Table 1: High Altitude De-Rating Factors: Form TN 1 2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Table 1: High Altitude De-rating Factors

Altitude

ANSI C37.40

IEC282-1.2

Dielectric
Strength Continuous
Ambient
Test Voltage Rated Voltage Continuous Allowable
Feet
Meters Correction
Current
Temperature
Ratio
Current
Temperature
Factor
Rating
Rise
3300
1000
1
1
1
1
1
1
1
4000
1200
0.98
0.99
0.992
*
*
*
*
5000
1500
0.95
0.99
0.980
1.05
0.95
0.99
0.98
6000
1800
0.92
0.98
0.968
*
*
*
*
7000
2100
0.89
0.98
0.956
*
*
*
*
8000
2400
0.86
0.97
0.944
*
*
*
*
9000
2700
0.83
0.96
0.932
*
*
*
*
10000
3000
0.80
0.96
0.920
1.25
0.8
0.96
0.92
12000
3600
0.75
0.95
0.896
*
*
*
*
14000
4300
0.70
0.93
0.872
*
*
*
*
16000
4900
0.65
0.92
0.848
*
*
*
*
18000
5500
0.61
0.91
0.824
*
*
*
*
20000
6100
0.56
0.90
0.800
*
*
*
*
* Intermediate de-rating factors can be determined by interpolation