Work:
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
TYPICAL BRANCH DUCT
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312 DUCTLESS AIR HANDLER FMC SECTIONS 303 -- 312
ZD
BP
Walk In Closet
8x4 = DEVICE NECK SIZE 4" = BRANCH DUCT SIZE 32 = AIRFLOW CFM
ADJUSTMENTS
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
HVAC NOTES
THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
BUILDING TOTALS
22x22,9",263 CFM
95
> 3 HRS
7800
6325
1475
1475
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Office
Lobby
22x22,9",263 CFM 22x22,9", 266 CFM 22x22,9", 266 CFM
OCCUPANTS 85 10
ADJUSTED AIR 15 20
BUILDING TOTALS
95
1475
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
EF-3
VTE
Restroom G Locker G
10x10 16x16, 9",-300 CFM 22x22,5",88 CFM 16x16,9",-300 CFM 10x14
Restroom B
10x14
Mech
10x12 8x4,4",51 CFM
Locker B
12x12,7",-125 CFM
Reading
Media
22x22,9",300 CFM
22x22,5",67 CFM
Electric
Office 102
22x22,8",168 CFM
Office 101
16x16,9",-300 CFM
8x4,4",36 CFM
16x16,9",-200 CFM
22x22,5",81 CFM 6x12 8x4,4",51 CFM TYPICAL (x6) 16x16 TRANSFER AIR GRILLE - WALL / DOOR MOUNT 300 MAX CFM 10x12 24x12
EF-1
VTE
Restroom
TRANE EQUIPMENT
AIR HANDLER MARK: UNIT MODEL NUMBER: UNIT DIMEN H/W/D: UNIT WEIGHT:
AHU-1,2,3,4
TWE065E 63X26X21 218 24X12 24X18 1800 / .40 1 368 1 / 60 208 / 240 7.2 / 9.6 50 / 60
AHU-5
ACWH1800 1.5 DUCTLESS DUCTLESS 600 / .40 .35 0 200/230/ 1 / 60 42X12X8 29 2.5
PIPE COVER - MAY MOUNT INTERIOR REFRIGERANT PIPING + CONTROL WIRING FMC 1101 - MAY ALSO ROUTE BELOW SLAB
Corridor 24x12 2
24x18
22x22,16",-860 CFM 14x16 22x22, 14", -460 24x18 24x12 22x22,14",-620 CFM
SUPPLY PLENUM SIZE : RETURN PLENUM SIZE : SUPPLY FAN CFM / SP : SUPPLY FAN H/P : OUTDOOR AIR CFM: UNIT PHASE / HERTZ: UNIT VOLTAGE: HEATER KW: HEATER BREAKER:
AHU-2
MECH ROOM ABOVE CEILING
8x4,4",29 CFM
WALL FLOOR
Corridor 1
22x22,6",97 CFM
AHU-3 Corridor 3
22x22,7",140 CFM
MECH ROOM ABOVE CEILING
AHU-1
MECH ROOM ABOVE CEILING
22x22,5",85 CFM
AHU-4
22x22,16",-889 CFM
CU-1,2,3,4
5 2TTR4060A 208/230/ 1 / 60 34 / 50 46.4X35.1X38.7 279 61,000 44,500 16,500 34,120 0.73 14 T8411R1002
CU-5
CCW18000 200/230/ 1 / 60 12.5 / 20 35X12X28 156 18,400 11,200 7,200 17,000 13
EQUIPMENT SLAB
Break
22x22,5",86 CFM
Office 120
24x12
24x18
Office 122
Pricipal Office
22x22,7",-103 CFM
UNIT MODEL NUMBER: UNIT VOLTAGE: UNIT MCA / BREAKER: UNIT DIMEN H/W/D: UNIT WEIGHT: TOTAL COOLING BTUH: SENS. COOLING BTUH: LAT. COOLING BTUH: TOTAL HEATING BTUH:
24x18 22x22,18",-686 TYPICAL (x4) 9" FRESH AIR DUCT VTE,FILTER,SET TO 368 CFM 22x22,9",238 CFM 22x22,9",238 CFM
22x22,6",93 CFM 24x12 12x16 22x22, 6",70 CFM 22x22,6",103 CFM 24x12 14x12 8x12 22x22,9", -174 CFM
16x12
SUPPLY AIR DUCT FMC 601 AUX. DRAIN PAN + FLOAT SWITCH FMC 301.2.3
10x12 22x22,9",199 CFM 22x22,9",199 CFM 22x22,9",199 CFM 14x12 22x22,8",171 CFM 22x22,8",171 CFM 22x22,9",171 CFM
TRANSFER AIR FROM BREAK - CORRIDOR HIGH WALL
14x12
EF-2
VTE
Server Corridor 4
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL.
* CEILING
CONDENSATE DRAIN FMC 307 ENCLOSED MECHANICAL ROOM IN ATTIC, R-19 INSULATION + SEALED GWB, PROVIDE ACCESS
EF-1
NUTONE 690 EXHAUST 50 0.25 120/1/60 0.5 9X11X8 3 12X11 10 1,2
EF-2
NUTONE QT-200 EXHAUST 200 .25 120/1/60 1.0 14X10X9 3.25X10 TO 7 15X11 14 1,3
EF-3
GREENHECK CSP-264 INLINE EXHAUST 1225 .5 120 / 1 / 60 7.8 24X14X14 19X8 23X13 59 1,2
DUCTLESS AIR HANDLER 600 CFM S/A 600 CFM R/A NO OCCUPANCY
22x22,8", -157 CFM 22x22,8", -157 CFM 22x22,7", 157 CFM 22x22,7", 157 CFM 22x22,8", 174 CFM
MODEL NUMBER: FAN TYPE: FAN CFM: TOTAL PRESSURE: FAN VOLTAGE: FAN AMPERAGE: FAN DIMEN LWH: DUCT OUTLET SIZE: DUCT INLET SIZE: FAN WEIGHT: NOTES:
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN DRAWING FOR EXACT CONFIGURATION.
