Copper Pipe
Size Nominal
mm
T=2K
( P=75 kPa)
12
2.3
2.44
2.60
7.08
11.24
15
4.37
4.65
4.95
11.49
21.54
18
7.59
8.06
8.59
17.41
37.49
22
13.32
14.15
15.07
26.66
66.18
28
26.24
27.89
29.70
44.57
131.01
35
48.03
51.05
54.37
70.52
240.67
42
79.5
84.52
90.00
103.45
399.34
54
157.33
167.24
178.09
174.13
794.19
67
279.41
297.02
316.29
269.94
1414.99
79
431.31
458.50
488.24
376.47
2190.88
105
919.67
977.64
1041.05
671.98
4696.95
The above tables gives kW of refrigeration resulting in a line friction drop ( P in kPa) per 100m equivalent
pipe length as shown, with corresponding change ( T) in saturation temperature.
12.7
15.9
19.1
22.2*
28.6*
34.9*
41.3*
54.0*
Pipe OD inches
1/2
5/8
3/4
3/4
1-1/8*
1-3/8*
1-5/8*
2-1/8*
90 Standard
0.40
0.50
0.60
0.70
0.90
1.10
1.28
1.58
90 Long Radius
0.30
0.30
0.40
0.45
0.60
0.75
0.85
1.05
45 Standard
0.20
0.20
0.30
0.35
0.45
0.55
0.65
0.85
45 Long Radius*
0.15
0.15
0.20
0.22
0.30
0.37
0.43
0.57
Table T Loss
Actual Le
Note 2. For other Capacity and Equivalent Lengths in a given pipe size:
1 .8
0 .55
For capacities at other condensing temperatures, multiply table capacity by the following factors:
Condensing Temperature, C
20
30
40
50
Suction Lines
Hot Gas Lines
1.18
1.10
1.00
0.91
0.80
0.88
1.00
1.11
Source: ASHRAE
Wills, I; Simplified R22 Suction Line sizing, AIRAH journal, pg 30-31 (June 2001)