E5TroubleshootingGuide

1 ComponentsofOutdoorController(ASWH24TA4/S#R1DI) DriverModularforCompressor PFCModular FilterCircuit Fuse TerminalBoard MaincontrolPanel Componentsaboveallremarkedinthepicturebelow:

DriverModular ForCompressor

PFCModular

Main Control Panel

FilterCircuit

Fuse

TerminalBoard

Voltageoutput ForPFC Connected to compressor(notice thesequence)

Connectionlight forcontrolpanel

Connection pin tocontrolpanel

Input line for DC280

Inputfor DCbusbar

Fig1,DriverModularforCompressor Outputfor PowerlightD1 DCbusbar

Voltageinput forPFC Outputfor DC280 Powerlight ForPFC

InputforAC Fig2 PFCModular

COM end ofRelay

Connect wire of control panel

Fig3MainControlPanel

2.Troubleshootingguide (1)whenpoweredon,lightD1ondrivermodularforcompressoris off,andthereisnoticksoundofelectricswitch; Cutoffthepower,checktheconnectionofmodulars,makesurethe connectioncableisok.Thenpoweron,checkthecontrollerfollowthe flowprocessdiagrambelow. a)


Poweron DriverModularforCompressor

1.checkdirectvoltagebetweenDC280andN()is280Vornot; 2.powerlightD1isonoroff.

If the voltage and light is ok, it indicates that the drivermodularisok.

If the voltage is 280V but the light D1 is off,then thereissomethingwronginthedrivermodular.

b)

Poweron CheckthevoltagebetweenLandNonterminalboardis220240Vornot

NO YES
Checktheinputcircuit CheckthevoltagebetweenCOMendon relayandNisequaltoLandN

NO YES
Checkthefuse ReplacethePFC

(2)whenpoweredon,thelightD1ondrivermodularisonbutintermittent,youcan heartheticksoundofelectricswitch. cut off thepower Breaktheconnectioncableofcontrolpaneltodrivermodular Power on CheckthelightD1oncontrolpanelisonoroff Lightonconstantly lightonintermittently Cutoffthepower,breakvoltageinputlineforPFC Replacethecontrolpanel (connectedtodrivermodular) Poweron CheckthelightD1oncontrolpanelisonoroff lightonintermittently ReplaceDrivermodular poweron CheckthelightD1oncontrolpanelisonoroff lightonintermittently ReplacePFC