PSYCHROMETRIC ANALYZER

Version 6.8 by McQuay International


0 cfm exhaust

16, 2013

50 cfm exfiltration
0 cfm
310 cfm

RAT: 77.0F
50.0 %RH
30.8852 Btu/lb
0.011327 lb(w)/lb
15.75550 ft/lb

12.85 psia
50 cfm
OAT: 98F
62F wb
12.3 %RH
29.4493 Btu/lb
0.005368 lb(w)/lb
16.21796 ft/lb
30

360 cfm

MAT: 79.82F
63.4F wb
30.6907 Btu/lb
0.01052 lb(w)/lb
15.81804 ft/lb
32

81.82F
31.1804 Btu/lb
15.87674 ft/lb

0.0 lb/h
0 Btu/h
34

100

28

ZAT: 77F
50.0%RH
30.8852 Btu/lb
0.011327 lb(w)/lb
15.75550 ft/lb
63.62F wb
57.0F dp

0.8 ton
9,076 Btu/h

36
90

80

38

70

60

SAT: 57F
55.27F wb
24.8106 Btu/lb
0.010246 lb(w)/lb
15.14245 ft/lb
40

50

7,776 Btu/h
Sensible

42
40

30

0.015
0.014

26

0.013
0.012

24

RAT
MAT

SAT

20

0.011
0.010

22

0.009
0.008

20

0.007
18

0.006

OAT
16

10

0.005
0.004
0.003

14

0.002
0.001

12
50

55

60

65

70

75

80
85
90
Dry Bulb Temperature (F)

95

100

105

www.mcquay.com