22x22,9",199 CFM
22x22,8",171 CFM
22x22,9",238 CFM
22x22,9",238 CFM
AHU-5
WALL MOUNT
Class
Science
Computers
NOTE: AHU-5, CU-5 ARE OPTIONAL ONLY IF THIS ROOM IS USED FOR COMPUTER SERVERS FOR OFFICE - USE 7" S/A DUCT AND 22x22 GRILLE
Office 121
Office 123
Office 125
CU-1
ON SLAB
CU-2
ON SLAB
CU-5
ON SLAB
CU-3
ON SLAB
CU-4
ON SLAB
North
PROJECT NAME: American Youth Academy 6949 w PROJECT ADDRESS: 5903 E 130th Avenue PROJECT STATE, ZIP: Temple Terrace Florida CONDITIONED SQ. FT.: 6949 CLASSIFICATION : Commercial Add + Remodel
HVAC DRAWING 1 OF 1
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15
HVAC SYMBOLS
RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
22x22,10",300 CFM
Unit J1
22x22,10",284 CFM
Unit J2
22x22,10",300 CFM
FLOOR
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN DRAWING FOR EXACT CONFIGURATION.
AHU-10A
ON STAND
16"
16"
ZD BP
Toilet 10 EF-1
VTE
AHU-10B
ON STAND
RAIL PIPE COVER REFRIGERANT PIPING + CONTROL WIRING FMC 1101 CONDENSING UNIT FMC 303 FASTENER FMC 301.13
Toilet 9
8x4,4",47 CFM
10" O/A DUCT 18x18 + 400 CFM O/A 22x22,10",311 CFM 22x22,10",311 CFM
AHU-9
ON STAND
8x4 4" 32
Walk In Closet
16"
B
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
RAISED PLATFORM
CU-10A CU-10B
22x22,10",311 CFM 22x22,10",311 CFM 22x22,10",311 CFM
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
CU-9
Unit I
CU-6
CU-7 CU-8
Unit H
18x18 + 420 CFM O/A 10" O/A DUCT 18x18 +360 CFM O/A 22x22,10",326 CFM 18x18 + 360 CFM O/A 22x22,10",326 CFM 10" O/A DUCT
Unit G
Unit F
Unit E
Unit D
Unit C
22x22,10",312 CFM
Unit B
22x22,10",312 CFM
22x22,10",300 CFM
Unit A1
22x22,10",300 CFM
22x22,10",312 CFM
22x22,10",312 CFM
16"
18"
22x22,10",326 CFM
22x22,10",310 CFM
16" 16"
30x20 R/A -1240 CFM
Unit A2
AHU-2
ON STAND
AHU-1B
ON STAND
16"
22x22,10",310 CFM
B
AHU-6
22x22,10",326 CFM 22x22,10",326 CFM
AHU-5
ON STAND
AHU-4
ON STAND
AHU-3
ON STAND
AHU-8
ON STAND
AHU-7
ON STAND
ON STAND
AHU-1A
ON STAND
Toilet 3
8x4,4",42 CFM
8x4,4",53 CFM
EF-1
VTE
EF-1
VTE
Toilet 4
EF-1
VTE
EF-1
8x4,4",42 CFM
VTE
Toilet 8
8x4,4",48 CFM
Toilet 7
Toilet 6
Toilet 5
Toilet 2
Toilet 1
CU-5
CU-4
CU-3
CU-2
CU-1A CU-1B
RAISED PLATFORM
AHU-1A,1B,10A,10B
2TEC3F36A 46.5X24X23.5 125 12.02X19.22 18.07X19.5 1200 / .40 1/3 240 1 / 60 208 / 240 5.76 / 7.68 40 / 45
AHU-2,3,4,5,6,7
2TEC3F48A 59.5X26X23.5 151 12.02X21.22 18.07X21.5 1600 / .40 1/2 360 1 / 60 208 / 240 7.2 / 9.6 50 / 60
AHU-8
2TEC3F60A 59.5X26X23.5 155 12.02X21.22 18.07X21.5 2000 / .40 1 420 1 / 60 208 / 240 7.2 / 9.6 50 / 60
2TEC3F48A 59.5X26X23.5 151 12.02X21.22 18.07X21.5 1600 / .40 1/2 400 1 / 60 208 / 240 7.2 / 9.6 50 / 60
BUILDING TOTALS
3920 PROVIDED
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
EF-1
NUTONE QT-80 EXHAUST 80 .25 120/1/60 .7 9X9X6 4 10X10 12 1,2
CU-1A,1B,10A,10B
3 2TTR3036A 208/230/ 1 / 60 18 / 30 38X30.1X33 194 34,200 25,400 8,800 25,590 0.74 13 T8411R1002
CU-2,3,4,5,6,7
4 2TTR3048A 208/230/ 1 / 60 25 / 40 46.4X35.1X38.7 273 47,000 33,800 13,200 34,120 0.72 13 T8411R1002
CU-8
5 2TTR3060A 208/230/ 1 / 60 32 / 50 46.4X35.1X38.7 269 58,000 40,000 18,000 34,120 0.69 13.5 T8411R1002
CU-9
4 2TTR3048A 208/230/ 1 / 60 25 / 40 46.4X35.1X38.7 273 47,000 33,800 13,200 34,120 0.72 13 T8411R1002
BUILDING TOTALS
97
> 3 HRS
18000
14080
3920
3920
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL. CYCLE EQUIPMENT OFF DURING UNOCCUPIED HOURS.
