SCHEDULE OF LOADS

MAIN: 40AT, 50AF, 230 volts, 2-poles MCB Branch Circuit


1 2 3 4 5 6 7 8

Description
Lighting outlet Lighting outlet Lighting outlet Lighting outlet Convenience outlet Convenience outlet ACU SPARE

No.of Outlet
9 8 10 12 9 8 1 1

Volts
230 230 230 230 230 230 230 230

Amperes
3.91 3.48 5.22 4.35 7.04 6.26 12

VA
900 800 1200 1000 1620 1440 2760 1500

Size of wire and conduit


Use 2 - 2.0 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 2.0 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 2.0 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 2.0 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 3.5 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 3.5 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC Use 2 - 3.5 & 1-2.0 sq.mm THWN copper wire Use 1 - 20 mm diameter PVC Use 2 - 3.5 sq.mm THWN copper wire Use 1 - 15 mm diameter PVC

Over Current Protection


15AT 15AT 15AT 15AT 20AT 20AT 30AT 20AT 2pole 2pole 2pole 2pole 2pole 2pole 2pole 2pole 30AF 30AF 30AF 30AF 30AF 30AF 50AF 30AF