Thermostatic Control
ENGINEERING ADVANTAGE
Self-sealing measuring points For simple, accurate balancing. Stainless steel Guarantees a longer lifetime.
Technical description
Application: Heating and cooling systems Tapwater systems Function: Measuring Dimensions: DN 20-900 Pressure class: PN 16 (DN 20-900) PN 25 (DN 65-300) PN 40 (DN 65-450) Temperature: Max. working temperature: 120C Min. working temperature: -20C Material: Fixed orifice: Stainless steel X3CrNiMo17-13-3 (No. 1.4436 according to EN 10028-7 or EN 10272 (BS 970 316/S16) Measuring points: AMETAL Sealing (measuring points): EPDM AMETAL is the dezinfication resistant alloy of TA. Marking: TA, MDFO, DN, PN, Charge No, flow direction arrow. DN 20-150 (PN 16): BS 7350.
General
Wafer pattern orifice for fixing between EN 1092, ISO 7005 (BS 4504) flanges. The measuring orifice fulfils the requirements of BS 1042: Section 1.1:1992 (ISO 5167-1:1991). The calculation of flow rates are according to BS 1042: Section 1.4:1992. Measuring points MDFO (52 176 and 52 276) with extended self-sealed measuring points.
Installation
Before you install the measuring orifice, check that: - it is clean and undamaged. - the surfaces that are to seal against are clean and undamaged. - there is enough straight pipe lengths before and after the measuring orifice. The measuring orifice should be installed betweeen two counter flanges. Check that these counter flanges are parallel and that the gaskets are according to given standard for flanges. Check also that the measuring orifice and the gaskets are correctly centred before tightening.
10 D
5D
Differential pressure measurement should take place with extreme care especially if this concerns hot media.
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
p [kPa]
q [l/s]
10
p [kPa]
q [l/s]
11
p [kPa]
q [l/s]
12
p [kPa]
q [l/s]
13
p [kPa]
q [l/s]
14
p [kPa]
q [l/s]
15
Articles
With self-sealed measuring points
PN 16
95 H
Article No
DN
Flange thickness 18 18 18 18 18 18 18 18 18 18 18 18 18 20 23 28 28 29 31 32 32 33
Kvmax 6 11 23 35 72 154 220 373 570 789 1383 2122 3116 4000 5300 6400 7950 10700 15000 17500 20300 26000
Kvsignal 4,68 8,64 16,6 24,5 46,1 90 120 220 342 468 792 1224 1800 2250 3000 3750 4500 6500 9000 10500 12000 15500
Kg
52 176-920 52 176-925 52 176-932 52 176-940 52 176-950 52 176-965 52 176-980 52 176-990 52 176-991 52 176-992 52 176-993 52 176-994 52 176-995 52 176-996 52 176-997 52 176-999 52 176-998 52 276-001 52 276-002 52 276-012 52 276-003 52 276-004 PN 25 Article No
20 25 32 40 50 65 80 100 125 150 200 250 300 350 400 450 500 600 700 750 800 900
63 73 84 94 109 127 142 162 192 218 273 329 384 444 496 556 618 735 805 865 911 1011
127 131 137 142 150 159 166 176 191 204 231 260 287 317 343 373 404 463 498 528 551 601
0,59 0,70 0,83 0,98 1,2 1,5 1,8 2,0 2,5 3,0 4,3 5,7 7,0 10 14 22 26 43 44 51 56 65
DN
Flange thickness 18 18 18 18 18 18 18 18
Kg
DN
Flange thickness 18 18 18 18 18 18 18 18 20 23 28
Kvmax 154 220 373 570 789 1383 2122 3116 4000 5300 6400
Kvsignal 90 120 220 342 468 792 1224 1800 2250 3000 3750
Kg
52 176-765 52 176-780 52 176-790 52 176-791 52 176-792 52 176-793 52 176-794 52 176-795 52 176-796 52 176-797 52 176-798
127 142 168 194 224 290 352 417 474 546 571
159 166 179 192 207 240 271 304 332 368 381
1,5 1,8 2,0 2,5 3,0 4,3 5,7 7,0 15,0 23,0 26,0
16
Commissioning set
COMMISSIONING SET This product, when combined with the STAF/STAF-SG balancing valve can be ordered as a commissioning set by the name of MDF4 or MDF4SG.
Accessories
Measuring points Max 120C (intermittent 150C)
Article No 52 179-014 52 179-015 L 44 103
Article No 52 179-016
d M14x1
L 71
The products, texts, photographs, graphics and diagrams in this brochure may be subject to alteration by TA Hydronics without prior notice or reasons being given. For the most up to date information about our products and specifications, please visit www.tahydronics.com.
5-30-5 UK MDFO 03.2011