North
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
PROJECT NAME: Rose Lake Plaza Phase 2 PROJECT ADDRESS: 14400 N Florida Ave PROJECT STATE, ZIP: Tampa Florida CONDITIONED SQ. FT.: 13352 CLASSIFICATION : New Commercial
Designed By: Neil Fimbel HVAC Designs 813-885-2258 FL BERS R#884 FL BERS C#8508
HVAC DRAWING 1 OF 1
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/A FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
ZD BP
8x4 4" 32
Walk In Closet
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
M Bed
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
8x4,4",43 CFM
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
12x8,116 CFM
A
AHU-1
WYE ABOVE CEILING IN SEALED MECH ROOM R-19 ISUL 12" BYPASS
Foyer
18x18 R/A @ CHASE -500 CFM 12"
14" Powder
4" DRYER VTE
ZD ZD
14"
ACCESS TO ATTIC
BP
12x12,7",-89 CFM
8x4,4",31 CFM
E
ON SLAB
CU-1
DUCTS DOWN
14"
8x4,4",24 CFM
Laundry
8x4,4",35 CFM
Bath 2
12x12,7",-99 CFM 12x12,7",-91 CFM
10x6,6",99 CFM
FIRST FLOOR
10x6,6",91 CFM
AHU-1
2TEC3F48A 59.5X26X23.5 151 12.02X21.22 18.07X21.5 1600 / .40 1/2 0 1 / 60 208 / 240 7.2 / 9.6 50 / 60
PIPE COVER - MAY MOUNT INTERIOR REFRIGERANT PIPING + CONTROL WIRING FMC 1101 - MAY ALSO ROUTE BELOW SLAB
1/2 THREADED ROD SUSPEND FROM TOP CHORD AIR HANDLER FMC 303
SECOND FLOOR
Bed Bed 23
WALL FLOOR
* CEILING
AUX. DRAIN PAN + FLOAT SWITCH FMC 301.2.3 CONDENSATE DRAIN FMC 307
CU-1
4 2TWR3048A 208/230/ 1 / 60 25 / 40 46.4X35.1X38.7 279 46,000 33,200 12,800 43,500 0.72 13 / 8.4 PROGRAM
EQUIPMENT SLAB
REDUCER - BOX
W H
*
13 17 21 13 17 21 13 17 21 13 17 21
W2
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. ZONING SHOWN PER MANUAL J
A B C D E F
18 18 18 18 18 18
N/A
N/A
N/A
EF-1
NUTONE 690 EXHAUST 50 0.25 120/1/60 0.5 9X11X8 3 12X11 10 1,2
* * *
North
PROJECT NAME: HDS Model Residence 1964 s PROJECT ADDRESS: PROJECT STATE, ZIP: CONDITIONED SQ. FT.: 1991 CLASSIFICATION : New Residence
HVAC DRAWING 1 OF 1
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
ZD BP
Cooler
8x4 4" 32
Walk In Closet
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
Kitchen
HVAC NOTES
22x22,10",320 CFM
THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER.
22x22,10",320 CFM
12x12 24x12
12x12
RTU-1
ON ROOF 22x22,10",320 CFM 22x22,10",320 CFM
KITCHEN HOOD BY OTHERS 380 CFM MUA BY A/C EQUIPMENT CONDENSATE DRAIN TO GUTTER / GRASS TYPICAL OF 2 22x22,10",320 CFM 22x22,10",320 CFM
BUILDING TOTALS
14
VARIES
3600
3220
380
380
RTU-2
EXISTING ON ROOF
RTU-1
TRANE THC063A3 5 DOWNFLOW 37X45X70 682 17X15 23X14 2000 / .4 1 160 3/60 208/230 28.8 40 9/12 37.5/42.4 45/45 62,400 47,300 15,100 40,944 0.76 13 T8411R1002
RTU-2
EXISTING THC043A3 4 DOWNFLOW 37X45X70 669 17X15 23X14 1600 / .4 1 220 3/60 208/230 22.6 35 9/12 37.5/42.4 40/45 49,800 39,400 10,400 40,944 0.79 13 T8411R1002 2" U CHANNEL X 1/4" THK SPAN 3 JOISTS ROOF JOIST 3/8 BOLT @ 18" O.C. CURB
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
CURB CONNECTION
DUCT CONNECTION
ROOFTOP EQUIPMENT MASTIC SEAL 1/2" SCREWS @ 8" O.C.
EQUIPMENT CONNECTION
20x12
SUPPLY PLENUM SIZE : RETURN PLENUM SIZE : SUPPLY FAN CFM / SP : SUPPLY FAN H/P : OUTDOOR AIR CFM: UNIT PHASE / HERTZ:
ROOFTOP EQUIPMENT
Restroom
DUCT
CURB
EF-1
VTE 8x4,4",18 CFM 22x22, 16" -1380 CFM 22x22, 10",316 CFM
UNIT VOLTAGE: UNIT MCA: UNIT MAX BREAKER: HEATER KW: HEATER MCA: HEATER BREAKER: TOTAL COOLING BTUH: SENS. COOLING BTUH: LAT. COOLING BTUH: TOTAL HEATING BTUH: SENS. HEAT %
BUILDING TOTALS
14
380
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE
THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
CURB
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604 MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL.
EF-1
NUTONE 690 EXHAUST 50 0.25 120/1/60 0.5 9X11X8 3 12X11 10 1,2
MANUFACTURER: MODEL NUMBER: FAN TYPE: FAN CFM: TOTAL PRESSURE: FAN VOLTAGE: FAN AMPERAGE: FAN DIMEN LWH: DUCT OUTLET SIZE: DUCT INLET SIZE: FAN WEIGHT: NOTES:
Order - Cashier
22x22, 10",316 CFM 22x22, 10",316 CFM
North
PROJECT NAME: PROJECT ADDRESS: PROJECT STATE, ZIP: CONDITIONED SQ. FT.: CLASSIFICATION :
Marcos Pizza Renov Boynton Beach 1320 e Boynton Beach Florida, 33461 1320 Restaurant Renovation
HVAC DRAWING 1 OF 1
HVAC SYMBOLS
RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
ZD
BP
8x4 4" 32
Walk In Closet
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
BUILDING TOTALS
68
VARIES
7600
6970
630
630
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM.
