANGEOVER SWITCH _____________________ OPTIONS AVAILABILITY _______________________________________ ENVIRONMENT ______________________________________________
6 4 4 4 5 6
TECHNICAL CARACTERISTICS_____________________________________ 6 ENCLOSURES INSTALLATION _________________________________ 7 - 37 FIRST OPERATIONS ______________________________________ 7 - 10 BOTTOM CABLE ENTRY ENCLOSURES ___________________ 11 - 17 TOP CABLE ENTRY ENCLOSURES _______________________ 18 - 24 OPTIONAL CONNECTIONS ______________________________ 25 - 37 GENERAL POINTS___________________________________________ 37 VOLTAGE CONFIGURATIONS _________________________________ 38 VOLTAGE OPTIONS__________________________________________ CABLE CONNECTIONS BETWEEN SWITCH AND ELECTRONIC MODULE _________________________________ ELECTRONIC MODULE CONNECTIONS ___________________ 39 42 38 38 42
INPUTS AND OUTPUT CONTACTS ________________________________ 43 CURRENT INPUTS (for metering) __________________________________ 43 BASIC PRODUCT USE________________________________________ 44 GENERAL INTRODUCTION ___________________________________ ELECTRONIC MODULE USAGE __________________________ 44 PROGRAMMING ACCESS____________________________________ PROGRAMMING EXIT________________________________________ PROGRAMMING MENUS_____________________________________ SETUP MENU___________________________________________ 47 VOLTAGE MENU ________________________________________ 49 FREQUENCY MENU _____________________________________ 50 TIMERS MENU__________________________________________ 51 COMMUNICATION MENU ________________________________ 52 MANUAL MODE _____________________________________________ AUTOMATIC MODE __________________________________________ LOSS OF MAINS AUTOMATIC SEQUENCE _____________________ MAINS RETURN AUTOMATIC SEQUENCE _________________ 58 TEST MODE ACCESS________________________________________ TEST MODE EXIT____________________________________________ OFF LOAD TESTING _________________________________________ ON LOAD TESTING __________________________________________ 62 44 45 45 45 46 48 50 51 52 54 55 56 57 59 60 60 61 62
METERING PRODUCT USE ___________________________________ 63 - 75 GENERAL INTRODUCTION ___________________________________ 63 ELECTRONIC MODULE USAGE __________________________ 63 - 64 PROGRAMMING ACCESS____________________________________ 64 PROGRAMMING EXIT________________________________________ 64 PROGRAMMING MENUS_____________________________________ 65 SETUP MENU___________________________________________ 66 - 67 VOLTAGE MENU ________________________________________ 68 - 69 FREQUENCY MENU _____________________________________ 69 - 70 TIMERS MENU__________________________________________ 70 - 71 COMMUNICATION MENU _____________________________________71 PRODUCT METERING ___________________________________ 72 - 73 MANUAL MODE _____________________________________________ 74 MAINS RETURN AUTOMATIC SEQUENCE _____________________ 74 TEST MODE ACCESS________________________________________ 75 TEST MODE EXIT____________________________________________ 75 COMMUNICATION ___________________________________________ 76 - 79 LIST OF PARAMETERS TO BE DISPLAYED_________________ 76 - 79 SAVED COMMAND __________________________________________ 79 MAINTENANCE ______________________________________________ 80 - 83 FAULT FINDING GUIDE ___________________________________________ 84
3
ENGLISH
INTRODUCTION
GENERAL INTRODUCTION NEW ATI enclosure integrates a new 4-pole changeover switch including electronics control to meet standard IEC 60947-6-1. Thanks to the changeover switch technology, it is always possible to manually operate the system to guarantee the changeover panel operation in any situation. The new enclosure design allows switch front panel access to: Avoid opening of the enclosure for manual operation Allow electronic module access for programming and monitoring ATI TRANSFER PANEL RANGE The new ATI panel range will be available from 63 A to 1 600 A. New ATI range models MODEL ATI 63 A ATI 100 A ATI 125 A ATI 250 A ATI 400 A Simplify connections between the mechanical switch and the electronic module. With the mode switch in manual position, Padlocking, as well as handle insertion operations are then directly accessible from the front panel. The electronic module, also accessible from the front panel, includes: Sources monitoring Metering display (V and f as standard) Test operations and Sequences programming using keypad.
ATI 630 A ATI 800 A ATI 1 000 A ATI 1 250 A ATI 1 600 A
Standard offer includes Bottom cable entry. Top cable entry is offered as an option. NEW MOTORIZED CHANGEOVER SWITCH The new switch included in the enclosure is made of 3 different parts: 1. A mechanical switch. 2. A motorized block to operate the switch electrically. 3. An electronic module on the top of the motorized block, driving loss of mains and mains return sequence. Features and benets: Main sensing circuit is 3 phases and Gen sensing circuit is single phase The new Motorisation block is inclu Standard product includes, phase to ded in a moulded case phase + phase to neutral voltage It is possible to remove the motorized measurement and displays system block and the electronic module frequency (phase 1) and switch numwithout being obliged to disconnect ber of operations. the power cables The product including metering allows Manual operation directly acts on the current measurement as well as power shaft of the mechanical switch for metering (kW, kVar, kVA and PF). better reliability The complete enclosure meets standard IEC 60947-6-1 (ATS applications) The enclosure is self-powered (from Main and Gen sources). There is no need for an external power source to allow automatic sequence after loss of power All thresholds and timers can be set using the display and the keypad, or via modbus (optional) The standard product integrates voltage and frequency control for better diagnostic
3 2
1
ATI 035 A
INTRODUCTION (continued)
OPTIONS AVAILABILITY
Option 9 Top Cable Entry Option 8 Communication Option 1 Metering Option Option 7 2In / 2Out
ATI 036 A GB
Factory options are delivered pre-installed in the enclosures Option 6: Option 9: Auxiliary contacts for switch posi- Top Cable Entry. For cables to be tion information, padlocking and routed through the top rather than Auto / Manual mode information are bottom. Option code is TICT. optionally available. Option code is TAUX. Option 1: Option 5: A metering module allowing stan- A switch allowing 277 Vac specific dard features + current and power voltage option for customers requimetering facilities on a larger backlit ring voltage code V601 (480/277 Vac). display. Option code is TMET. Option code is THVM. Loose options are available, for customer mounting in the enclosures Option 2: Option 7: IP54 protection rating is available as 2IN / 2OUT.1 plug in module allowing an option. A specic protection winauxiliary contacts for Main and dow must be installed on the front Generator available information is also panel of the enclosure to avoid water available as an option. Option code is infiltration in the enclosure. Option TIO2. code is TIP5. Option 8: Option 3: 1 plug in communication module, Solid neutral link is available as an JBUS / MODBUS protocole, can option on the switch itself, when optionally be ordered allowing remote switching of the neutral cable is not communication of the changeover required. Option code is TLNK. system. Option code is TCOM. Option 4: Lightning protection is also available as an option to avoid ATS damage in case of a strike on the power cables. This option is highly recommended in stormy areas. Option code is TLPR and TI02 is included.
