ELECTRICAL TESTS for Automatic Transfer Switches Yes 1.

Perform insulation resistance tests phase to phase and phase to round with switch in !oth alternate and source positions. ". Set and cali!rate the #olta e Sensin rela$s. Chec% settin s complies with the pro&ect specifications '. Set and cali!rate the Transfer Time dela$ rela$. Chec% settin s complies with the pro&ect specifications (. Perform automatic transfer !$ simulatin loss of normal power. ). Perform automatic transfer !$ return to normal power. *. +onitor and ,erif$ correct operation and timin of Normal #olta e sensin rela$s. -. +onitor and ,erif$ correct operation and time dela$ upon transfer. .. +onitor and ,erif$ correct operation and timin of Alternate ,olta e sensin rela$s. /. +onitor and ,erif$ correct operation and timin of Automatic transfer operation. 10. +onitor and ,erif$ correct operation and timin of mechanical and electrical interloc%s and limit switches 11. +onitor and ,erif$ correct operation and timin 1 of time2dela$ and retransfer upon normal power restoration. No