BUILDING TOTALS
68
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Exam
22x22,6",120 CFM
Exam Reception
22x22,9",253
Exam
22x22,10",307 CFM 22x22,7",-89 22x22,14",-615
6x10
Waiting
22x22,5",82 CFM
22x22,7",-105
Corridor
Exam
22x22,7",-101
22x22,10",307 CFM
12x10
Exam
Exam
10x12
8x10
22x22,6",105 CFM
AHU-3
RELOCATED TO MEZZANINE ABOVE
22x22,7",124 CFM
12x16
22x22,9",257
Exam
22x22,6",101 CFM
20x12
16x12
CU-3
ON SLAB
U Restroom
22x22,7"-100 8x4,4",24 CFM
Office
22x22,7",130 CFM
Exam
22x22,14",-615 22x22,6",89 CFM 22x22,7",-89 22x22,10",307 CFM
10x12
CU-4
ON SLAB
12x8
14x12
22x22,8",-124
Restroom
8x4,4",21 CFM
22x22,8",-127
24x12
14x16
22x22,12",-427
Office
22x22,7",-118
Restroom
8x4,4",24 CFM
Storage
8x4,4",12 CFM
22x22,8",-130
MAY CONFIGURE EXISTING AHU VERTICAL OR HORIZONTAL
22x22,7",129 CFM
CU-5
ON SLAB
AIR HANDLER MARK: UNIT MODEL NUMBER: UNIT DIMEN H/W/D: UNIT WEIGHT: SUPPLY PLENUM SIZE : RETURN PLENUM SIZE :
AHU-1,2,5
EXISTING 59.5X26X23.5 155 12.02X21.22 18.07X21.5 2000 / .70 1 130 / 130 / 130
AHU-3,4
EXISTING 44.5X24X23.5 111 12.02X19.22 19.5X18.07 800 / .60 1/4 120 / 120 * * * *
1/2 THREADED ROD SUSPEND FROM TOP CHORD AIR HANDLER FMC 303
22x22,6",118 CFM
22x22,6",108 CFM
14x14
22x22,8",-119
AHU-4
EXISTING ON MEZZANINE ABOVE
AHU-5
EXISTING ON MEZZANINE ABOVE
18x16
P Restroom
8x4,4",10 CFM
Corridor
AIR HANDLER FMC 303 REFRIGERANT PIPING + CONTROL WIRING FMC 1101 CONDENSATE DRAIN FMC 307
Exam
22x22,5",64 CFM
Exam
22x22,5",64 CFM
Break
22x22,10",-243
E Restroom
8x4,4",23 CFM
SUPPLY FAN CFM / SP : SUPPLY FAN H/P : OUTDOOR AIR CFM: UNIT PHASE / HERTZ: UNIT VOLTAGE: HEATER KW: HEATER BREAKER: CONDENSER MARK: NOMINAL A/C TONS :
* CEILING
AUX. DRAIN PAN + FLOAT SWITCH FMC 301.2.3 CONDENSATE DRAIN FMC 307
Lab
8x4,4",39 CFM
AHU-2
RELOCATED ABOVE CEILING
*
* * *
* ACCESS PANEL FMC 306.3 * = OPTIONAL ITEM, SEE HVAC FLOOR PLAN DRAWING FOR EXACT CONFIGURATION.
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN DRAWING FOR EXACT CONFIGURATION.
22x22,9",243 CFM
CU-1,2,5
5 EXISTING * * 46.4X35.1X38.7 269 58,000 40,000 18,000 34,120 0.69 13
CU-3,4
2 EXISTING * * 37.2X26.7X30 175 22,800 16,600 6,200 17,060 0.73 13
10x10
EF-1
VTE
22x22,6",-64
22x22,6",-64
22"
24x12
(TYPICAL x7)
22x22,7",-94
22x22,10",-335
THIS AREA CONTAINS A FOUNTAIN - CALCULATE AND PROVIDE STAND ALONE DEHUMIDIFICATION MAY CONFIGURE EXISTING AHU VERTICAL OR HORIZONTAL VERIFY EXISTING AHU TYPE
UNIT MODEL NUMBER: UNIT VOLTAGE: UNIT MCA / BREAKER: UNIT DIMEN H/W/D: UNIT WEIGHT: TOTAL COOLING BTUH: SENS. COOLING BTUH:
ON SLAB
Work Stations
14x12
CU-1
22x22,10",332 CFM
18x12
Restroom
Waiting
22x22,10",335 CFM
WALL FLOOR
CU-2
ON SLAB
Restroom
AHU-1
ON STAND
8x4,4",38 CFM
22x22,10",332 CFM
22x22,14",-646 22x22,14",-646
Reception
EQUIPMENT SLAB
24x12 20x14
20x12
12x14
22x22,10", -304 22x22,10",347 CFM 22x22,10",347 CFM
THERMOSTAT MODEL: T8411R1002 T8411R1002 NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE DATA FOR EXACT INFORMATION. CLEAN AND CHECK EQUIPMENT TO INSURE PROPER OPERATION. SIZE AND INSTALL STAND ALONE DEHUMIDIFICATION AT THE INDOOR FOUNTAIN AREA.
