Butterfly Valve Specification

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

BUTTERFLY VALVE SPECIFICATION

GENERAL REQUIREMENT

SIZE FLUID HANDLED TEMPERATURE

: 400MM 450MM 500MM 600MM : WATER : AMBIENT TEMPERATURE

LEAK TIGHTNESS DUTY

TIGHT SHUT OFF / LOW LEAKAGE REGULATION/ INCH/ ON-OFF

: TIGHT SHUT OFF : REGULATION

MATERIAL OF CONSTRUCTION

BODY DISC SHAFT SEAT RING CLAMPING RING SEGMENT BEARING SEAL

: : : : : : :

CAST IRON IS 210Gr.FG260 S.G.IRON IS 1865 Gr.FG 500/7 AISI410 ST.STEEL ASTM A 240 TYPE 304 ST.STEEL ASTM A 351 TYPE CF8 ST.STEEL PACKED PTFE BUNA-N- NITRILE

MODE OF OPERATION

MANUAL LEVER/G BOX WITH H WHEEL ELECTRICAL PNEUMATIC OPERATING TIME

: GEAR BOX WITH HANDLE WHEEL : YES : NO : CLOSE-OPEN-CLOSE < 15 MIN

CONSTRUCTION

FLANGED/ WAFER GOVERNING STAND FACE TO FACE DIMENSIONS (MM)

: FLANGED : BS5155 : 216, 222, 229, 267

UPS SPECIFICATION

CAPACITY INPUT VOLTAGE INPUT FREQUENCY INPUT POWER FACTOR BATTERY/DC LINK VOLTAGE

: 3 KVA : 1 PHASE 230V INPUT : 50 HZ +/- 6% : 0.7 TO 0.85 : VENDOR SPECIFIC

CHARGER TYPE INVERTER BACK-UP TIME OUTPUT VOLTAGE OUTPUT FREQUENCY

: IGBT BASED : IGBT : 1 HOUR : 1 PHASE 230V AC, 50HZ : 50Hz, +/-O.1% FREE RUNNING : 50Hz, +/ -3%-BYPASS SYNC.

BATTERIES LOAD POWER FACTOR RANGE INVERTER EFFICIENCY

: SOUTHERN : 0. 6 TO 1 WITHIN KVA : 90%

UPS SPECIFICATION

CAPACITY INPUT VOLTAGE INPUT FREQUENCY INPUT POWER FACTOR BATTERY/DC LINK VOLTAGE

: 7 KVA : 3 PHASE 415V INPUT : 50 HZ +/- 6% : 0.7 TO 0.85 : VENDOR SPECIFIC

CHARGER TYPE INVERTER BACK-UP TIME OUTPUT VOLTAGE OUTPUT FREQUENCY

: IGBT BASED : IGBT : 1 HOUR : 3 PHASE 415V AC : 50Hz, +/-O.1% FREE RUNNING : 50Hz, +/ -3%-BYPASS SYNC.

BATTERIES LOAD POWER FACTOR RANGE INVERTER EFFICIENCY

: SOUTHERN : 0. 6 TO 1 WITHIN KVA : 90%

PROBE UNIT PROBE TYPE MOUNTING PROBE LENGTH PROBE WIRE SS_304 COUNTER WEIGHT PROCESS CONNECTION PROBE ENCLOSURE FLANGE D, 2" ANSI,#1S0 CAST AI. 20 RNETRES(MAX) FLEXIBLE WITH SENSING HEAD VERTICAL ON TANK TOP REF. SHEET 2 DD RU4 L, I T-H TAPED FLEXIBLE WITH

DASTANCE BETWEEN PROBE AND CONTROL UNIT SENSITIVITY CONTROL UNIT SWITCH ACCURACY DWTRCN/UONLACT TYPE I TRNE SETAY (TOR ATARM ; SECONDS 9T:, J0 CONTACT RATING LNDICATION 5 A AT 230 V.A.C .L'E.D- FOR ALARM LEVEL DISPLAY IPOWER REQUIREMENT - LENCLOSURE MATERIAL I ENCLOSURE PROTECTION CLASS WORKING PRESSURE 24 VDC MS SHEET FABRICATED , POWDER COATED LP:54 112" N.P.T.(F); 03 NOS REFER SHEET NO. 2 AMBIENT / 50O C 10MM +L-0.5%

DPDT (2 NO + 2 NC)

ATMOSPHERIC FFI..-T AT | |