GUARANTEED TECHNICAL PARTICULARS FOR 66KV POTENTIAL TRANSFORMERS S.

NO DESCRIPTION GUARANTEED PARTICULARS 1 2 3 4 5 6 7 8 9 10 11 12 13 Type Nominal System Voltage & Frequency Highest System Voltage Application Neutral Earthing No of secondary Secondary Rated Primary Voltage Rated Secondary Voltage Burden Accuracy Class Rated Voltage factor Reference Ambient Temperature Max.Temp Rise over design ambient Temperature at and voltage & Frequency Dynamic rating Outdoor , Oilfilled Hermetically Sealed Dead Tank 66KV, 50HZ 72.5KV Outdoor HV Neutral solidly earthed Three Secy I 66KV/3 110V/3 300VA 3P 50C Max 50 over 50C Secy II 66KV/3 110V/3 200VA 0.2 Secy III 66KV/3 110V/3 50VA 3P

1.2 Continuous/ 1.5 for 8 Hours

14

Not applicable since PT is a high impedance path in the circuit and fault current will not be flowing in PT. Oil immersed Class 'A' 1815mm Not applicable since offered PT is induction type. 800KG 140KV rms 340 KVp Will be Provided Weather proof box , sheet steel clad of min 3mm thick complete with fuse/MCB , terminals & wiring for neutral earthing will be provided. Two terminal boxes one for secondary that can be sealed and another one for earthing primary will be provided.

15 16 17 18 19 20 21 22

Class of Insulation Creepage Distance Rated Capacitance Cantilever strength 1 minute power frequency withstand voltage 1.2/50 mic sec impulse voltage Oil level gauge, filling & Drain plugs Secondary Terminal Box

23

For Tariff metering

24

Earthing pads

Each equipment shall be provided with 2 nos grounding pad with 2 nos M10 bolts