ENGLISH
INTRODUCTION (continued)
ENVIRONMENT The complete enclosure meets following environmental requirements: Ingress protection of IP41 with overall Operating temperature of 40 C to 95 % humidity non condensing at 65 C with de-rating 40 C rating of IP21 Maximum operating altitude without Operating temperature of 10 C to Maximum storage is one year 80 % humidity non condensing at switch de-rating is 2 000 m above 40 C without de-rating 55 C sea level.
TECHNICAL CARACTERISTICS
Characteristics
Thermal Current Ith (40 C) Assigned isolement voltage Ui (V) Assigned voltage to chocks Uimp (kV) 63 A 800 8 100 A 800 8 125 A 800 8 250 A 800 8 400 A 800 8 630 A 1 000 12 800A 1 000 12 1 000A 1 000 12 1250 A 1000 12 1600 A 1000 12
Other Characteristics
Commutation duration I-II ou II-I (s) (1) I-o ou II-0 (s) (1) Black time durating during commutation under Un (ms) Power input 230 Vac mini / maxi (V) 277 Vac mini / maxi (V) - Option 5 Consumption during switching operation 230 Vac maxi / average (VA) 277 Vac maxi / average (VA) - Option 5 Mechanical characteristics Number of commutation (durability) Weight (complete std enclosure) kg 0.75 0.45 300 0.75 0.45 300 0.75 0.45 300 184/276 221/332 420/80 420/80 10 000 21 1.3 0.85 600 1.3 0.85 600 1.3 0.85 600 2,6 1,6 1 500 2,6 1,6 1 500 2.8 1,7 1700 210/310 240/380 470/128 470/128 3000 230 2.8 1,7 1700 210/310 240/380 470/128 470/128 3000 330
184/276 184/276 221/332 221/332 420/80 420/80 10 000 21 420/80 420/80 10 000 21
184/276 184/276 221/332 221/332 400/100 400/100 400/110 400/110 8 000 39 8 000 44
184/276 184/276 184/276 221/332 221/332 221/332 420/110 450/120 450/120 420/115 450/125 450/125 5 000 66 4 000 125 4 000 130
All these characteristics are given as information and are not contractual (1): Between order sent and nal position (under nominal conditions)
Temperature Derating
Nominal Rating (40 C Max) (A) 63 100 125 250 400 630 800 1 000 1 250 1 600 Cable Size (mm2) 16 35 50 120 240 2 x 185 2 x 240 4 x 150 4 x 240 5 x 240 50 C (A) 63 100 125 250 360 550 720 880 1 150 1 300 De rate 60 C (A) 50 80 100 220 300 500 640 800 1 000 1 100 65 C (A) 45 63 80 200 250 400 540 680 820 930 IEC 947-3 40 C 415 V 60 C 415 V AC 22 AC 23 AC 22 AC 23 AC23A 63A AC23A 45A AC23A 100A AC23A 63A AC23A 125A AC23A 80A AC23A 250A AC23A 200A AC22A 400A AC23A 250A AC23A 250A AC22A 630A AC23A 500A AC23A 400A AC22A 800A AC23A 800A AC23A 540A AC22A 1000A AC23A 1000A AC23A 680A AC22A 1 250A AC22A 1 000A AC22A 1 600A AC22A 1 100A
(1)
Short circuit level required for 160A not acceptable for 100A version Short circuit level required for 630A not acceptable for 400A version (3)Short circuit level required for 800A not acceptable for 630A version (4)Short circuit level required for 1 600A not acceptable for 1 000A version (5) Short circuit level required for 2 500A not acceptable for 1 600A version
(2)
Metering accuracy
Voltage and frequency: 1 % on power input range.
ENCLOSURES INSTALLATION
FIRST OPERATIONS The system is delivered in position 0 in manual mode, start generator contact closed. Shroud Remove the shroud to allow terminals access.
400A / 630A
ATI 037 A
ENGLISH
x1
ATI 038 A
x4 x4
M6 x4 x4
ATI 039 A
ENGLISH
2 3
10
ATI 040 A
A-A
1 2 3 N Load
Generator
Main
Torque : M8 M10
13 Nm (Max) 26 Nm (Max)
400 276
128
273 248
238 448
122
39 15 600 558
ATI 041 A GB
12.5
9 7.5 17 39
441 455
70
90
11
ENGLISH
A-A
1 2 3 N Load
Generator
Main
Torque : M8 M10
13 Nm (Max) 26 Nm (Max)
600 495
245
348 323
435 648
82.5
39 15
900
9 7.5 17 39
ATI 042 A GB
12.5
858
641 655
12
60
185
1 2 3 N
Main
Load
Generator
26 Nm (Max) 45 Nm (Max)
600 495
245
348 323
435 648
82.5
39 15
900
9 7.5 17 39
ATI 043 A GB
12.5
858
641 655
60
185
13
ENGLISH
Main
Load
Generator
26 Nm (Max) 45 Nm (Max)
600
14
320
423 398
900
14
ATI 044 A
200
30
328
Load Earth cable: -800A:2x120mm2 or 1x300mm2 (Max) -1000A:2x240mm2 or 1x300mm2 (Max) Main
Generator
Phase and neutral cable 800A:3x240mm2 or 2x300mm2 (Max) 1000A:4x240mm2 or 2x300mm2 (Max) 28
14
623 600
520
536
1375
1175
200
775
ATYS 127 A GB
536 50 50 120
80
14
80
50
480
480
30
720
15
ENGLISH
Main
Generator
555
100
100
Torque: M12
45Nm (Max)
798 775
1800
1800 200 100 58 100 81
ATYS 131 B GB
555
58 100
100
79
100
800
16
803
1600
Main
Generator
555
100
100
Torque: M12
45Nm (Max)
798 775
1800
1800
200
100
58 100 81
ATYS 132 B GB
555
58 100
100
79
100
800
803
1600
17
ENGLISH
Generator
Main
Load 1 2 3 N
Torque : M8 M10
13 Nm (Max) 23 Nm (Max)
273
448
248
39 15
558
9 7.5 17 39
12.5
128
276 400
ATI 045 A GB
18
90
600
Main
Generator Load
1 2 3N
Torque : M8 M10
13 Nm (Max) 26 Nm (Max)
348
648
323
39 15
9 7.5 17 39
858
12.5
245
ATI 046 A GB
495 600
900
19
ENGLISH
185
Load
Main
Generator
1 2 3 N Phase and neutral cable Torque 240 mm2 or 2 x 120 mm2 (Max)
: M10 M12
26 Nm (Max) 45 Nm (Max)
348
648
323
39 15
9 7.5 17 39
858
12.5
245
495 600
ATI 047 A GB
20
900
185
A-A
Load
Main
Generator
1 2 3 N
26 Nm (Max) 45 Nm (Max)
423 398
200
600
30 72.5
288
46
280
13
600
ATI 048 A
328
21
ENGLISH
1150
Generator Main
Load
A Phase and neutral cable: 800A:3x240mm2 or 2x300mm2 (Max) 1000A:4x240mm22 or 2x300mm2 (Max) 30 720 Torque: M10 M12 26Nm (Max) 45Nm (Max)
28
14
520
480
1375
1175
200
ATI 048 C GB
14
22
80
50
480
12
13
A-A A
Generator
Main
A
100
Torque : M12
45Nm (Maxi)
555
100
798 775
1800
1800
200
100
58 100 81
ATYS 133 B GB
555
58 100
100
79
100
800
803
1600
23
ENGLISH
A-A
Load
Generator
A
100
Torque M12
45Nm (Maxi)
555
100
798 775
1800
1800 200 100 58 100 81
ATYS 134 B GB
555
58 100
100
79
100
800
24
803
1600
Verify there is no voltage Metering Option on the terminals before Available from third release 2004. This mounting the options. option is factory tted and includes a
specific metering display + metering CTs to allow current + power metering.