12x12
22x22,10",-261
22x22,10",347 CFM
EF-1
NUTONE QT-80 EXHAUST 90 .2 120/1/60 .7 9X9X6 4 10X10 12 1,2
FAN TYPE: FAN CFM: TOTAL PRESSURE: FAN VOLTAGE: FAN AMPERAGE: FAN DIMEN LWH: DUCT OUTLET SIZE: DUCT INLET SIZE: FAN WEIGHT: NOTES: 1 = VENT TO EXTERIOR 2 = INTERLOCK WITH LIGHTS
22x22,9",258 CFM
22x22,7",146 CFM
22x22,9",261 CFM
Office
Exam
Exam
Reception
22x22,10",304 CFM
x
Designed By: Neil Fimbel HVAC Designs 813-885-2258 FL BERS R#884 FL BERS C#959
North
PROJECT NAME: 14378 Spring Hill Dr Office Renovation PROJECT ADDRESS: 14378 Spring Hill Drive PROJECT STATE, ZIP: Spring Hill Florida (Hernando) CONDITIONED SQ. FT.: 7563 Revised 9/28/08 CLASSIFICATION : Commercial Office Renovation
HVAC DRAWING 1 OF 1
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
TYPICAL BRANCH DUCT TYPICAL AIR DEVICE
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
ZD
FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/ A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15
BP
BUILDING TOTALS
597
OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA. CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1
Walk In Closet
8x4 4" 32
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
CU-1
ON ROOF ABOVE
22x22,9",250 CFM 22x22,9",250 CFM
AHU-1
ABOVE CEILING
20x18
20x12
12x12,8",-105 CFM
FIRST FLOOR
22x22,16",-895 CFM
Lobby
12x12 OAL,8" RELIEF AIR DUCT SET BAROMETRIC RELIEF AIR DAMPER TO RELIEVE 105 CFM
22x22,9",250 CFM
CURB CONNECTION
CURB 3/8 BOLT @ 18" O.C. ROOF JOIST CONNECT TO TRUSS MEMBER ROOFTOP EQUIPMENT FMC 303
EQUIPMENT CONNECTION
ROOFTOP EQUIPMENT
1/2 THREADED ROD SUSPEND FROM TOP CHORD AIR HANDLER FMC 303
CURB
* CEILING
AUX. DRAIN PAN + FLOAT SWITCH FMC 301.2.3 CONDENSATE DRAIN FMC 307
2TEC3F30A 46.5X24X23.5 125 12.02X19.22 18.07X19.5 1000 / .40 1/3 105 1 / 60 208 / 240 3.6 / 4.8 25 / 30
UNIT DIMEN H/W/D: UNIT WEIGHT: SUPPLY PLENUM SIZE : RETURN PLENUM SIZE :
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
SUPPLY FAN CFM / SP : SUPPLY FAN H/P : OUTDOOR AIR CFM: UNIT PHASE / HERTZ: UNIT VOLTAGE: HEATER KW: HEATER BREAKER: CONDENSER MARK: NOMINAL A/C TONS :
CU-1
2.5 2TTR3030A 208/230/ 1 / 60 13 / 20 38X30.1X33 198 27,600 20,400 7,200 17,060 0.74 13 T8411R1002
UNIT MODEL NUMBER: UNIT VOLTAGE: UNIT MCA / BREAKER: UNIT DIMEN H/W/D: UNIT WEIGHT: TOTAL COOLING BTUH: SENS. COOLING BTUH: LAT. COOLING BTUH: TOTAL HEATING BTUH: SENSIBLE HEAT % SEER:
14
0.5
1000
895
105
105
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
THERMOSTAT MODEL:
105
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL.
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
North
PROJECT NAME: PROJECT ADDRESS: PROJECT STATE, ZIP: CONDITIONED SQ. FT.: CLASSIFICATION : Prieto Office Building 1st Floor Corner of Lakewood & Oakfield Hillsborough County Florida 721 of 22,597 New Office Building
x
Designed By: Neil Fimbel HVAC Designs 813-885-2258 FLORIDA BERS R#884 C#959
HVAC DRAWING 1 OF 3
1/2 THREADED ROD SUSPEND FROM TOP CHORD AIR HANDLER FMC 303 SUPPLY AIR DUCT FMC 601
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15 FLOOR GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/ A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
EF-1
NUTONE QT-150 EXHAUST 140 .25 120/1/60 1.0 14X10X9 3.25X10 TO 7 15X11 14 1,2
EF-2
NUTONE QT-110 EXHAUST 92.85 .25 120/1/60 .7 9X9X6 4 10X10 12 1,2
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
TYPICAL BRANCH DUCT TYPICAL AIR DEVICE
89
1490
* CEILING
AUX. DRAIN PAN + FLOAT SWITCH FMC 301.2.3 CONDENSATE DRAIN FMC 307
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
FAN CFM: TOTAL PRESSURE: FAN VOLTAGE: FAN AMPERAGE: FAN DIMEN LWH:
* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN DRAWING FOR EXACT CONFIGURATION.
