Stephen Pierce Condition Monitoring Officer AGL Torrens Island Power Station
Condition Monitoring Of Electrical Assets Types of condition monitoring. Thermography Motor testing Transformer oil analysis Battery testing Ultrasonics Vibration Lube oil analysis
Switchgear and Control gear Assemblies (AS3439) Terminals of load cables; 70C Temperature rise limit. External covers; Metal, 30C Temperature rise limit. Insulating, 40C Temperature rise limit. Fuses (AS60269.1) Contacts tin plated;
Spring, 60C Temperature rise limit. Bolted; 65C Temperature rise limit.
14C
23C
16C
26C
Motor testing
Insulation testing
Using the appropriate equipment to test the quality of the insulation from phase to earth and between phases to determine if it will withstand the applied voltage.
16.5
16
mH
15.5
15
14.5
14
Degrees
AS 2676.1 1992; Vented cells AS 2676.2 1992; Sealed cells Guide to the installation, maintenance, testing and replacement of secondary batteries in building