ATI 049 A GB
1
x1
M5
x4 x1
25
25
7
2
92
354
ATI 050 A GB
25
ENGLISH
x2
M8 x1
x2
x2 x1 x1
x2 M8x20
ATI 051 A
2
Torque : M8 > 13 Nm (Max)
26
x3 x1 x1
x1 x2 x3 M8/M10 x 20
3
ATI 052 A
2
Torque : M8 > 13 Nm (Max) M10 > 26 Nm (Max)
27
ENGLISH
x1 x1
x4
M10 / M12
x2
x1 x1
x2
ATI 053 A
x1
x1
x1 x1
A see detail
ENGLISH
A see detail
detail A 1/2
M10x45 (x4)
M10x35 (x4)
x2 x1 x1
A see detail
M12X45: x18
detail A
A
A
ATYS 135 B
SECTION
A-A
31
ENGLISH
x4 x1 x1
A see detail
M12X45: x18
detail A
A A
ATYS 136 B
SECTION
A-A
32
A 3 minutes power off action is required before startup to allow option recognition.
Bottom Connection Top Connection
x1
M6
x1 M8 x2 x1
125A 250A 250A
x2
125A
A B
5 4
1/2
C
B 1 2 3
4
N
SURGYS CONTACTS
FUSE CONTACT Q2 3P
ATI 054 A GB
5
2IN/2OUT Option
A specific menu in the metering architecture allows monitoring of the protection. Cf variable LIP in the monitoring menu. LIP variable = 1 as soon as the protection operates (fuse blow or lightning protection operation). This information is verified every 5 seconds. Error led also blinks to inform of LIP operation. It might then either be required to change a fuse or the lightning module.
FUSE CONTACT Q2 1P
33
ENGLISH
L3 L2 L1 N
4mm
2
L3 L2 L1 N
Q2
RMS 50 50A
4mm2
SURGYS
7
Opt.2 Opt.1
6mm2
ATI 055 A GB
0.75mm2
+ -
11 14
11 14
11 14
11 14
FUSE CONTACT Q2 3P
2IN/2OUT Option
34
14 13
FUSE CONTACT Q2 1P
SURGYS CONTACTS
+ C
106
105
104
103
102 101
8 9 10 11 12
Option 6 Auxiliary contacts for 0,1,2 position, padlock and Auto / Manual Mode. Available from factory.
f g h
20 21 22 23 24 25 26 27
ATI 056 A GB
1 2 3 N 1 2 0 A/M Padlocking
20-22
Output
20-23
Output
24-25
Output
26-27
Output
Contact f, g and h are closed when the switch is in position 1, 2 or 0. Contact i is closed when the switch is in Automatic mode. Contact j is closed when the switch is padlocked.
Resistive load: 10 A Inductive load: 3 A Max Vac: 250 - Max operations: 5 x 107 35
Identication f
Terminals 20-21
Type Output
Feature Position 1 Auxiliary contact Contact closed when switch is in position 1 Position 2 Auxiliary contact Contact closed when switch is in position 2 Position 0 Auxiliary contact Contact closed when switch is in position 0 Auto / Manu information Contact closed when Automatic mode is active Padlocking information Contact closed when the switch is padlocked
Rating
ENGLISH
A 3 minutes power off action is required before startup to allow option recognition.
x1
1
1/2
OUT
9 / 10 : Main Available output contact 11/12 : Gen Available output contact
ATI 057 A GB
a b 9 10 11 12
11-12
Output
36
230 Vac - 5 A - 1 150 VA Max operations 105 - Galvanic insulation 2,5 kV (1 min 50 Hz)
Identication a
Terminals 9-10
Type Output
Rating
A 3 minutes power off action is required before startup to allow option recognition.
1
1/2
2
ATI 058 A GB
RS485 2 or 3 wires half duplex Protocol JBUS / MODBUS protocol / RTU mode Speed 2400, 4800, 9600, 14 400, 19 200, 28 800, 38 400 Bauds Galvanic insulation 4 kV (1 min 50 Hz) GENERAL POINTS Recommendations: You should use a shielded twisted pair (LIYCY type). In a disturbed environment or large network (in terms of length) we recommend the use of 2 shielded pairs (type LIYCY-CY). In this case, one pair is used for the + and the , and another pair, where the 2 wires are short-circuited, for the 0 V. A repeater (1 channel) or an arrestor (4 channels) should be used if you intend to exceed the distance (1 500 m) and / or maximum number (31) of ATI. Please contact us for more information. NB: A 120 ohm resistance (found on the additional module) must be fixed at both ends of the link. Other solutions are available (modem, optical bre, etc.). Please contact us.
R = 120 N 1
For standard configurations, an RS 485 link is used to connect up to 31 ATI with a PC or a PLC over a distance of 1 500 metres, using JBUS / MODBUS protocol.
