1 Customer Utility Supply 3-Breaker Maintenance Bypass Panel


Bypass Breaker CB2

Hz

UPS Cabinet

Static Bypass 3
83 BF THY. SW. (Optional) Key Interlock

SKR K

Jumper installed for single operation SYNC

83MC2

5 Primary AC Input 480V, 3Ph/4W, 60Hz

CB1

Hz V 52R F20 Filter RECT INV T91 F50

Hz V 83MC1 CB3 A

ST

UPS Bypass Input Breaker

F30

UPS Output Breaker

Output 480Y/227V 3Ph/4W, 60Hz, 100 kVA

DC CONV

Customer supplied wiring

7
V A Customer supplied wiring 72B Battery Cabinet with Main Breaker
UVR

8 + 480 VDC Nominal

10

10

NOTES
1) This drawing is for illustration purposes only and is subject to change without notice. TIC is not responsible for any errors or omissions.

Drawn by EKM Date 6/04/08 Approved by

TITLE

INTERNATIONAL CORPORATION Houston Texas, USA


THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL CORPORTION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED TO OTHERS UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.

One-Line Diagram 100 kVA G8000MM Series UPS 480V Single Input, 480Y/277V Output, with External 3-Breaker Bypass Panel
REV.

DRAWING NO.

T8MS3K10KK6XSN-E3-SI