TRANSFORMER TEST CERTIFICATE

Date: 16-11-12

A:-MAKE-

UNVERSAL VOLTAGECONNECTION2- Polarity :- OK 2 + 0.04 +0.08 +0.05 3 + 0.05 +0.06 +0.04 4 +0.04 +0.05 +0.09

HV 6.6 Delta

LV 0.433 Star 3- Vector Group :- DYN11

B:-MAKER SL NO- FCB-005/0005 C:-RATING- 250 KVA 1-No Load Voltage Ratio in % Error :Tap Position : U-V V-W W-U 1 + 0.06 +0.04 + 0.02

5 +0.07 +0.09 +0.04

4 DC Resistance Measurement :HV Side (Ohms) U-V V-W W-U 2.1 2.6 2.9 LV Side (milli Ohms) u-v 0.0062

v-w 0.0068 w-u 0.0064 Average/Phase

Average/Phase 5 No Load Loss TestV 441 I 2.5 W1 395

W2 259

MF 4

LOSS 898 Watts

6- Load Test (Normal Tap)I 21/22 A V 319/341 W1 405 W2 59 MF 8 LOSS 2955/3655

I2R Loss at Test Temperature Load Loss at Test Temp at full load : I2R Loss at 750C Stray Loss at Test Temperature Stray Loss at 750C Short Ckt Loss at 750C

3458 Watts 3689 Watts 3458 Watts 245 Watts 222 Watts 3465 Watts

% Imp at Test Temp % Resistance at Test Temp % Reactance % Resistance at 750 C % Impedance at 750C

5.458 1.986 5.325 1.466 5.477

7- Separate Source Voltage for 60sec :H.V. L.V. 18 3 K.V K.V. withstood withstood

Leakage Current :18 mA 6 mA

8- Induced Over Voltage Test 0.866 KV applied on LV side for 60 seconds at frequency 100 Hz withstood. 9- Measurement of Insulation Resistance (M Ohms) HV LV 3000 Insulation Tester2500 HV EARTH 2500 Make-WACO LV EARTH 2200

10- Dielectric Strength of Oil : The oil of the above transformer withstood 67 KV(rms) with 2.5 mm gap setting