1500 M
R = 120
N 1
N 2
N n R = 120
DIRIS 109 B
1500 M
1500 M
N n R = 120
DIRIS 110 B
37
ENGLISH
VOLTAGE CONFIGURATIONS
VOLTAGE OPTIONS To meet all voltages required by the market, 2 ATI versions have been developed: Standard 230Vac +/- 20%
50 Hz 3 phase 4 wires - 3P4L Star connections FG Wilson Voltage option code V502 415 / 240V V503 400 / 230V V504 380 / 220V V507 220 / 127V V510 200 / 115V (1) (1): +20%/-12% (2): +13%/-20% (3): +20%/-15% 50 Hz 3 phase 3 (4) wires - 3P3(4)L Delta connections V506 230 / 115V V508 220 / 110V 60 Hz 3 phase 4 wires 3P4L Star connections FG Wilson Voltage option code V603 440 / 254V (2) V605 380 / 220V V608 220 / 127V V610 208 / 120V (3) V611 240 / 139V
60 Hz 3 phase 3 (4) wires 3P3(4)L Delta connections V606 240 / 120V V607 230 / 115V V609 220 / 110V 60 Hz single phase 3 wire 1P3L V622 240 / 120V V624 230 / 115V V626 220 / 110V 60 Hz single phase 2 wire 1P2L V621 240V V623 230V V625 220V
50 Hz single phase 3 wire 1P3L V522 240 / 120V V524 230 / 115V V526 220 / 110V 50 Hz single phase 2 wire 1P2L V521 240V V523 230V V525 220V
Optional 277 Vac ( + / -20 % for rating below 630 A, + 20 / -15 % for rating 800 A and above)
50 Hz 3 phase 4 wires - 3P4L Star connections FG Wilson Voltage option code 60 Hz 3 phase 4 wires 3P4L Star connections FG Wilson Voltage option code V601 480 / 277V
CABLE CONNECTIONS BETWEEN SWITCH AND ELECTRONIC MODULE A voltage sensing kit is used to provide sensing and power connections from the switch terminals to the electronic module terminals. The ATI enclosures are delivered as standard for 3 phases 4 wires applications, 400 /230 Vac nominal voltage. In some 3 phase 4 wires, all 3 phases 3 wires, or single phase 2 or 3 wires applications, sensing connections keep the same, but power connections must be modified according to guidelines included before connection diagrams.
In standard ATI (bottom entry) generator cable is red and main cable is black. In top entry ATI main cable is red and generator cable is black.
38
Verify voltage between 101 / 102 & 201 / 202 = 220 / 240 Vac20 %
3 Phases 4 Wires connections-3P4L A. No wiring change required from standard delivery Congurations: V502 415 / 240 Vac 50 Hz V503 400 / 230 Vac 50 Hz V504 380 / 220 Vac 50 Hz V603 440 / 254 Vac 60 Hz V605 380 / 220 Vac 60 Hz V601 480 / 277 Vac 60 Hz - Special Voltage Option 5 = 277 Vac
LOAD
1 2 3 N
Genset controller
103
102 101
A B
A B
a b c d
Opt. 2 Opt. 1 11 12
ATI 059 A GB
20 21 22 23 24 25 26 27
106
105
104
39
ENGLISH
Main sensing is 3 phases sensing: 103: Neutral 104: Phase 3 105: Phase 2 106: Phase 1
Congurations: V507 220 / 127 Vac 50 Hz V510 200 / 115 Vac 50 Hz V608 220 / 127 Vac 60 Hz V610 208 / 120 Vac 60 Hz V611 240 / 139 Vac 60 Hz
103
102 101
A B
A B
Voltage Sensing
a b
3 Phases 3 (4) Wires connections-3P3(4)L Wiring change required from standard delivery: A & B power wires from terminals 206 & 103 must be connected to terminals 205 & 104 to provide 220 / 230 Vac or 240 Vac to the power inputs 101/102 and 201/202. LOAD
1 2 3 M
Genset controller
106
105
104
Congurations: V506 230 / 115 Vac 50 Hz V508 220 / 110 Vac 50 Hz V606 240 / 120 Vac 60 Hz V607 230 / 115 Vac 60 Hz V609 220 / 110 Vac 60 Hz
103
102 101
A B
A B
Voltage Sensing
a b
40
106
105
104
Congurations: V522 240 / 120 Vac 50 Hz V524 230 / 115 Vac 50 Hz V526 220 / 110 Vac 50 Hz V622 240 / 120 Vac 60 Hz V624 230 / 115 Vac 60 Hz V626 220 / 110 Vac 60 Hz
Genset controller
103
102 101
A B
A B
a b
1 Phase 2 Wires connections-1P2L Wiring change required from standard delivery: A & B power wires from terminals 206 & 103 must be connected to terminals 205 & 104 to provide 220 / 230 Vac or 240 Vac to the power inputs 101/102 and 201/202. LOAD
1
106
105
104
240 Vac 50 Hz 230 Vac 50 Hz 220 Vac 50 Hz 240 Vac 60 Hz 230 Vac 60 Hz 220 Vac 60 Hz
Genset controller
103
102 101
A B
A B
a b
106
105
104
41
ENGLISH
201 202 203 204 205 206 7 8 201 202 203 204 205 206 7 8 Power 230 Vac Voltage Sensing Power 230 Vac Voltage Sensing
1 2
103
102 101
A B
A B
Voltage Sensing
a b
Three phase network / single phase This configuration must be used on generator. applications using single phase generators to supply 3 phases networks feeding single phase loads. Wiring change required. Change 5-6 and 7-8 on 205 & 206. LOAD
1 1 1 N
Genset controller
106
105
104
1 2 3 N
103
102 101
A B
A B
Voltage Sensing
a b
42
106
105
104
7-8
a b c d
Opt. 2 Opt. 1
e
ATI 066 A GB
Identication a b
Terminals 7 7-8
Type
Rating
- Max number of operations 108 - Max inverse voltage 30 Vdc
7-9
Input
Remote test on load input Dry contact to close between terminals 7-9 to start remotely a test on load (only available in automatic mode) Power supply dedicated to lightning option 5 Vdc < V7-10 < 16 Vdc without load 9 Vdc < V7-10 < 10 Vdc for 1 to 2 inputs Start Gen signal 30 V DC 1 A
10 ( + ) 7 (-)
Power supply
11-12
Output
CURRENT INPUTS
R1 R2 S1 S2 T1 T2 T2 T1 S2 S1 R2 R1
(for METERING)
LOAD If the load is supplied, before disconnecting the main connector, it is necessary to short-circuit the secondary of the current transformer (short-circuit plug to be mounted).
1 2 3 N
1 2 3 N
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
ATI 090 A
I1
I2
I3
106
105
104
103
102 101
Input
AT Timer inhibit input Dry contact to close between terminals 7-8 to inhibit AT timer
43
ENGLISH
106
ensing
206 7 8 9 10 11 12
Puissance 230 V AC -
- Mesure de tension
Verify power applied on the electronic module power inputs terminals 101-102 or 201-202 before powering up the unit.
The product provides sources availability monitoring, Automatic / Manual Retransfer, Manual / Automatic or Test operation monitoring, voltage and frequency metering, and good operation or error information.
The product requires at least one type of network conguration and a network nominal voltage conguration to be input via the keypad by the user. Other default values can be kept or modied according to hereafter programming guidelines.
