S.O No.: Tpe-103 Customer: Unity Ivrcl

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Marketed by : TRANSFORMER ENGINEERING DEPARTMENT SCHEDULE OF TECHNICAL PARTICULARS FOR DISTRIBUTION TRANSFORMERS

Manufactured by :

TRANSFORMER DIV

For EMCO LTD Sheet : 01 of 02

S.O No.: TPE-103 SR. NO. 1 2 3 4 5 6 7 8 9 10 DESCRIPTION UNIT

CUSTOMER : Unity IVRCL PARTICULARS Marketed by EMCO Ltd, Mfg by : Telawne Power Equipments Pvt. Ltd for EMCO LTD Dry Type Transformer CRT OUTDOOR

Name of the manufacturer Type Service KVA Rating Rated No load Voltage Rated Frequency Number of Phases HV Winding LV Winding Connection Symbol Tapping Details i) Tapping Range ii) Number of steps iii) OLTC or Off Circuit Tap Switch Connections Winding Material
12 Type of Cooling 13 Maximum Temp. Rise in winding AL/CU

HV Winding LV Winding

kVA kV kV Hz

630 11 0.433 50
THREE

Delta Star Dyn11 +5% TO - 10% @ 2.5% 6


OCTC

11

COPPER

AN 90 1.60 Sub to IS tol

14

i) No Load Loss at rated voltage on principal tapping and at rated frequency ii) Load Loss at rated current at principal tapping, at rated frequency at 75 C HV LV voltage at

KW 6.00 KW % 5 Sub to IS tol Sub to IS tol

15

Marketed by : TRANSFORMER ENGINEERING DEPARTMENT SCHEDULE OF TECHNICAL PARTICULARS FOR DISTRIBUTION TRANSFORMERS

Manufactured by :

TRANSFORMER DIV

For EMCO LTD Sheet : 02 of 02

S.O No.: TPE-103 16

CUSTOMER : Unity IVRCL

17

18

Percentage Efficiency i) At 100% ii) At 75 % iii)At 50% iv) At 25% Percentage Regulation At 100% Insulation i) SeparateLevel source power frequency HV Winding voltage withstand LV Winding ii) Induced over voltage HV Winding withstand LV Winding iii) Impulse voltage withstand Terminal Arrangement HV Winding LV Winding High Voltage Low Voltage Approximate Weights Core and Winding Enclosure, Fittings and Accessories Total Weight

% % % % % kV rms kV rms kV rms kV rms kVp kVp

At unity p.f/0.8 p.f 98.809/98.515 98.959/98.701 99.026/98.785 98.762/98.457 Unity p.f / 0.8 p.f 1.073/3.764 28 3 2x Rated voltage at 100 Hz 2x Rated voltage at 100 Hz 75 NA CABLE BOX CABLE BOX

19

Kg (appx.) Kg (appx.) Kg (appx.)


LXBXH

2135 850 3000


2200 X 2600 X 2300

20

21 22 23

Approximate Overall dimensions Reference Standards Degree Of Protection

IS: 2026/11171 IP 54

Prepared by :

Checked by :

Authorised by :

Rev : R1

Date : 06.12.2012