13 FAB300-2 Blowdown Tanks

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

BLOWDOWN TANKS

INSTALLATION

The vessel should be installed with the flash steam outlet (5) at the top as shown.

DESIGN SPECIFICATIONS
Design Pressure: Design Temperature: Design Code: Max. Boiler Pressure: Material of Construction: 100 PSIG 450F ASME Sect VIII, Div. I, latest revision 600 PSIG Carbon Steel (optional stainless steel)

OPTIONAL ACCESSORIES

Self operating thermostatic cooling control valve Thermometer Vent Condenser

FEATURES
Internal weir assembly retains blowdown and allows it to cool to atmosphere, saving on cooling water. Baffled inlet extends tank life Standard inspection cover

Notes:

Dimensions can be modified to suit customer requirements. Larger sizes and selections for higher boiler pressures are available upon request

DIMENSIONS (All dimensions in inches)


Model BDT-15 BDT-50 BDT-100 BDT-200 BDT-400 BDT-750 BDT-3000 Nominal Boiler HP 5-15 26-50 51-100 101-200 201-400 401-750 751-3000 A 12 24 30 36 36 42 48 B 30 39 46 44 53 60 69 C 8 8 8 8 8 8 8 Inspect. Cover 1 4x6 4x6 12 x 16 12 x 16 12 x 16 12 x 16 12 x 16 Cold Water 2 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Drain 3 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 Inlet 4 1-1/2 1-1/2 2 2 2 2 2 Vent 5 3 3 4 4 4 4 4 Outlet 6 3 3 4 4 4 4 4 Therm. 7 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Temp. Sensor 8 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 Gauge Glass 9 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Weight (Lbs.) 230 441 661 772 904 1102 1433

Colton has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice

Tel: 1-888-300-9155 Fax: 1-888-300-9160

www.COLTONIND.com info@coltonind.com