CHILLER COMMISSIONING REPORT DATE: 03rd August 2013 CLIENT NAME UNIT DETAIL TYPE CHILLER : WELCARE HOSPITAL

-DUBAI : SCROLL CHILLER NO: 3 AIR COOLED CHILLER Make MCQUAY Model No MCSMART-400CFAAE Serial No 72-00040ARICCA Power Supply 380 V 3/N/E-50H/Z Nomi.Capacity 30 TR SYSTEM 2 407C 65 PSI 250 PSI 12C 38C 46C L1:
R-13.2

Refrigerant Suction Pressure Discharge Pressure

WORK PERFORMANCE DETAILS SYSTEM 1 407C Refrigerant 65 PSI 250 PSI 10.5C 39C 46C L1:
R-13.2

Suction Pressure Discharge Pressure Suction Pipe Line Temp. Cond Suction Air Temp.
Cond Discharge Air Temp

Suction Pipe Line Temp. Cond Suction Air Temp. Cond Discharge Air Temp Running Amps. Ambient Temp. Chilled Water Flow Rate Chiller Inlet Pressure Chiller Outlet Pressure Chiller Inlet Temperature Chiller Outlet Temperature
Condensing Air Temp Deff

L2:
L-12.7

L3:
B-12.7

Running Amps.

L2:
L-12.7

L3:
B-12.7

38C 100 GPM 80 PSI 74 PSI 14C 6C FOUR COMPRESSORS ARE RUNNING (BOTH SYSTEMS FULL LOAD) L2: L - 56.8 L3: B - 56.8

Total Amps

7C L1: R - 58.8

UNIT IS RUNNING/WORKING IN SATISFACTORY CONDITION JOB PREFORMED BY Engineer Name Rajan V Valathe Customer Name Signature with Date Signature with Date