Restroom
22x22,9",-195 CFM
10x6,5",63 CFM
10' SEPERATION
Conference
Lunch
22x22,12",-278 CFM 22x22,10",307 CFM
Dr Off 1
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",164 CFM
22x22,8",164 CFM
EF-2
VTE
ZD
20x12
18x20
22x22,9",-184 CFM
CU-4
ON ROOF CURB ABOVE 3rd FLOOR
12x12
12x8
12x8
AHU-4
Storage
22x22,6",90 CFM
ABOVE CEILING
EF-2
VTE
Restroom
Restroom
CU-2
ON ROOF CURB ABOVE 3rd FLOOR
Restroom
12x8
Admin
NOTES:
106 CFM T/A
BP
1 = VENT TO EXTERIOR
CU-1
8x4,4",19 CFM
CU-3
8x4,4",14 CFM
ON ROOF CURB ABOVE 3rd FLOOR
EF-1
VTE
12x12
Restroom
22x22,9",-183 CFM 22x22,6",-75 CFM
8x4,4",13 CFM
8x4,4",11 CFM
8x4,4",14 CFM
Billing
22x22,7",-90 CFM
18x20
20x12
18x20
20x12
22x22,16",-1040 CFM
18x20
20x12
CURB CONNECTION
CURB 3/8 BOLT @ 18" O.C. ROOF JOIST CONNECT TO TRUSS MEMBER
EQUIPMENT CONNECTION
22x22,16",-860 CFM
12x12
14x12
AHU-5
ABOVE CEILING
12x12
22x22,14",-868 CFM
8x4,4",14 CFM
22x22,6",103 CFM
Corridor
12x12 T/A HIGH WALL
8x12
Restroom
CU-6
ON ROOF CURB ABOVE 3rd FLOOR
AHU-3
Dr Off 3
22x22,5",75 CFM 22x22,6",-75 CFM
ABOVE CEILING
AHU-2
ABOVE CEILING
AHU-1
ABOVE CEILING
ROOFTOP EQUIPMENT
EF-2
VTE
CURB
18x20
Exam 5
22x22,5",65 CFM
22x22,6",-65 CFM
Storage
22x22,4",28 CFM
18x20
Walk In Closet
8x4 4" 32
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
8x12
10' SEPERATION
22x22,9",252 CFM
Exam 4
22x22,5",63 CFM
8x12
10x6,6",100 CFM
8x12
8x4,4",19 CFM
CU-5
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",198 CFM
22x22,8",198 CFM
8x12
Server
F Office
CURB
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
22x22,10",-252 CFM
21x12
18x21
AHU-6
ABOVE CEILING
22x22,5",75 CFM
Dr Off 4
22x22,14",-860 CFM
Exam 3
22x22,6",-63 CFM
AHU-7
ABOVE CEILING
Files
22x22,4",28 CFM 22x22,5",81 CFM
Phone
22x22,8",164 CFM
22x22,8",164 CFM
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",164 CFM
22x22,8",164 CFM
EF-2
VTE
Corridor
10x6,6",92 CFM
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
20x12
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
Unit 2 C
22x22,8",165 CFM
PIPING UP FROM LOBBY BELOW
Unit 2 B
Unit 2 A
22x22,6",-63 CFM
Restroom Exam 1
18x12
18x14
22x22,10",-223 CFM
SR-82,8",165 CFM
10x12
CU-7
ON ROOF CURB ABOVE 3rd FLOOR
22x22,5",65 CFM
EF-2
8x4,4",54 CFM
VTE
Exam 2
22x22,6",91 CFM 22x22,9",223 CFM
22x22,5",63 CFM
Restroom
22x22,8",165 CFM 22x22,8",165 CFM
22x22,10",-300 CFM
16x12
12x12,6",-66 CFM
12x14
Lab
22x22,8",165 CFM
8x4,4",51 CFM
Recep / Wait
16x10
10x6,5",66 CFM
22x22,9",249 CFM
Restroom P Infusion
EF-2
VTE
Pharmacy Infusion
Cold
22x22,9",213 CFM
22x22,14",-640 CFM
SECOND FLOOR
8x4,4",43 CFM
EF-1
VTE
EF-2
VTE
Restroom
8x4,4",13 CFM
Restroom
18x20
AHU-8
ABOVE CEILING
22x22,8",198 CFM
127 CFM T/A
20x12
8x12
22x22,8",198 CFM
CU-8
22x22,8",198 CFM
ON ROOF CURB ABOVE 3rd FLOOR
22x22,8",198 CFM
Unit 2 F
18x20
Restroom
8x4,4",12 CFM
AHU-1,3,6
2TEC3F30A 46.5X24X23.5 125 12.02X19.22 18.07X19.5 1000 / .40 1/3 120/140/140 1 / 60 208 / 240 3.6 / 4.8 25 / 30
AHU-2,4,5,8,10
2TEC3F36A 46.5X24X23.5 125 12.02X19.22 18.07X19.5 1200 / .40 1/3 160/120/140/140/120 1 / 60 208 / 240 3.6 / 4.8 25 / 30
AHU-7
2TEC3F60A 59.5X26X23.5 155 12.02X21.22 18.07X21.5 2000 / .40 1 250 1 / 60 208 / 240 7.2 / 9.6 50 / 60
AHU-9
2TEC3F42A 53.25X26X23.5 150 12.02X21.22 18.07X21.5 1400 / .40 1/2 160 1 / 60 208 / 240 3.6 / 4.8 25 / 30
AHU-9
ABOVE CEILING
22x22,9",231 CFM
148 CFM T/A
20x12
16x12
22x22,9",231 CFM
CU-9
22x22,9",231 CFM
ON ROOF CURB ABOVE 3rd FLOOR
CU-1,3,6
2.5 2TTR3030A 208/230/ 1 / 60 13 / 20 38X30.1X33 198 27,600 20,400 7,200 17,060 0.74 13 T8411R1002
CU-2,4,5,8,10
3 2TTR3036A 208/230/ 1 / 60 18 / 30 38X30.1X33 194 34,200 25,400 8,800 17,060 0.74 13 T8411R1002
CU-7
5 2TTR3060A 208/230/ 1 / 60 32 / 50 46.4X35.1X38.7 269 58,000 40,000 18,000 34,120 0.69 13.5 T8411R1002
CU-9
3.5 2TTR3042A 208/230/ 1 / 60 21 / 35 38.4X35.1X38.7 250 41,000 29,800 11,200 17,060 0.73 13.5 T8411R1002
Unit 2 G
AHU-10
ABOVE CEILING
18x20
Restroom
22x22,8",198 CFM
20x12
22x22,8",198 CFM
12x8
22x22,8",198 CFM
12x12 8x12
22x22,8",198 CFM
22x22,16",-1080 CFM
CU-10
22x22,8",198 CFM
ON ROOF CURB ABOVE 3rd FLOOR
22x22,8",198 CFM
Unit 2 H
9 9 X ZONE 10 10
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL.
