NGR Design
NGR Design
Generator capacity 2.5 MVA Rated voltage =11 kv Rated current 131 amp Earth fault current limitation < 100 amp
Therefore.
100 = (11000/1.732)/R 100 = 6350/R R = 6350/100 =63.5 ohm Therefore Required value of Neutral grounding resistance to limit the ground fault to 100 amp = 63 ohm for 10 second