Coordinaide™-The S&C Protection and Coordination Assistant
Coordinaide™-The S&C Protection and Coordination Assistant
1) DEVICE# 1: S&C Fault Tamer Fuse Limiter Speed: 450-8-3 Ampere Rating: 20 Preload: 14.45 Amps Ambient Temperature: 25C
2) DEVICE# 2: Transformer (Damage Curve) Connection: Delta-Grd.Y Primary_kV/Full Load Amps: 10/14.43 Secondary_kV/Full Load Amps: .23/627.55 Xfmr Rating: 250kVA Impedence: 4% Phase-Grd. Fault Current: 630A Phase-Grd. TPI: 323% 3-Phase Fault Current: 229.43A 3-Phase TPI: 1911% Magnetizing Inrush: @ .01 Second = 360.84A @ .10 Second = 173.21A Cold-Load Pickup Inrush: @ 1 Second = 86.6A @ 10 Seconds = 43.3A @ 900 Seconds = 28.87A