Open circuit test.

P-1

1. Turn off power to the cubicle with the mains switch. Follow the local safety instructions of the plant! 2. Disconnect the TR out put from ESP Field. 3. Turn on power to the cubicle. Follow the local safety instructions of the plant! 4. Set temporarily Ignition angle limit =10% to 40 % in [Set Up] [T/R] 5. Turn on the High voltage ON in [Operation]. 6. Check that the Panel Meter and Reading window in PC. ( KVp/KVa/KVv ). A. Turn off power to the cubicle with the mains switch. Follow local safety instructions! 7. Turn off power to the cubicle with the mains switch. Follow the local safety instructions of the plant! The temporary settings in EPIC III are lost. 8. Connect the TR out put to ESP Field. 9. Turn on power to the cubicle. Follow the local safety instructions of the Plant.