ELECTRONIC MODULE USAGE Front Panel Introduction The electronic module is directly mounted on the motorized block. It integrates the following features: - Voltage and frequency metering - Automatic transfer controls
LCD 7 digits to display information 14 pointers to inform about displayed information unit or source: : Mains information - Com: communication active - : Generator information - V: Volt - L1, L2, L3 : Information - Hz: Hertz regarding Phase 1,2 or 3 - %: percentage - : Timer active - sec: second - PROG: Programming active - min: minute - n: number of commutations Modes annunciation and Tests 1 Top yellow led for Manual Mode position linked to the key position 1 green led for Automatic Mode position linked to the key position 2 Bottom yellows leds for Test On and Off Load position Linked to the test pushbutton press Symbols are represented to make comprehension easier Source availability 2 green Leds to indicate if Gen and Mains sources are available (voltage and frequency measurement) - Led is on = source available - Led is off = source missing Keypad
Following diagram introduces product front panel. Led indication is only active once the product is powered (power led activated).
Error Led 1 red led to indicate a fault - Led is on = switch error Action from software not confirmed by an auxiliary contact. Reset after power off - Led blinks in case of lightning protection operation No reset required (blinking disappears once input is low)
ATI 067 A
Switch state 2 green Leds to indicate if the switch is opened or closed - Led is on = switch is closed - Led is off = switch is opened 1 Yellow led to indicate if both switches are in 0 position - Led is on = both switches opened - Led is off = Gen or Mains switch closed
Power Led 1 green led - Blinks slowly as soon as the product is powered and software runs correctly - Always on = Power OK and software error - Always off = Power off or software error if another led is on and LCD is OK
Push button
: Home push button during programming : Lamps test button
Retransfer Inhibit 1 yellow Led, linked to retransfer inhibit pushbutton - Led is on = retransfer inhibit feature is active - Led is off = retransfer inhibit inactive - Led is blinking = retransfer is blocked, waiting for a push on the retransfer inhibit pushbutton to allow retransfer
Switch Position Indications 0, 1 or 2 position display Keyswitch Insert key to allow switch operational mode modification Turn right to access automatic mode Turn left to access manual mode
ATI 068 A
Manual Operation Insert handle to manually operate the switch. Manual operation only possible in Manual mode (keyswitch), when not padlocked
Padlock Pull the yellow handle to allow padlock insertion Padlocking possible in position 0,1 or 2 but only in Manual mode (keyswitch position), handle out of housing.
44
Version Number
PROGRAMMING ACCESS Programming mode is accessible by pressing and holding the validation pushbutton for 5 seconds and then entering the code 1000:
Validate
Access to programming Menus PROGRAMMING EXIT To exit the Programming and come back to visualisation mode, hold the validation pushbutton for 5 seconds. Parameters saved permanently once exit.
ATI 070 A
45
ENGLISH
Before rst product use, access programming mode and verify product programming parameters.
Product Programming Product Programming is possible in It is not accessible when a test or an Automatic Mode in position 1 when the automatic sequence is activated. Mains Source is available, or in Manual mode.
ATI 068 A GB
{ {
Optional
46
ATI 071 A
Press Press or
Down push button to access parameter required. Up push button to come back to previous value, or press Home push button to come back to
nt: Network conguration. Type of metering (1P or 3P phases). Number of active wires (2L, 3L or 4L) denition. Fn: Nominal frequency.
3P4L
50 or 60 Hz
50 Hz
trI: Retransfer inhibit feature: press on RTI button required to allow retransfer from gen to main.
Yes or No
No
Crs: Reset number of commutation counter (from Main to Gen). Displays no once reset.
Yes or No
No
ATI 073 A
47
ENGLISH
Press
Press
Press
Press
Press
To return to Setup menu press home pushbutton or press down to continue. Press to return to Setup menu Press to reach next parameter
ATI 074 A
48
ATI 075 A
ATI 076 A
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to .
101 - 119 %
110 %
80 - 98 %
85 %
81 - 99 %
95 %
102 - 120 %
115 %
101 - 119 %
110 %
80 - 98 %
85 %
81 - 99 %
95 %
49
ENGLISH
Press Press or
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to .
100.5 - 119.5 %
103 %
80 - 99 %
95 %
80.5 - 99.5 %
97 %
101 - 120 %
105 %
100.5 - 119.5 %
103 %
80.5 - 99.5 %
95 %
80 - 99 %
97 %
50
Press Press or
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to .
Denition 2Mt: loss of mains validation timer. Once mains has disappeared, 2Mt is started. If Mains comes back before 2Mt ends, the commutation cycle is not started. (Delay on Gen start.) At: Generator voltage and frequency stabilisation timer. Generator needs to be stable during AT to allow transfer from Mains.
0 to 60 sec.
5 sec.
1Mt: Mains Return validation timer. Once main is back 1Mt is started. If Mains disappears before 1Mt ends, the load is not switched back to the Mains. rot: Run on time timer. Once the load is switched back from the Generator to the Mains, ROT is started and the Generator will stop once ROT is nished (allows generator cool down).
0 to 30 min.
2 min.
0 to 10 min.
4 min.
dbt: Dead Band timer. This timer is counted down before transferring the load from the Mains source to the Generator or vice versa. It allows the load residual voltage to decrease under a non critical value before transfer (Necessary in case of rotating loads).
0 to 20 sec.
5 sec.
ATI 079 A
51
ENGLISH
This menu is only accessible when the option has been purchased and is present in the optional slots. Once plugged into the electronic module, a 3 minutes power off action is required for option identication by software.
To reach timer menu from frequency menu press once Parameter Display
The COMM menu integrates 4 Communication operation is described in parameters described in the table paragraph 5. hereunder. The table explains parameters denition, settings possibilities, and default values.
Press Press or
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to .
9600
Stop Bit
0,1,2
Parity
ATI 080 A
No
52
ATI 081 A
53
ENGLISH
Main frequency Reminder: Mains sensing is 3 phases. Generator sensing is single phase.
Generator Frequency
LIP = option
Lightning protection operation (0 or 1)
54
Padlock is only possible in manual position. handle must be out of its housing to padlock padlock is possible in position 0, 1, 2. Manually pull the padlock handle to allow padlock insertion in the hole. Manual mode operation Once in manual mode it is possible: To access programming and visualisation menus To padlock the switch To operate the switch with the handle To start the Gen using test off load pushbutton.
MANUAL MODE
Programming
Visualisation
Padlocking
Handle Operation
55
ENGLISH
Possible actions Once in automatic mode it is possible: To access programming and visualisation menus To start off load or on load testing To start a loss of Mains sequence To start a Mains return sequence
AUTO MODE
Programming Visualisation
On load testing
Manual-automatic mode/power return condition As soon as the unit is switched from The same table is considered after a Manual to Automatic mode, the autocomplete power off action (Power matic cycle is started. Cap must be completely discharged Mains and Generator voltage & = 3 minutes). Read timers denition for 1MT or 2MT frequency are verified to define the understanding. new stable position of the switch. New stable switch position: Original switch position Mains Mains Status of supply Available, genset available or unavailable Mains unavailable for 2MT time period, genset available or unavailable Genset on load, mains unavailable Genset on load, mains available for 1MT time period Mains available, genset unavailable Mains available, genset available Mains unavailable, genset available Mains unavailable, genset unavailable New position Mains Genset. If genset unavailable start genset rst and wait for AT timer period before transfer Genset Mains Genset to count down 1MT before transfer to Mains Mains Genset No action (because no supply). When supply becomes available change to mains or genset
The switch immediately transfers as soon as the keyswitch is turned from Manual to Automatic mode or as soon as Power comes back.
