PVM9 Signal converter / power amplifier 32 W


The PVM9 proportional signal converter / power amplifier is used to drive magnetic valves from a DC 0 ...10 V or DC 0 ... 20 V phase cut control signal.

181

PVM9

Technical data
Power supply Supply voltage Max. tolerance Controller fuse Controller consumption Control voltage Output voltage Output power Connection terminals Protection class Protection standard Ambient temperature Operation Storage Weight (incl. packaging) Extra low voltage (SELV, PELV) AC 24 V, 50 ... 60 Hz +15 /10 % T 2 A (slow blow) max. 3 VA DC 0 ...10 V or DC 0 ... 20 V phase cut DC 0 ... 20 V phase cut 32 W max. Screw terminals for max. 2.5 mm2 wire II ( 1 ) IP30 to IEC529 0 ... 50 C 25 ... 50 C 0.66 kg

Warning Controller and power amplifier PVM9 must be supplied from the same phase Where the DC 0 ...10 V signal is derived from controllers, an isolated AC 24 V supply from a separate transformer must be provided Switch off electricity supply before removing the power amplifier or plugging it into the baseplate Do not touch the PCB. Electronic components can be damaged by electrostatic discharge.

Principle of operation
The PVM9 functions as a signal converter and / or power amplifier to give a phase cut output rated at 32 W (max.). There is provision for two alternative signal inputs: DC 0 ...10 V for the control of magnetic valves which can only accept a phase cut signal or DC 0 ... 20 V phase cut, for use when the total power required by the valve(s) exceeds the power rating of a controller having a phase cut output.

Construction, mounting and dimensions


See data sheet 5559

Siemens Building Technologies Landis & Staefa Division

CA1N5181E / 11.1998 1/2

Terminal layouts
PVM9 Control voltage DC 0 ...10 V
50280

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

DC 0 ...10 V

SGND Max. 32 W

AC 24 V, 50 ... 60 Hz

PVM9 Control voltage DC 0 ... 20 V phase cut


50535

Note: Links 3 to 10 and 8 to 26 to be made at time of installation.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

DC 0 ... 20 V phase cut

Max. 32 W

AC 24 V, 50 ... 60 Hz

twisted pairs

1998 Siemens Building Technologies Ltd. CA1N5181E / 11.1998 2/2 Siemens Building Technologies Landis & Staefa Division