Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 14

Pump Head Calculation Layout

Head Calculation Layout

PUMP HEAD CALCULATION


A

Water
Quantity
Header Section (GPM)
pump to R1
R1-R2
R2-R3
R3-R4
R4-R5
R5-R6
R6-R7
R7-R8
R8-R9
R9-R10
R10-R11
R11-R12
R12-R13
R13-R14
R14-R15
R15-R16
R16-R17
R17-R18

360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20

Length
Pipe Size Between Take(in)
Offs (ft)
5
5
5
5
4
4
4
4
4
4
3
3
3
3
3
2
2
1 1/4

27
18
20
20
20
8
20
20
20
8
20
20
20
20
8
20
20
20

Fittings

Fitting
Equivalent
Length (ft)

2- ells
1-tee
1-tee
1-tee
1-red, 1-tee
1-tee, 1-ell
1-tee
1-tee
1-tee
1-tee, 1-ell
1-red,1-tee
1-tee
1-tee
1-tee
1-tee, 1-ell
1-red,1-tee
1-tee
1-red,1-tee

26
8.2
8.2
8.2
12
16.7
6.7
6.7
6.7
12.7
9
5
5
5
12.5
7
3.3
5

Pump Friction He

CALCULATION
G

Total
Equivalent
Length (ft)

Friction Loss (Ft of


water per 100
equivalent Ft)

Friction Head
(ft of water)

53
26.2
28.2
28.2
32
24.7
26.7
26.7
26.7
20.7
29
25
25
25
20.5
27
23.3
25

2.3
2
1.8
1.6
4.4
3.8
3.2
2.7
2.3
2.1
5.5
4.6
3.2
2.5
1.6
6.8
3.2
6.5
Pump Friction Head

1.22
0.52
0.51
0.45
1.41
0.94
0.85
0.72
0.61
0.43
1.60
1.15
0.80
0.63
0.33
1.84
0.75
1.63
16.38

Table