2000handbook Amendment01 R22

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

REFRIGERANT PIPE CAPACITY - R22

Fig 1 R22 Suction line capacity for 1K equivalent pressure drop

Amendment Replaces pages 1016 1017 AIRAH HANDBOOK Millenium Edition

Copper Pipe
Size Nominal
mm

100m Discharge Line: T=2 K,


( P=75kPa)
Saturated Suction Temperature, C
-40
-20
+5

100m Liquid Line


Velocity = 0.5 m/s

T=2K
( P=75 kPa)

12
2.3
2.44
2.60
7.08
11.24
15
4.37
4.65
4.95
11.49
21.54
18
7.59
8.06
8.59
17.41
37.49
22
13.32
14.15
15.07
26.66
66.18
28
26.24
27.89
29.70
44.57
131.01
35
48.03
51.05
54.37
70.52
240.67
42
79.5
84.52
90.00
103.45
399.34
54
157.33
167.24
178.09
174.13
794.19
67
279.41
297.02
316.29
269.94
1414.99
79
431.31
458.50
488.24
376.47
2190.88
105
919.67
977.64
1041.05
671.98
4696.95
The above tables gives kW of refrigeration resulting in a line friction drop ( P in kPa) per 100m equivalent
pipe length as shown, with corresponding change ( T) in saturation temperature.

REFRIGERANT PIPE CAPACITY - R 22 (cont.)


FITTING EQUIVALENT LENGTHS (METERS OF STRAIGHT PIPE)
Pipe OD mm

12.7

15.9

19.1

22.2*

28.6*

34.9*

41.3*

54.0*

Pipe OD inches

1/2

5/8

3/4

3/4

1-1/8*

1-3/8*

1-5/8*

2-1/8*

90 Standard

0.40

0.50

0.60

0.70

0.90

1.10

1.28

1.58

90 Long Radius

0.30

0.30

0.40

0.45

0.60

0.75

0.85

1.05

45 Standard

0.20

0.20

0.30

0.35

0.45

0.55

0.65

0.85

45 Long Radius*

0.15

0.15

0.20

0.22

0.30

0.37

0.43

0.57

Smooth bend type

*Data for these sizes fitting interpolated


Table 1: Fitting Equivalent Lengths (meters of a straight pipe)

Amendment Replaces pages 1016 1017 AIRAH HANDBOOK Millenium Edition

Fig 2: R22 suction risers minimum capacity for oil return

Notes for discharge and liquid lines


Note 1. For other Ts and Equivalent Lengths, Le:

Table Le Actual T Loss Desired


Line Capacity = Table Capacity

Table T Loss
Actual Le

Note 2. For other Capacity and Equivalent Lengths in a given pipe size:

Actual Le Actual Capacity


T = Table T

Table Le Table Capacity

1 .8

Note 3. Values based on 40C condensing temperature.


Amendment Replaces pages 1016 1017 AIRAH HANDBOOK Millenium Edition

0 .55

For capacities at other condensing temperatures, multiply table capacity by the following factors:
Condensing Temperature, C
20
30
40
50
Suction Lines
Hot Gas Lines

1.18

1.10

1.00

0.91

0.80

0.88

1.00

1.11

Source: ASHRAE
Wills, I; Simplified R22 Suction Line sizing, AIRAH journal, pg 30-31 (June 2001)

Amendment Replaces pages 1016 1017 AIRAH HANDBOOK Millenium Edition