North
x
PROJECT NAME: PROJECT ADDRESS: PROJECT STATE, ZIP: CONDITIONED SQ. FT.: CLASSIFICATION : Prieto Office Building 2nd Floor Corner of Lakewood & Oakfield Hillsborough County Florida 10,938 of 22,597 New Office Building
Designed By: Neil Fimbel HVAC Designs 813-885-2258 FLORIDA BERS R#884 C#959
89
VARIES
12400
10910
1490
1490
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
HVAC DRAWING 2 OF 3
HVAC SYMBOLS
CEILING REGISTER 1 WAY THROW FMC 603.15 CEILING REGISTER 2 WAY THROW FMC 603.15 CEILING REGISTER 3 WAY THROW FMC 603.15 CEILING REGISTER 4 WAY THROW FMC 603.15 CEILING REGISTER CORNER THROW FMC 603.15 RECTANGULAR DUCTWORK FMC SECTION 603 FLEXIBLE DUCTWORK FMC SECTION 603 AIR DISTRIBUTION BOXES FMC SECTION 603 RETURN AIR PLENUM TRUNK FMC SECTION 602 SUPPLY AIR PLENUM TRUNK FMC SECTION 602 AIR VOLUME CONTROL DAMPER FMC 603.15 DUCT MOUNTED FIRE DAMPER FMC SECTION 607 DRYER VENT ROOF / WALL CAP FMC 504 RANGE VENT ROOF / WALL CAP FMC 505 - 506 CONTROL / REFRIGERANT PIPING FMC 1101 CONDENSATE DRAIN TO GRASS FMC SECTION 307 CONDENSATE TO DRYWELL FMC SECTION 307
T H
S D
THERMOSTAT @ 60" ABOVE FLOOR FEC 13-613 WALL MOUNTED HUMIDISTAT @ 60" ABOVE FLOOR DUCT MOUNTED SMOKE DETECTOR FMC SECTION 606 EQUIPMENT ACCESS PANEL FMC SECTION 306 EXHAUST FAN EF-1 or as NOTED FMC SECTION 403 ZONE CONTROL AIR DAMPER FMC 303 -- 312 BYPASS AIR DAMPER FMC 303 -- 312 1" UNDERCUT DOOR 30 CFM T/A
TYPICAL BRANCH DUCT TYPICAL AIR DEVICE
HORIZONTAL AIR HANDLER MOUNT FROM STRUCTURE FMC SECTIONS 303 --- 312
TYPICAL 12x12 LOUVER + BAROMETRIC RELIEF AIR DAMPER + 12x12 RELIEF AIR GRILLE -- FOR INTERIOR AIR PRESSURE RELIEF / TYPICAL OF 4 ZONES
Unit 3 Dwest
22x22,9",267 CFM 22x22,9",267 CFM 22x22,9",267 CFM
Unit 3 Deast
22x22,9",267 CFM 22x22,8",197 CFM 22x22,8",197 CFM 22x22,8",198 CFM 22x22,8",198 CFM 22x22,8",198 CFM 22x22,8",198 CFM
WALL REGISTER 2 WAY THROW FMC 603.15 FLOOR REGISTER 2 WAY THROW FMC 603.15
ZD
BP
22x22,16",-1060 CFM
12x12
22x22,18",-1400 CFM
12x14
12x12
12x12
Restroom
22x22,16",-1040 CFM
22x22,16",-1080 CFM
8x4,4",14 CFM
Restroom
18x16
8x4,4",15 CFM 8x4,4",12 CFM
EF-1
VTE
RTU-5
22x14
ON ROOF
RTU-4
ON ROOF
RTU-3
22x14
ON ROOF
RTU-2
22x14
ON ROOF
Restroom
CEILING GRILLE FILTER RETURN AIR FMC 603.15 WALL GRILLE FILTER RETURN AIR FMC 603.15 CEILING GRILLE DUCTED T/ A FMC 603.15 WALL GRILLE DIRECT T/ A FMC 603.15
RTU-1
22x14
ON ROOF
22x14
18x16
Walk In Closet
8x4 4" 32
12x14
8x14
22x22,9",267 CFM
22x22,9",267 CFM
22x22,8",197 CFM
12x12
22x22,8",197 CFM
22x22,8",198 CFM
12x12
22x22,198 CFM
18x16
18x16
18x16
Bedroom
TYPICAL ROOM
SF = SUPPLY FAN T/A = TRANSFER AIR VTE = VENT TO EXTERIOR ZD = ZONE DAMPER
22x22,9",267 CFM
22x22,9",267 CFM
TYPICAL CURB MOUNTED CONDENSING UNIT ON ROOF ABOVE SPLIT SYSTEMS SERVE FIRST AND SECOND FLOORS
12x14
AFF = ABOVE FINISH FLOOR AHU = AIR HANDLING UNIT BP = BYPASS DAMPER BD = BAROMETRIC DAMPER
CFM = CUBIC FEET / MINUTE CU = CONDENSING UNIT DH = DE-HUMIDIFIER E/A = EXHAUST AIR
EF = EXHAUST FAN FPM = FEET PER MINUTE MUA = MAKE UP AIR O/A = OUTSIDE AIR
PKG = PACKAGE UNIT R/A = RETURN AIR RTU = ROOFTOP UNIT S/A = SUPPLY AIR
22x22,9",267 CFM
16x14 22x14
22x22,8",197 CFM
22x22,198 CFM
HVAC NOTES
THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW.
Unit 3 C
Unit 3 B
Unit 3 A
22x22,9",267 CFM
18x16
12x14
22x22,18",-1400 CFM
RTU-6
ON ROOF
22x22,9",267 CFM
22x22,9",267 CFM
ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR.