56
Sequence description
Automatic mode
Loss of mains?
No Loss of main?
Yes
Genset start up
Start Genset
Generator available?
Yes
No
Yes ATI = AT max ? Reset AT No No ATI = 1 ? Gen fails Count down AT Yes
AT = 0
Yes DBT 0 ?
No
Transfer 1
>0
DBT = 0
Transfer 0
>2
Transfer 1
>2
Transfer 1
ATI 083 A
>2
57
ENGLISH
ATI 084 A GB
58
Mains return
Mains return? No Yes
Manual re-transfer
Yes
No
Loss of Mains ?
RTI activated?
Yes
No
Yes
RTI PB pressed ?
No
Yes
DBT 0? No
Transfer 2
>0
Transfer 0
>1
Transfer 2
>1
Reset ROT
Transfer 2
>1
ATI 085 A GB
59
ENGLISH
Press
during 5 sec
Press
4 times to display 4
Validate
Press and hold the test pushbutton for 5 seconds to exit test mode and come back to visualisation mode after test TEST achievement.
60
ATI 086 A
Sequence Press Test pushbutton to make test off load Led blink and press validation pushbutton to start.
Press Test Push button TEST Press Test Push button 5 seconds to exit TEST
No
Yes
Validate
Start Gen
No Gen ?
Yes Validate
No Stop G ?
ATI 087 A GB
Validate
61
ENGLISH
This mode allows generator testing This test is possible in automatic or without load transfer from the Mains manual mode This test is not possible when an to the Generator. automatic sequence is running. The generator is started and stopped normally
62
Verify power applied on the electronic module power inputs terminals 101-102 or 201-202 before powering up the unit.
The product provides sources availability monitoring, Automatic/Manual Retransfer, Manual / Automatic or Test operation monitoring, voltage and frequency metering, and good operation or error information. The product provides sources error information. Furthermore, the metering module allows current and power metering on a large backlited display.
The product requires at least one type of network conguration and a network nominal voltage configuration to be input via the keypad by the user. Other default values can be kept or modied according to hereafter programming guidelines.
It integrates the following features: - Voltage and frequency metering - Automatic transfer controls
LCD Larger LCD to display information. Keypad
Led indication is only active once the product is powered (power led activated).
Error Led 1 red led to indicate a fault - Led is on = switch error Action from software not confirmed by an auxiliary contact. Reset after power off - Led blinks in case of lightning protection operation No reset required (blinking disappears once input is low)
Modes annunciation and Tests 1 Top yellow led for Manual Mode position linked to the key position 1 green led for Automatic Mode position linked to the key position 2 Bottom yellows leds for Test On and Off Load position Linked to the test pushbutton press Symbols are represented to make comprehension easier
Source availability 2 green Leds to indicate if Gen and Mains sources are available (voltage and frequency measurement) - Led is on = source available - Led is off = source missing Power Led 1 green led - Blinks slowly as soon as the product is powered and software runs correctly - Always on = Power OK and software error - Always off = Power off or software error if another led is on and LCD is OK
Switch state 2 green Leds to indicate if the switch is opened or closed - Led is on = switch is closed - Led is off = switch is opened 1 Yellow led to indicate if both switches are in 0 position - Led is on = both switches opened - Led is off = Gen or Mains switch closed
Push button
: Home push button during programming : Lamps test button
Retransfer Inhibit 1 yellow Led, linked to retransfer inhibit pushbutton - Led is on = retransfer inhibit feature is active - Led is off = retransfer inhibit inactive - Led is blinking = retransfer is blocked, waiting for a push on the retransfer inhibit pushbutton to allow retransfer
Switch Position Indications 0, 1 or 2 position display Keyswitch Insert key to allow switch operational mode modification Turn right to access automatic mode Turn left to access manual mode
Manual Operation Insert handle to manually operate the switch. Manual operation only possible in Manual mode (keyswitch), when not padlocked
Padlock Pull the yellow handle to allow padlock insertion Padlocking possible in position 0,1 or 2 but only in Manual mode (keyswitch position), handle out of housing.
ATI 068 B
63
ENGLISH
Before rst product use, access programming mode and verify product programming parameters.
Product Programming Product Programming is possible in It is not accessible when a test or an Automatic Mode in position 1 when the automatic sequence is activated. Mains Source is available, or in Manual mode. PROGRAMMING ACCESS Programming mode is accessible by pressing and holding the validation pushbutton for 5 seconds and then entering the code 1000:
Validate
Access to programming Menus PROGRAMMING EXIT To exit the Programming and come back to visualisation mode, hold the validation pushbutton for 5 seconds. Parameters saved permanently once exit.
64
ATI 070 B
{ {
Version Number
Option
ATI 071 B
65
ENGLISH
Press Press or
Down push button to access parameter required. Up push button to come back to previous value, or press Home push button to come back to
Denition
NOM.VOLT : Phase-Phase nominal voltage.
Setting range
From 200 to 480 V
Default value
400 V AC
NETWORK : Network conguration. Type of metering (1P or 3P phases). Number of active wires (2L, 3L or 4L) denition. NOM.FREQ : Nominal frequency.
3P4L
50 or 60 Hz
50 Hz
50 / 5 to 1600 / 5
500 / 5
TRANS IHI : Retransfer inhibit feature: press on RTI button required to allow retransfer from gen to main.
Yes or No
No
66
ATI 073 C
CNT RST : Reset number of commutation counter (from Main to Gen). Displays no once reset.
Yes or No
No
Press
Press
Press
Press
Press
ATI 074 B
Press
Press
ATI 075 B
ATI 076 B
67
ENGLISH
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to
Denition
OV U : Main Over voltage detection
Setting range
102 - 120 %
Default value
115 %
101 - 119 %
110 %
80 - 98 %
85 %
81 - 99 %
95 %
102 - 120 %
115 %
101 - 119 %
110 %
80 - 98 %
85 %
81 - 99 %
95 %
68
ATI 077 B
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to
Setting range
101 - 120 %
Default value
105 %
100.5 - 119.5 %
103 %
80 - 99 %
95 %
80.5 - 99.5 %
97 %
101 - 120 %
105 %
100.5 - 119.5 %
103 %
80.5 - 99.5 %
95 %
80 - 99 %
97 %
69
ENGLISH
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to
2Mt: loss of mains validation timer. Once mains has disappeared, 2Mt is started. If Mains comes back before 2Mt ends, the commutation cycle is not started. (Delay on Gen start.) At: Generator voltage and frequency stabilisation timer. Generator needs to be stable during AT to allow transfer from Mains.
