Light Bulb Test.: 0 and Ignition Angle Limit 30 % in (Set Up) (T/R)

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 1

Light bulb test.

P-1

1. Turn off power to the cubicle with the mains switch. Follow the local safety instructions of the plant! 2. Disconnect the power cables between the control cubicle and the T/R and connect 2nos light bulbs in place of T/R. The light bulbs have to withstand the full line voltage. (415V AC ) 3. Turn on power to the cubicle. Follow the local safety instructions of the plant! 4. Set temporarily Voltage limit low warning = 0, Voltage limit low trip = 0 and Ignition angle limit = 30 % in [Set Up] [T/R] 5. Set temporarily Arc det. level = 0 in [Process settings] [Spark settings]. 6. Turn on the ignition by High voltage ON in [Operation]. 7. Check that the power to the light bulbs is controllable by setting Ignition angle limit to values between 1 and 100%. If so the phase is okay, continue with point 10. 8. If the light does not change it is probably because the phase reference is shifted 180 . This can be corrected by switching the reference voltage to the EPIC III as follows: A. Turn off power to the cubicle with the mains switch. Follow local safety instructions! B. Swap the wires to EPIC III terminal 10 and 22 (Primary line voltage transformer input). This is the phase reference to the EPIC III. C. Repeat from point 3 above. 9. Turn off power to the cubicle with the mains switch. Follow the local safety instructions of the plant! The temporary settings in EPIC III are lost. 10. Disconnect the light bulbs and connect power cables to the T/R. 11. Turn on power to the cubicle. Follow the local safety instructions of the Plant.

You might also like