Our Order No.4200059720 Current Transformers Guaranteed Technical Particulars
Our Order No.4200059720 Current Transformers Guaranteed Technical Particulars
Page 1 of 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Type Designation Standards applicable Construction of primary winding Rated Voltage (kV) Highest system voltage Rated frequency No. of phases Type of connection Short time thermal current withstand ability Dynamic current (kA peak) Switching surge withstand voltage (kV peak) Impulse withstand voltage (kV peak) One minute dry & wet power frequency withstand voltage(kV) Partial discharge level (pC) Radio Interference Voltage level at 1.1 Um/3 at 1.0 MHz Corona Inception voltage (kV) Corona Extinction voltage (kV) Material of Primary Winding One Minute Power Frequency withstand voltage on secondary (kV rms) Minimum Creepage distance Quantity of Oil/CT (litres) Total weight (kg) Temp. rise over an ambient temp.of 50 C temp. after passing short circuit current for 1 sec. Extended primary current
IMB 245 IS:2705/ IEC:60044-1 Hair pin 220/ 3 245 50 Hz Single Secondary Taps 50 kA for 1 sec. 125 NA 1050 460 < 5 at Um x 1.2/3, < 10 at Um (where Um is highest system voltage) < 2500 V >225 <156 Aluminum 3 Kv 25 mm/kV 310 1300 (Approx) Within limits of IS:2705/ IEC:60044-1
23
120%
Page 2 of 2
1 2 3 4 5