0 to 60 sec.
5 sec.
1Mt: Mains Return validation timer. Once main is back 1Mt is started. If Mains disappears before 1Mt ends, the load is not switched back to the Mains. dbt: Dead Band timer. This timer is counted down before transferring the load from the Mains source to the Generator or vice versa. It allows the load residual voltage to decrease under a non critical value before transfer (Necessary in case of rotating loads). rot: Run on time timer. Once the load is switched back from the Generator to the Mains, ROT is started and the Generator will stop once ROT is nished (allows generator cool down).
0 to 30 min.
2 min.
0 to 20 sec.
5 sec.
0 to 10 min.
4 min.
70
ATI 079 B
This menu is only accessible when the option has been purchased and is present in the optional slots. Once plugged into the electronic module, a 3 minutes power off action is required for option identication by software.
To reach timer menu from frequency menu press once Parameter Display
The COMM menu integrates 4 Communication operation is described in parameters described in the table paragraph 5. hereunder. The table explains parameters denition, settings possibilities, and default values.
Press Press or .
Down push button to access parameter required. Up push button to come back to previous value Home push button to come back to
9600
Stop Bit
0,1,2
Parity
ATI 080 B
No
71
ENGLISH
Option
ATI 081 B
72
Generator Frequency
ENGLISH
Main frequency
MAINS RETURN AUTOMATIC SEQUENCE This sequence is started as soon as the unit is in automatic mode and in position 2. Position 2: Mains is not available Switch is in position 2 (Generator) Generator is off Specic features
Retransfer Inhibit Feature Once retransfer from the Generator to the Mains is ready, RTI feature Once the Mains is back, it might be blocks the retransfer and the RTI led preferable not to immediately transfer is blinking. the load from the generator to the A manual press on the RTI push butmains. ton is necessary to start retransfer. If Retransfer inhibit feature has been enabled in the programming mode, the RTI led is on (default value).
ATI 084 B GB
74
Press
during 5 sec
Press
4 times to display 4
Validate
Press and hold the test pushbutton for 5 seconds to exit test mode and come back to visualisation mode after test TEST achievement. Test on load and test off load facilities are similar to the basic product.
ATI 086 B
75
ENGLISH
COMMUNICATION
The JBUS/MODBUS used by the ATI involves a dialogue using a masterslave hierarchical structure. There are two possible dialogues: the master communicates with a slave (ATI) and waits for its reply the master communicates with all the slaves (ATI) without waiting for their reply. The mode of communication is the RTU (Remote Terminal Unit) using hexadecimal characters of at least 8 bits.
NB: When selecting slave address 0, a message is sent to all the instruments present on the network (only for functions 6 and 16).
According to the JBUS / MODBUS To correctly use information, the protocol, transmission time must be following functions are important: less than 3 silences, i.e. the emission 3 : to read n words (maximum 128). time of 3 characters so that the mes6 : to write one word. sage is processed by the ATI. 8 : to diagnose exchanges between the master and the slave via meters 1, 3, 4, 5 and 6. 16 : to write n words (maximum 128). LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) Table of values on 2 words Decimal Address 768 770 772 774 776 778 780 782 784 786 788 790 792 794 796 880 882 884 886 888 890 892 894 895 896 897 898 Hexa Address 300 302 304 306 308 30A 30C 30E 310 312 314 316 318 31A 31C 370 372 374 376 378 37A 37C 37E 37F 380 381 382 Number of words Variable Units 2 I1 A/100 2 I2 A/100 2 I3 A/100 2 In A/100 2 U12Main V/100 2 U23Main V/100 2 U31Main V/100 2 V1Main V/100 2 V2Main V/100 2 V3Main V/100 2 Freq.Main Hz/100 2 Active power (total) kW/100 2 Reactive power (total) kVar/100 2 Apparent power (total) kVA/100 2 Power factor 0,001 2 U12 Gen V/100 2 U23 Gen V/100 2 U31Gen V/100 2 V1Gen V/100 2 V2Gen V/100 2 V3Gen V/100 2 FreqGen Hz/100 1 1MT V/100 1 2MT V/100 1 AT s 1 DBT s 1 ROT s
Example: To read U31 gen = 228,89, the following message should be sent:
76
COMMUNICATION (continued)
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued) Slave
05
Function
03
High-order address
03
Low-order address
74
High-order word n
00
Low-order word n
02
CRC 16
85D1
Function
03
04
59 89
69 105
458D
Table of values on 1 word Decimal Address 1792 1793 1794 1795 1796 1797 1798 1799 1800 1801 1802 1803 1804 1805 1806 1807 1808 1809 1810 1813 1814 1815 1816 1817 1818 1819 1820 Hexa Address 700 701 702 703 704 705 706 707 708 709 70A 70B 70C 70D 70E 70F 710 711 712 715 716 717 718 719 71A 71B 71C Number of words Variable 1 U12 Main 1 U23 Main 1 U31 Main 1 V1 Main 1 V2 Main 1 V3 Main 1 Freq. Main 1 U12 Gen 1 U23. Gen 1 U31 Gen 1 V1. Gen 1 V2. Gen 1 V3. Gen 1 Freq. Gen 1 1MT Timer 1 2MT Timer 1 AT Timer 1 DBT Timer 1 ROT Timer 1 I1 1 I2 1 I3 1 In 1 Active power (total) 1 Reactive power (total) 1 Apparent power (total) 1 Power factor Units V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 s s s s s A/100 A/100 A/100 A/100 kW kVar kVA 0,001
77
ENGLISH
Number of bytes
Value high-order
Value low-order
CRC 16
COMMUNICATION (continued)
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3) (continued) Table of values of the programming zone Decimal Address Hexa Number Address of words
Standard
512 513 518 519 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542
200 201 206 207 209 20A 20B 20C 20D 20E 20F 210 211 212 213 214 215 216 217 218 219 21A 21B 21C 21D 21E
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Variable Units Product Type of network x 0 = 3P4L - 1 = 1P3L 2 = 1P2L - 3 = 3P3L 4 = 1PAP CT primary A x VNominal V x FNominal - 50 or 60 Hz x 0 = No, 1 = Yes Transfer Inhibit Feature x VOver % (0-100) x VHystOver % (0-100) x VUnder % (0-100) x VHystUnder % (0-100) x VGenOver % (0-100) x VHystGenOver % (0-100) x VGenUnder % (0-100) x VHystGenUnder % (0-100) x FOver % (0-100) x FHystOver % (0-100) x FUnder % (0-100) x FHystUnder % (0-100) x FGenOver % (0-100) x FHystGenOver % (0-100) x FGenUnder % (0-100) x FHystGenUnder % (0-100) x 1MT Timer min x 2 MT Timer s x AT Timer s x DBT Timer s x ROT Timer min x
Slave
Hex Dec 05
Function
10 16
N word
00 01
N octet
02
CRC 16
76B8
Function
10
High-order address
02
Low-order address
06 89
N word
00 105 01
CRC 16
E1F4
78
COMMUNICATION (continued)
SAVED COMMAND (RESET) The following command should be done to save programming parameters changes for ATI number 5.