22x22,9",267 CFM
ROOM NAME Unit 3 A Restroom X ROOM NAME Unit 3 B Restroom X ROOM NAME Unit 3 C Restroom X ROOM NAME Unit 3 Deast X ROOM NAME Unit 3 Dwest X ROOM NAME Unit 3 Enorth X ROOM NAME Unit 3 Esouth X ROOM NAME Unit 3 F Restroom X ROOM NAME Unit 3 G Restroom X ROOM NAME Unit 3 H Restroom
OCCUPANTS 6 0 X OCCUPANTS 8 0 X OCCUPANTS 7 0 X OCCUPANTS 10 X OCCUPANTS 10 X OCCUPANTS 10 X OCCUPANTS 10 X OCCUPANTS 7 0 X OCCUPANTS 8 0 X OCCUPANTS 6 0
DURATION > 3 HRS N/A X DURATION > 3 HRS N/A X DURATION > 3 HRS N/A X DURATION > 3 HRS X DURATION > 3 HRS X DURATION > 3 HRS X DURATION > 3 HRS X DURATION > 3 HRS N/A X DURATION > 3 HRS N/A X DURATION > 3 HRS N/A
SUPPLY AIR CFM 1186 14 X SUPPLY AIR CFM 1188 12 X SUPPLY AIR CFM 1185 15 X SUPPLY AIR CFM 1600 X SUPPLY AIR CFM 1600 X SUPPLY AIR CFM 1600 X SUPPLY AIR CFM 1600 X SUPPLY AIR CFM 1187 13 X SUPPLY AIR CFM 1587 13 X SUPPLY AIR CFM 1187 13
RETURN AIR CFM 1080 0 X RETURN AIR CFM 1040 0 X RETURN AIR CFM 1060 0 X RETURN AIR CFM 1400 X RETURN AIR CFM 1400 X RETURN AIR CFM 1400 X RETURN AIR CFM 1400 X RETURN AIR CFM 1060 0 X RETURN AIR CFM 1440 0 X RETURN AIR CFM 1080 0
EXHAUST AIR CFM 0 120 X EXHAUST AIR CFM 0 160 X EXHAUST AIR CFM 0 140 X RELIEF AIR CFM 200 X RELIEF AIR CFM 200 X RELIEF AIR CFM 200 X RELIEF AIR CFM 200 X EXHAUST AIR CFM 0 140 X EXHAUST AIR CFM 0 160 X EXHAUST AIR CFM 0 120
FRESH AIR CFM 120 0 X FRESH AIR CFM 160 0 X FRESH AIR CFM 140 0 X FRESH AIR CFM 200 X FRESH AIR CFM 200 X FRESH AIR CFM 200 X FRESH AIR CFM 200 X FRESH AIR CFM 140 0 X FRESH AIR CFM 160 0 X FRESH AIR CFM 120 0
12x14
18x16
12x14
RTU-7
ON ROOF
22x22,9",267 CFM
22x22,9",267 CFM
THIRD FLOOR
22x22,9",267 CFM
Restroom
22x22,198 CFM 22x22,8",198 CFM
127 CFM T/A 8x4,4",13 CFM
22x22,8",198 CFM
5 X ZONE 6 X ZONE
12x12
18x16
12x12
Unit 3 F
22x22,16",-1060 CFM
1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS. THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. 10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER. HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD.
RTU-8
ON ROOF
22x14
22x14
22x22,8",198 CFM
22x22,8",198 CFM
22x22,8",198 CFM
Restroom
22x22,9",265 CFM
147 CFM T/A 8x4,4",13 CFM
CURB CONNECTION
CURB
DUCT CONNECTION
ROOFTOP EQUIPMENT DUCT SEAL FMC 601 1/2" SCREWS @ 8" O.C.
EQUIPMENT CONNECTION
22x22,9",265 CFM
22x22,9",265 CFM
DUCT
RTU-1,2,3,8,10
TRANE THC033A3 3 DOWNFLOW 37X45X70 627 17X15 23X14 1200 / .4 1 120/160/140/140/120 3/60 208/230 19.9 30 4.5/6 21.9/24.3 25/25 38,000 28,800 9,200 20,472 0.76 13 T8411R1002
RTU-4,5,6,7,9
TRANE THC043A3 4 DOWNFLOW 37X45X70 669 17X15 23X14 1600 / .4 1 200/200/200/200/160 3/60 208/230 22.6 35 9/12 37.5/42.4 40/45 49,800 39,400 10,400 40,944 0.79 13 T8411R1002
EF-1
NUTONE QT-150 EXHAUST 140 .25 120/1/60 1.0 14X10X9 3.25X10 TO 7 15X11 14 1,2
22x14
82
> 3 HRS
14000
12360
1640
1640
12x14
18x16
12x14
Unit 3 G
22x22,18",-1440 CFM
RTU-9
ON ROOF
22x22,9",265 CFM
22x22,9",265 CFM
22x22,9",265 CFM
CURB
NOTE: TIE DOWN METHOD MAY VARY A/C CONTRACTOR MAY USE FLAT PLATE, ANGLE PLATE, OR STRAP FOR TIE DOWN BOLT AND SCREW SIZES MAY VARY - TIE DOWN FOR A MAXIMUM OF 140 MPH WIND
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Restroom
22x22,8",198 CFM
107 CFM T/A 8x4,4",13 CFM
22x22,8",198 CFM
22x22,8",198 CFM
MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD MECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604 MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOAD
82
1640
THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )
Unit 3 H
12x12 18x16 12x12
22x22,16",-1080CFM
RTU-10
ON ROOF
22x22,8",198 CFM
22x22,8",198 CFM
THERMOSTAT MODEL:
22x22,8",198 CFM
NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE. SUBMIT PERFORMANCE DATA FOR APPROVAL.
North
PROJECT NAME: PROJECT ADDRESS: PROJECT STATE, ZIP: CONDITIONED SQ. FT.: CLASSIFICATION : Prieto Office Building 2nd Floor Corner of Lakewood & Oakfield Hillsborough County Florida 10,938 of 22,597 New Office Building
x
Designed By: Neil Fimbel HVAC Designs 813-885-2258 FLORIDA BERS R#884 C#959
HVAC DRAWING 3 OF 3