05
06
06
00
0000
88C6
Diagnostic zone
Decimal Hexa Address Address 257 101 258 102 Number of words 1 1 Variable Product Identication Slot Ident Option 1 Standard version 1239 Metering version 1241 available option 0 communication option Option of slot 1 0xFF no option 0x20 Main/Gen available option 0 communication option Option of slot 2 0xFF no option 0x20 Main/Gen soft version of product serial number 3 stable states Bit3 Bit2 Bit1 Bit0 1 0 1 0 Auto 1 0 0 1 Padlock 0 1 1 0 Manu 3 stable states Bit2 Bit1 Bit0 0 0 1 Position 1 0 1 0 Position 0 1 0 0 Position 2 Counter number of transfer 2 stable states Bit1 Bit0 1 0 relay stopped 0 1 relay started
259
103
2 1 2 17 1
282
11A
Switch State
2 1 1
79
ENGLISH
Slave
Function
High-order address
Low-order address
Values
CRC 16
MAINTENANCE
N F H
G1 G2 J E I K
M D L C A B
63/100/125A
250/400A BB
H = 876 L = 596
Ref : 610-832 (BB) Ref : 610-833 (TT)
H = 876 L = 596
Ref : 610-832
Ref : 610-834
Enclosure
BB H = 600
H
L = 400 P = 230
Lp = 276 Pp = 128
Ref : 590-950
Lp = 495 Pp = 245
Ref : 590-951
Lp = 495 Pp = 328
Ref : 590-953
Ref : 530-956
80
ATI 088 A GB
MAINTENANCE (continued)
63/100/125A 250/400A
Ref : 603-413 (250A) Ref : 603-414 (400A)
630A
Ref : 603-415
Ref : 603-412
G1
G1 : Ref : 650-881 230V Version (basic product) Ref : 650-883 (metering product) G2 : Ref : 601-700 (63A) Ref : 601-701 (100A) Ref : 601-702 (125A) G1 : Ref : 650-882 277V Version (basic product)
G2
Motorized Module
L
Ref : 650-884 (metering product) G2 : Ref : 601-736 (63A) Ref : 601-737 (100A) Ref : 601-738 (125A)
G1 : Ref : 650-882 (basic product) Ref : 650-884 (metering product) G2 : Ref : 601-739 (250A) Ref : 601-740 (400A)
G1 : Ref : 650-882 (basic product) Ref : 650-884 (metering product) G2 : Ref : 601-741
H = 180 L = 200
P = 250 l = 145
Ref : 330-169
Ref : 330-168
x1 x3
I
ATI Connectors Kit / ATI Voltage Sensing Kit
Ref : 656-932
Ref : 656-931
Ref : 656-935
Terminal Shroud
Pc
Hc = 300 Lc = 177
Hc
Pc = 176
Rc
Rc = 47
Lc
Ref : 604-668
Ref : 604-669
L M
Manual/auto Key
x2
Ref : 531-273
x4
Ref : 509-310 Ref : 530-195 Ref : 530-196
N O
81
ENGLISH
G1 : Ref : 650-881 (basic product) Ref : 650-883 (metering product) G2 : Ref : 601-703 (250A) Ref : 601-704 (400A)
G1 : Ref : 650-881 (basic product) Ref : 650-883 (metering product) G2 : Ref : 601-705
MAINTENANCE (continued)
N F H
G1 G2 J E I K
M D L C A B
800/1000A
1250 / 1600A
H = 1580 L = 990
Enclosure
H = 1175
H
L = 775 P = 596
Top Plate
Bottom Plate
Lp = 536 Pp = 480
Ref : 590-957
Lp = 1000 Pp = 800
Ref : 590-958
Lp = 916 Pp = 717
Ref : 590-961
D E
Wall Mounting Brackets Manual changeover 800A H = 321 L = 466 1000A H = 330 L = 466 P = 327 H = 1000 L = 716 P = 392
Ref : 604-685 (1250A) Ref : 604-686 (1600A)
P = 327
82
MAINTENANCE (continued)
800/1000A 1250 / 1600A
G1
230V Version
G2
Motorized Module
L
277V Version
G1 : Ref : 650-882 (basic product) Ref : 650-884 (metering product) G2 : Ref : 601-742 (800A) Ref : 601-743 (1000A)
G1 : Ref : 650-882 (basic product) Ref : 650-884 (metering product) G2 : Ref : 601-744 (1250A) Ref : 601-745 (1600A)
H = 270 L = 260
P = 250 l = 145
H = 270 L = 260
Ref : 330-171 (1250A) Ref : 330-172 (1600A)
P = 250 l = 145
Ref : 330-170
x1 x3
I
ATI Connectors Kit / ATI Voltage Sensing Kit
Ref : 656-943
Ref : 656-931
Ref : 656-944
160
29 5
510 338
Terminal Shroud
Pc 165
308
Rc
345
200
Lc
Ref : 604-682
L M
Manual/auto Key
x2
Ref : 531-273
x4
Ref : 509-310 Ref : 509-314 Ref : 530-197
940
360
x2
N O
83
ENGLISH
G1 : Ref : 650-881 (basic product) Ref : 650-883 (metering product) G2 : Ref : 601-732 (800A) Ref : 601-733 (1000A)
G1 : Ref : 650-881 (basic product) Ref : 650-883 (metering product) G2 : Ref : 601-734 (1250A) Ref : 601-735 (1600A)
Hc
ACTION
Check that there is a 230V 20 %* AC supply on the mains or gen power supply terminals (101,102 for mains & 201, 202 for gen). * or 277V 20 % Check Lamp Test. Make sure correct nominal voltage, network conguration & frequency has been set. Check under / over, voltage / frequency, parameters. Check key switch is in Auto mode (AUT). Check two wire start signal to gens autostart control panel. Check Lamp Test. Make sure genset has the same nominal voltage, network conguration & frequency as the mains. Check under / over voltage / frequency parameters. Check that mains restoration timer is not too long. Check key switch is in Auto mode (AUT). Check mains voltage is within restoration limits. Verify if manual retransfer has been disabled.
Switch retransfers ok when mains restores, but gen keeps on running Switch will not transfer with the handle
Check that the ROT timer is not at a long setting. Check the start signal contact on the module. Check key switch is in manual position. Check that the switch has not been padlocked. Check the required rotation of the switch. Check that sufcient torque has been applied to the handle. Check that handle has been removed from the shaft. Check that the switch has not been padlocked. Check that the correct key is used.
Verify password entered is 4 000. Verify if the Lightning protection did not operate. Replace the fuses or the lightning protection module if damaged. Power off the unit by removing power on power terminals 101, 102 & 201, 202 during three minutes and power up again.
84